Product Model: AH12H15D5B
Dimensions and Installation Information:
- Wall Case Dimensions:
- A: 30 inches
- C: 70 inches
- Maximum Cord Extension: 30 inches
- Wall Opening Dimensions: Add 1/4 to A and C dimensions for all cut-outs. RAB80 16-1/4 Min. H x 42-1/4 Min. W
AH12 ELECTRIC HEATER 230/208 VOLT LINE CORD CONNECTED UNITS:
- Heater Watts: 5,000 / 4,100
- Heater BTU: 15,000 / 12,200
- Heater Amps: 22.3 / 20.1
- Min Circuit: 30
- Recommended Protective Device: 30 amp time-delay fuse or breaker
AH12 HEAT PUMP:
- Heat Pump Watts: 1180 / 1120
- Heat Pump BTU: 13,400 / 13,100
- COP: 3.2
Product Usage Instructions
To install the AH12H15D5B unit, follow these steps:
- Measure and mark the wall opening dimensions, adding an extra 1/4 inch to the A and C dimensions for all cut-outs.
- Ensure the wall case dimensions match the specified dimensions for the unit.
- Connect the line cord to a 230/208 volt power source.
- For electric heating, ensure the unit is connected to a circuit with a minimum rating of 30 amps.
- Install a 30 amp time-delay fuse or breaker as the recommended protective device.
- If using the AH12 as a heat pump, connect it to a power source with the appropriate wattage and voltage.
- Refer to the product manual for further instructions on configuring and operating the AH12H15D5B unit.
DIMENSIONS AND INSTALLATION INFORMATION
WALL CASE DIMENSIONS
RAB80 WALL SLEEVE Heavy-gauge galvanized steel, with insulation, for quick
self-assembly. A – 42”, B – 13-3/4”, C – 16”
MAXIMUM CORD EXTENSION
WALL OPENING DIMENSIONS Add 1/4” to A and C dimensions for all cut-outs. RAB80
16-1/4” Min. H x 42-1/4” Min. W
ELECTRICAL WIRING
All wiring, including installation of receptacle, must be made in accordance
with local electrical codes and regulations.
NOTE : Aluminum wiring may pose special problems – consult a qualified
electrician.
GRILLE OPTIONS
- Stamped Aluminum Grille – RAG70
ELECTRICAL CONNECTION
- 230/208 volt units must be plugged into a receptacle. Installation must comply with local electrical codes and regulations.
- Power cord is permanently attached on all Hotpoint chassis
SPECIFICATION
AH12 ELECTRIC HEATER
230/208 VOLT| LINE CORD CONNECTED UNITS
Heater Watts| 5,000 / 4,100
Heater BTU| 15,000 / 12,200
Heater Amps| 22.3 / 20.1
Min Circuit| 30
Recommended protective Device| 30 amp time-delay fuse or breaker
AH12 HEAT PUMP
Heat Pump Watts| 1180 / 1120
Heat Pump BTU| 13,400 / 13,100
COP| 3.2
FEATURE AND BENEFITS
- 14,800 / 14,600 cooling BTU
- 10.6 EER
- 13,400 / 13,100 heating BTU
- 3.2 COP
- R32 Refrigerant – Environmental friendly, low GWP (Global Warming Potential)
- 3-Speed Fan – Give guests control over their comfort with three fan speeds to choose from
- 4-Temperature Limiting Options – Easily select one of four temperature ranges for peak efficiency and total customer comfort
- Intuitive Display – Allow guests to easily customize their preferred settings and reduce maintenance calls with an easy-to-use control panel
- Power Cord (LCDI) Included – Hotpoint PTACs come with everything needed for a quick and easy installation
- Automatic Emergency Heat – Keep guests comfortable with a heating option that uses electric resistance heat in heat pump mode
- Freeze and Frost Protection – Automatic freeze and indoor frost control keep units operating in peak condition
- Auto Power Recovery – In case of power failures, units automatically resume their operation when power restores, reducing maintenance calls
- Self Diagnostics – Quickly and easily identify service needs with a nine-point diagnostic code system
- Backed by an Industry Leader – With a long history of creating durable products at an affordable price, Hotpoint is your trusted PTAC brand
PRELIMINARY SPECIFICATIONS – SUBJECT TO CHANGE
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>