magicpak M-Series Electric Heat Packaged Unit User Guide
- June 12, 2024
- magicpak
Table of Contents
- magicpak M-Series Electric Heat Packaged Unit User Guide
- APPLICATIONS
- UNIT APPROVALS
- ETL (INTERTEK)
- AHRI/DOE
- CORROSION PROTECTION
- SOUND RATING
- ALUMINUM LOUVER – PAINT SPECS
- WARRANTY
- ALL OTHER COVERED COMPONENTS
- STANDARD FEATURES
- AIRFLOW CHOICE
- ELECTRICAL CONNECTIONS & GAUGE PORTS
- CABINET
- INTERNAL FILTER
- VENTILATION AIR
- REFRIGERATION SYSTEM
- Indoor and Outdoor Coils
- High Pressure Switch
- Low Pressure Switch
- Reversing Valve
- Defrost Control
- Low Ambient Operation
- TRANSFORMER
- SUPPLY AIR BLOWER
- Electronic Blower Control
- OUTDOOR FAN
- CONDENSATE MANAGEMENT
- Overflow Protection
- Secondary Drain Pan
- _OPTIONS & ACCESSORIES _FACTORY-INSTALLED OPTIONS
- ELECTRIC HEAT
- CORROSION PROTECTION
- FIELD-INSTALLED ACCESSORIES
- WALL SLEEVES & LOUVERS
- WALL SLEEVES (ASLEEVE)
- WALL SLEEVE EXTENSION (ASLEEVEXT4)
- LOUVERS
- Aluminum Louvers (ALVRAL)
- Impact-Resistant Aluminum Louvers (ALVRALC)
- CRANKCASE HEATER (ACASE841)
- SHORT CIRCUIT CURRENT RATING KIT (ASCCR)
- FILTERS
- VENTILATION DAMPERS
- Motorized Damper w/ Controller (AVADAMP1)
- Motorized Damper w/ Field-Supplied Relay (AVADAMP2)
- THERMOSTAT
- UNIT ELECTRICAL AND PHYSICAL DATA (208/230 Volt – 1 Phase – 60HZ)1
- UNIT DIMENSIONS (IN.)
- MINIMUM CLEARANCES
- Accessibility Clearances
- Supply Duct Clearances
- OUTDOOR SOUND RATING & CABINET AIR LEAKAGE
- __ FACTORY FILTER SIZE (IN.) AND PRESSURE DROP (IN. W.C.)
- VENTILATION AIR CAPABILITY
- 1 thru #2| 10| 15| 20| 24| 28
- 1 thru #3| 12| 18| 25| 32| 38
- 1 thru #4| 18| 28| 36| 45| 54
- 1 thru #5| 23| 35| 46| 57| 69
- 1 thru #6| 27| 41| 54| 67| 80
- 1 thru #7| 32| 48| 63| 78| 93
- 1 thru #8| 37| 55| 73| 90| 107
- 1 thru #9| 41| 61| 80| 100| 118
- WALL SLEEVES & LOUVERS
- WALL SLEEVE & WALL OPENING DIMENSIONS (IN.)
- SCCR ACCESSORY
- CRANKCASE HEATER
- RATED COOLING & HEATING PERFORMANCE
- EXTENDED HEATING PERFORMANCE DATA (HEAT PUMP ONLY)
- EXTENDED HEATING PERFORMANCE DATA (HEAT PUMP ONLY)
- __ COMBINED EXTENDED HEATING PERFORMANCE DATA (HEAT PUMP + ELECTRIC
- COMBINED EXTENDED HEATING PERFORMANCE DATA (HEAT PUMP + ELECTRIC HEAT) 1
- BLOWER PERFORMANCE
- Read More About This Manual & Download PDF:
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
magicpak M-Series Electric Heat Packaged Unit User Guide
APPLICATIONS
- MagicPak units are designed for use in all multifamily applications, such as: apartments, condominiums, student housing and senior living
- Installation in conditioned and non-conditioned mechanical spaces
UNIT APPROVALS
ETL (INTERTEK)
- Design certified by ETL (Intertek) to latest edition of UL 1995
- Certified for the S. and Canada
- Certified for less than 4% cabinet air leakage using ASHRAE Standard 193
- Factory-installed electric heaters are ETL listed for the S. and Canada
- Rated with a 5kA Short Circuit Current Rating (SCCR) in accordance with RMS Symmetrical per UL 508A
- Refer to Unit Electrical and Physical Data table for additional details
AHRI/DOE
- Certified to AHRI Standard 210/240-2008; refer to the AHRI Directory for AHRI certificates
- Rated and tested in accordance with DOE test procedures (latest edition) and Federal Trade Commission (FTC) labeling regulations
CORROSION PROTECTION
- Epoxy coating is specifically designed for use on HVAC type coils and demonstrates 6800+ hours of Sea Water Acetic Acid Testing (SWAAT) per ASTM G85:A3
SOUND RATING
- Outdoor sound level measurements tested per ANSI/AHRI Standard 270
- Refer to Outdoor Sound Rating & Cabinet Air Leakage table for additional details
ALUMINUM LOUVER – PAINT SPECS
- Standard and impact-resistant louvers meet AAMA 2605 specifications
WARRANTY
COMPRESSOR
- Five (5) years limited parts warranty
ALL OTHER COVERED COMPONENTS
- Refer to Equipment Limited Warranty for additional details
STANDARD FEATURES
AIRFLOW CHOICE
-
Factory shipped ready for top supply and return duct connections
-
Return air may be brought in through the optional front return opening
NOTE : If ductwork is attached to the optional front return opening, provisions to service unit filter must be provided
NOTE : Filter may need to be relocated to a suitable location outside the cabinet for ease of service -
Ducted or free/non ducted return configuration, which may utilize the top or front as return points
-
Front access panel doubles as cover for top return (except 0 ton)
ELECTRICAL CONNECTIONS & GAUGE PORTS
- Line voltage knockouts (two concentric) to accommodate field required wire size
- Thermostat connections are located at the top of the cabinet
- Two gauge ports are located within the lower compartment of the unit
- Refer to Unit Dimension figure for additional details
CABINET
- Embossed galvanized steel cabinet
- Indoor section of the cabinet insulated with 5 in. dual density fiberglass insulation
- Outdoor section of the cabinet insulated with 5 in. weather-resistant polystyrene insulation
INTERNAL FILTER
- Tool-less filter access
- Factory-installed 1 filter rack with washable filter
- Field-supplied filters up to MERV 6 can typically be installed in the filter slot internal to unit in lieu of washable filter, when proper duct design is applied
- If a higher resistance filter is field installed in the unit, the added resistance must be included in the external static pressure and must not exceed 5 in. w.c. including ductwork
- Refer to Factory Filter Size and Pressure Drop and Blower Performance tables for additional details
VENTILATION AIR
- Units are outfitted with ventilation air openings and are shipped with the openings sealed
- Refer to Ventilation Air Capability table and Optional Field-Installed Accessories section for additional details
- Check that equipment complies with all applicable building codes, laws, and regulations for its intended use prior to installation
REFRIGERATION SYSTEM
- Factory charged with R-410A refrigerant
- Factory sealed and tested
- Refer to Unit Electrical and Physical Data table for additional details
Indoor and Outdoor Coils
- Copper tube with aluminum fin coils
High Pressure Switch
- Shuts off unit if abnormal operating conditions cause the refrigerant discharge pressure to rise above acceptable levels
Low Pressure Switch
- Provides loss of charge protection by shutting off unit if refrigerant liquid pressure falls below acceptable levels
Reversing Valve
- Reverses the direction of refrigerant flow within the unit’s refrigeration circuit, to change between cooling and heating operation
- Reverses refrigerant flow direction during heat pump defrost cycles to clear outdoor coil of frost buildup
Defrost Control
- Factory mounted sensor determines when defrost cycle starts and ends
- Anti-short cycle, timed-off control (field- adjustable to 30-90 minutes) is incorporated in the control board
- The time between defrost cycles is preset at 90-minute intervals at the factory, but can be field adjusted to 30 or 60 minutes
Low Ambient Operation
- Units are not equipped with low ambient compressor cutoffs and can be safely operated to -5°F outdoor ambient temperatures
- Refer to Extended Heating Performance Data tables for performance data starting at 0°F outdoor ambient temperature
TRANSFORMER
- Rated for 40VA
- Factory wired for 230/240V power supply, and includes field selectable terminal for 208V
- Converts line voltage to 24V for the thermostat and control circuits within the unit
SUPPLY AIR BLOWER
Constant Torque ECM Blower Motor
- Motor provides specified air volume at 1 in. – 0.5 in. w.c. external static pressure
- Blower assembly is easily removed for servicing
- Refer to Blower Performance tables for additional details
Electronic Blower Control
- Dedicated blower speed taps for continuous fan, cooling, and heating operation are programmed for optimal airflow and controlled by 24V thermostat signals
- Blower speed adjustment is easily accomplished by speed tap selection
- Fixed blower delays have been selected to enhance comfort
- Refer to Blower Performance tables for additional details
OUTDOOR FAN
- Heavy duty, fully enclosed and weatherproof
- Aluminum fan blades
CONDENSATE MANAGEMENT
Primary Drain Pan
- Antimicrobial protection: drain pan is injected with an antibacterial agent that destabilizes the membrane of microorganism cells, disrupting the cellular function of odor-causing mold and bacteria so that they can no longer grow or reproduce
Overflow Protection
- Indoor drain pan overflow switch monitors the condensate level in primary drain pan
- Prevents unit from running if water is sensed
Secondary Drain Pan
- Polypropylene wall sleeve base is specifically designed to direct rain water out of the building and in the event of any restriction in the primary drain will act as a redundant overflow protection
_OPTIONS & ACCESSORIES _FACTORY-INSTALLED OPTIONS
ELECTRIC HEAT
- Mounted internal to unit cabinet
- Multiple kW sizes available; must specify the electric heating element size (3kW to 10kW)
- Optional two stage electric heat wiring on 7 & In order to utilize this option, it will require a thermostat with single stage cooling and two stage heating
- Compatible with 208V, 230V and 240V
- Helix wound nichrome heating elements exposed directly into the air stream resulting in instant heat transfer and low element temperatures
- Cutoff limit control provides positive protection in case of excessive temperatures
- Refer to Rated Cooling & Heating Performance table for additional details
CORROSION PROTECTION
- Epoxy coated indoor and outdoor coils
FIELD-INSTALLED ACCESSORIES
WALL SLEEVES & LOUVERS
- Units must be installed with approved wall sleeve and louver accessories for safe operation and are required for all installations
- Larger height wall sleeves may be used on smaller tonnage equipment to maintain a uniform wall opening on the building façade
- Refer to Wall Sleeves and Louvers table for additional details
WALL SLEEVES (ASLEEVE)
- Penetrates the building envelope and creates a path for condenser air intake and exhaust
- Provides a sealed connection to the unit and a secure attachment foundation for the louvers
- Available in 6 to 12 in. depths
WALL SLEEVE EXTENSION (ASLEEVEXT4)
- Provides an additional 4 of depth to the wall sleeve, for a maximum depth of 16 in.
LOUVERS
Polypropylene Louvers (ALVRP)
- Constructed from durable, corrosion-resistant plastic
- Available in four standard colors
Aluminum Louvers (ALVRAL)
- Constructed with 6063-T6 grade aluminum
- Available in anodized clear coat, primer (to be painted in the field), standard paint colors and custom colors with paint matching*
Impact-Resistant Aluminum Louvers (ALVRALC)
- Impact and wind load certified up to 186 MPH, risk categories III and IV, and wind exposures C and D
- ALVRALC-1 & ALVRALC-2: FBC Notice of Acceptance (NOA) 20-0909.03
- ALVRALC-3, -4 & -7: FBC Notice of Acceptance (NOA) 21-1216.11
- Constructed with 6063-T6 grade aluminum
- Available in anodized clear coat, primer (to be painted in the field), standard paint colors and custom colors with paint matching*
CRANKCASE HEATER (ACASE841)
- Warms compressor crankcase to limit migration of liquid refrigerant back to compressor during off cycle
- Available for models with scroll compressors
- Refer to Crankcase Heater table for additional details
SHORT CIRCUIT CURRENT RATING KIT (ASCCR)
- Provides 200kA of SCCR protection
- Refer to SCCR Accessory table for additional details
FILTERS
- Field-supplied filters up to MERV 6 can typically be installed in the filter slot internal to unit NOTE : Use of paper frame not recommended
VENTILATION DAMPERS
- Check that the equipment complies with all applicable building codes, laws, and regulations for its intended use prior to installation
Motorized Damper w/ Controller (AVADAMP1)
- Utilizes a ventilation air control module that is field programmable to assist with meeting ASHRAE 2 requirements
- Once programmed with values for ventilation air amounts, the control module opens the damper in response to thermostat inputs and monitors the run time
- Upon meeting the ventilation air needs, the control module will close the damper until the start of the next cycle
- If, during an observation period it is determined that thermostat operation alone may not provide the desired ventilation air, the control module can independently operate the unit’s indoor blower, in continuous fan mode, and open the damper to aid in providing ventilation air needs
Motorized Damper w/ Field-Supplied Relay (AVADAMP2)
- Opens ventilation air damper during indoor blower operation and closes during blower off periods
- Requires field-supplied and installed current sensing relay to detect indoor blower operation
THERMOSTAT
- Required for all installations (field-supplied)
- Units are individually controlled with conventional 24V thermostat
- Thermostat must be capable of:
- Single stage cooling, single stage heat pump operation (compressor heating), and single stage electric heat (3 and 5 kW)
- Single stage cooling, single stage heat pump operation (compressor heating), and two stage electric heat (7 and 10 kW)
- Refer to Unit Electrical and Physical Data table for additional details
* Certain exclusions apply. Refer to louver manufacturer’s literature and warranty documentation.
UNIT ELECTRICAL AND PHYSICAL DATA (208/230 Volt – 1 Phase – 60HZ)1
Model
|
MCA2
|
MOCP3.
| Default SCCR (kA)4|
Compressor
|
Outdoor Fan
|
Indoor Blower
| R-410A Refrigerant Charge (oz)| Approx. Shipping Weight (lbs)
---|---|---|---|---|---|---|---|---
Circuit 15| Circuit 25| Circuit 15| Circuit 25| Rated Load Amps (RLA)| Locked
Rotor Amps (LRA)| Dia. (in)|
Nominal RPM
| Rated Load Amps (RLA)| Rated HP| Wheel D x W (in.)| Rated Load Amps (RLA)| Rated HP
208V
|
230V
|
208V
|
230V
|
208V
|
230V
|
208V
|
230V
3MHP4-12-091*P| 23.0| 25.5| —| —| 25| 30| —| —|
5
|
4.4
|
21
|
16
|
1100
|
0.9
|
1/8
|
9 x 6
|
0.4
|
1/3
|
44
|
192
5MHP4-12-091P| 28.4| 31.8| —| —| 30| 35| —| —
3MHP4-12-121P|
24.2
|
26.7
|
—
|
—
|
25
|
30
|
—
|
—
|
5
|
5.1
|
27
|
16
|
1125
|
0.9
|
1/8
|
9 x 6
|
0.6
|
1/3
|
44
|
202
5MHP4-12-121P| 29.6| 32.9| —| —| 30| 35| —| —
3MHP4-12-181P| 26.6| 29.1| —| —| 30| 30| —| —|
5
|
6.7
|
37.5
|
16
|
1125
|
0.9
|
1/8
|
9 x 6
|
1
|
1/3
|
70
|
219
5MHP4-12-181P| 32.0| 35.3| —| —| 35| 40| —| —
7MHP4-12-181P| 42.8| 47.8| —| —| 45| 50| —| —
10MHP4-12-181P| 10.3| 10.3| 43.3| 50.0| 15| 15| 45| 50
5MHP4-12-241P| 37.4| 40.8| —| —| 40| 45| —| —|
5
|
10
|
52
|
18
|
1100
|
1.6
|
1/4
|
9 x 6
|
1.6
|
1/3
|
83
|
268
7MHP4-12-241P| 48.3| 53.3| —| —| 50| 60| —| —
10MHP4-12-241P| 15.8| 15.8| 43.3| 50.0| 25| 25| 45| 50
5MHP4-12-301*P| 41.9| 45.2| —| —| 50| 50| —| —|
5
|
13.4
|
72.5
|
18
|
1100
|
1.6
|
1/4
|
10 x 8
|
1.8
|
1/2
|
78
|
271
7MHP4-12-301P| 20.2| 20.2| 32.5| 37.5| 30| 30| 35| 40
10MHP4-12-301P| 20.2| 20.2| 43.3| 50.0| 30| 30| 45| 50
5MHP4-14-361*P| 45.6| 48.9| —| —| 50| 50| —| —|
5
|
14.7
|
75
|
18
|
1060
|
2.8
|
1/3
|
10 x 8
|
2.8
|
1/2
|
91
|
299
7MHP4-14-361P| 23.9| 23.9| 32.5| 37.5| 35| 35| 35| 40
10MHP4-14-361P| 23.9| 23.9| 43.3| 50.0| 35| 35| 45| 50
1 Acceptable voltage range 197 – 253V 2 MCA = Minimum Circuit Ampacity
- MOCP = Maximum Over Current Protection
- SCCR = Short Circuit Current Rating; refer to SCCR Accessory table, up to 200kA
- Circuits 1 and 2 are independent sets of power wires being run to the unit, each backed by an independent circuit Units with dual circuits use Circuit 2 exclusively to power electric heaters. Refer to wiring diagram for additional details.
NOTE: Units are rated at 208/230V, but MOCP & MCA values are calculated at
240V
NOTE: The 7.2 and 10 kW heats strips offer a W1 and W2 thermostat
connection. Taking advantage of the two heat strip circuits requires a 3-stage
thermostat (Y for heat pump, W1 for electric heat stage 1, and W2 for electric
heat stage 2). If a 2-stage thermostat is used, “pigtail” W1 and W2 wires
together when connecting the thermostat wires at the unit.
UNIT DIMENSIONS (IN.)
Model | A | B* | C | D | E | F | G | H | J | K | L | M | N |
---|
MHP4-12-091P
MHP4-12-121P
| 43-7/8| 16-7/8| 25-1/4| 21-1/2| 18-5/8| 19-1/4| 6| 8| 16| 17-1/16| 3/4|
2-1/4| 24-5/8
MHP4-12-181P| 47-7/8| 18-7/8| 27-1/4| 21-1/2| 20-5/8| 21-1/4| 6| 8| 16| 17-1/16| 3/4| 2-1/4| 26-5/8
MHP4-12-241P| 55-7/8| 22-7/8| 31-1/4| 24-3/8| 24-5/8| 25-1/4| 6| 8| 16| 22-7/16| 3/4| 1| 30-5/8
MHP4-12-301P| 55-7/8| 22-7/8| 31-1/4| 24-3/8| 24-5/8| 25-1/4| 6| 11-3/8| 10-7/16| 22-7/16| 3-3/4| 1| 30-5/8
MHP4-14-361P| 67-7/8| 26-7/8| 35-1/4| 24-3/8| 28-5/8| 29-1/4| 10| 11-3/8| 10-7/16| 22-7/16| 3-3/4| 1| 38-5/8
Provisions must be made to properly drain condensate from the primary and secondary drain pans.
MINIMUM CLEARANCES
Accessibility Clearances
The front of the unit must be accessible for service. A minimum clearance of
30” in front of unit is required for service.
If the unit is enclosed, a door or access panel aligned with the front of the
unit is the preferred method of providing access. The door or access panel
opening must be a minimum of 30” wide (centered on the unit) and be as tall as
the unit.
IMPORTANT
The unit must be installed with approved wall sleeve and louver accessories for safe operation. Improper installations could result in property damage, personal injury, or death.
Supply Duct Clearances
Minimum Clearances to Combustible Materials 1
Front| Sides| Top
0”| 0”| 0”
Unit Clearances | Minimum Clearances 1 |
---|---|
Return Duct Configuration | Unit Height |
Ducted Top Opening | All |
Ducted Front Opening5 | All |
Non-Ducted/ Free Return | 43” |
48” – 68” | 5” |
OUTDOOR SOUND RATING & CABINET AIR LEAKAGE
Model | Outdoor Sound Rating (dBa)1 | Cabinet Air Leakage (%)2 |
---|---|---|
MHP4-12-091P | 73 | 1.4 |
MHP4-12-121P | 73 | 1.4 |
MHP4-12-181P | 73 | 1.4 |
MHP4-12-241P | 79 | 1.4 |
MHP4-12-301P | 79 | 1.4 |
MHP4-14-361P | 79 | 1.4 |
1 Per ANSI / AHRI Standard 270 2 Per ASHRAE Standard 193
__ FACTORY FILTER SIZE (IN.) AND PRESSURE DROP (IN. W.C.)
Model
| ****
Filter Size
| Supply Airflow (CFM)
---|---|---
200| 300| 400| 500| 600| 700| 800| 900| 1000| 1100| 1200| 1300
MHP4-12-091P
MHP4-12-121P
| 18 x 20 x 1| 0.01| 0.01| 0.01| 0.02| 0.03| 0.04| —| —| —| —| —| —
MHP4-12-181P| 20 x 20 x 1| —| 0.01| 0.01| 0.02| 0.02| 0.03| 0.04| —| —| —| —| —
MHP4-12-241P
MHP4-12-301P
| 24 x 22 x 1| —| —| —| 0.01| 0.01| 0.02| 0.03| 0.03| 0.04| 0.05| —| —
MHP4-14-361P| 28 x 22 x 1| —| —| —| —| 0.01| 0.01| 0.02| 0.02| 0.03| 0.03| 0.04| 0.04
Performance based on factory-provided washable filter installed in the unit. If a higher resistance filter is field installed in the unit, the added resistance must be included in the external static pressure and must not exceed 0.5 in. w.c. including ductwork.
VENTILATION AIR CAPABILITY
Chart and figure below show the amount of ventilation air as a function of unit tonnage and total External Static Pressure (supply and return).
Ventilation Air (CFM) * | |
---|---|
Cumulative Knockouts Removed | Total External Static Pressure (supply + return) |
**
0.1| 0.2| 0.3| 0.4| 0.5
0.75, 1.0, 1.5 TON| # 1 Only| 7| 9| 12| 15| 18
1 thru #2| 10| 15| 20| 24| 28
1 thru #3| 12| 18| 25| 32| 38
1 thru #4| 18| 28| 36| 45| 54
1 thru #5| 23| 35| 46| 57| 69
1 thru #6| 27| 41| 54| 67| 80
1 thru #7| 32| 48| 63| 78| 93
1 thru #8| 37| 55| 73| 90| 107
1 thru #9| 41| 61| 80| 100| 118
2.0, 2.5, 3.0 TON | # 1 Only | 21 | 20 | 19 | 17 | 16 |
---|---|---|---|---|---|---|
#1 thru #2 | 28 | 27 | 25 | 24 | 22 | |
#1 thru #3 | 35 | 33 | 32 | 30 | 28 | |
#1 thru #4 | 45 | 42 | 40 | 38 | 35 | |
#1 thru #5 | 55 | 52 | 49 | 46 | 43 | |
#1 thru #6 | 66 | 62 | 59 | 55 | 52 | |
#1 thru #7 | 79 | 75 | 71 | 66 | 62 | |
#1 thru #8 | 91 | 86 | 81 | 76 | 71 | |
#1 thru #9 | 105 | 99 | 94 | 88 | 82 |
* Assumes proper speed tap adjustments to maintain nominal supply air CFM
** Assumes equal supply and return static pressures
WALL SLEEVES & LOUVERS
Wall Sleeves
| ****
Louvers
| ****
Model
| Dimensions (in.)
---|---|---|---
Wall Sleeve| Wall Opening
Wall Sleeve
| ****
Wall Sleeve Extension
| ****
Polypropylene Louvers
| ****
Aluminum Louvers
| ****
Impact Louvers
| MHP4-12-091P| MHP4-12-121P| MHP4-12-181P| MHP4-12-241P| MHP4-12-301P| MHP4-14-361P| ****
Height (A)
| ****
Height (B)
| Depth (C)
Sleeve Only
| Sleeve Plus Extension
ASLEEVE6-1| —| ALVRP-1| ALVRAL-1^| ALVRALC-1^| •| •| •| | | | 29|
29-1/8| 6| —
ASLEEVE8-1| —| ALVRP-1| ALVRAL-1^| ALVRALC-1^| •| •| •| | | | 29|
29-1/8| 8| —
ASLEEVE10-1| ASLEEVEXT4-1| ALVRP-1| ALVRAL-1^| ALVRALC-1^| •| •| •| | |
| 29| 29-1/8| 10| 14
ASLEEVE12-1| ASLEEVEXT4-1| ALVRP-1| ALVRAL-1^| ALVRALC-1^| •| •| •| | |
| 29| 29-1/8| 12| 16
ASLEEVE6-2| —| ALVRP-2| ALVRAL-2^| ALVRALC-2^| | | | •| •| | 32-3/4|
32-7/8| 6| —
ASLEEVE8-2| —| ALVRP-2| ALVRAL-2^| ALVRALC-2^| | | | •| •| | 32-3/4|
32-7/8| 8| —
ASLEEVE10-2| ASLEEVEXT4-2| ALVRP-2| ALVRAL-2^| ALVRALC-2^| | | | •| •|
| 32-3/4| 32-7/8| 10| 14
ASLEEVE12-2| ASLEEVEXT4-2| ALVRP-2| ALVRAL-2^| ALVRALC-2^| | | | •| •|
| 32-3/4| 32-7/8| 12| 16
ASLEEVE6-2| —| ALVRP-2| ALVRAL-7^| ALVRALC-7^| ○| ○| ○| | | | 32-3/4|
32-7/8| 6| —
ASLEEVE8-2| —| ALVRP-2| ALVRAL-7^| ALVRALC-7^| ○| ○| ○| | | | 32-3/4|
32-7/8| 8| —
ASLEEVE10-2| ASLEEVEXT4-2| ALVRP-2| ALVRAL-7^| ALVRALC-7^| ○| ○| ○| | |
| 32-3/4| 32-7/8| 10| 14
ASLEEVE12-2| ASLEEVEXT4-2| ALVRP-2| ALVRAL-7^| ALVRALC-7^| ○| ○| ○| | |
| 32-3/4| 32-7/8| 12| 16
ASLEEVE6-5| —| ALVRP-3| —| —| ○| ○| ○| ○| ○| •| 45| 45-1/8| 6| —
ASLEEVE8-5| —| ALVRP-3| —| —| ○| ○| ○| ○| ○| •| 45| 45-1/8| 8| —
ASLEEVE10-5| ASLEEVEXT4-3| ALVRP-3| —| —| ○| ○| ○| ○| ○| •| 45| 45-1/8| 10|
14
ASLEEVE12-5| ASLEEVEXT4-3| ALVRP-3| —| —| ○| ○| ○| ○| ○| •| 45| 45-1/8| 12|
16
ASLEEVE6-5| —| —| ALVRAL-3^| ALVRALC-3^| ○| ○| ○| | | | 45| 45-1/8| 6| —
ASLEEVE8-5| —| —| ALVRAL-3^| ALVRALC-3^| ○| ○| ○| | | | 45| 45-1/8| 8| —
ASLEEVE10-5| ASLEEVEXT4-3| —| ALVRAL-3^| ALVRALC-3^| ○| ○| ○| | | | 45|
45-1/8| 10| 14
ASLEEVE12-5| ASLEEVEXT4-3| —| ALVRAL-3^| ALVRALC-3^| ○| ○| ○| | | | 45|
45-1/8| 12| 16
ASLEEVE6-5| —| —| ALVRAL-4^| ALVRALC-4^| | | | ○| ○| •| 45| 45-1/8| 6| —
ASLEEVE8-5| —| —| ALVRAL-4^| ALVRALC-4^| | | | ○| ○| •| 45| 45-1/8| 8| —
ASLEEVE10-5| ASLEEVEXT4-3| —| ALVRAL-4^| ALVRALC-4^| | | | ○| ○| •| 45|
45-1/8| 10| 14
ASLEEVE12-5| ASLEEVEXT4-3| —| ALVRAL-4^| ALVRALC-4^| | | | ○| ○| •| 45|
45-1/8| 12| 16
Note: Wall Sleeve and Louver size must be coordinated
*** Louver colors: WHT = white, SAN = sandstone, BGE = beige, TPST = taupestone
^ -P: Option to paint standard, aluminum, and impact-resistant louver
- Wall sleeve and louver sizes equal to the required wall opening dimensions for the unit size
- Optional: Wall sleeves and louvers can be oversized to maintain a uniform appearance
WALL SLEEVE & WALL OPENING DIMENSIONS (IN.)
SCCR ACCESSORY
Model | Kit1 |
---|---|
3MHP4-12-091*P | ASCCR2 |
5MHP4-12-091*P | ASCCR3 |
3MHP4-12-121*P | ASCCR2 |
5MHP4-12-121*P | ASCCR3 |
3MHP4-12-181*P | ASCCR2 |
5MHP4-12-181*P | ASCCR3 |
7MHP4-12-181*P | ASCCR4 |
10MHP4-12-181*P | ASCCR6 |
5MHP4-12-241*P | ASCCR4 |
7MHP4-12-241*P | ASCCR5 |
10MHP4-12-241*P | ASCCR7 |
5MHP4-12-301*P | ASCCR4 |
7MHP4-12-301*P | ASCCR8 |
10MHP4-12-301*P | ASCCR7 |
5MHP4-14-361*P | ASCCR4 |
7MHP4-14-361*P | ASCCR9 |
10MHP4-14-361*P | ASCCR10 |
CRANKCASE HEATER
Model | Kit |
---|---|
MHP4-12-091P | **** |
N/A
MHP4-12-121P
MHP4-12-181P
MHP4-12-241P| ****
ACASE841
MHP4-12-301P
MHP4-14-361P
RATED COOLING & HEATING PERFORMANCE
Model
| Cooling| Heating| Electric Heat|
---|---|---|---|---
Net Capacity (Btu/hr)
| Efficiency| ****
S/T^
| 47°F| 240V| 230V| 208V|
Net Capacity (Btu/hr)| Efficiency (HSPF / HSPF2)| ****
kW
| ****
BTU/hr
| ****
kW
| ****
BTU/hr
| ****
kW
| ****
BTU/hr
|
SEER / EER| SEER2 / EER2|
3MHP4-12-091*P| ****
8,600 /
8,600
| ****
12.0 / 11.0
| ****
11.9 / 10.5
| ****
0.79
| ****
8,600
| ****
7.4 / 6.3
| 3.60| 12,284| 3.31| 11,281| 2.70| 9,226|
5MHP4-12-091P| 4.80| 16,378| 4.41| 15,042| 3.61| 12,302|
3MHP4-12-121P| ****
12,000 /
12,000
| ****
12.5 / 11.0
| ****
11.9 / 10.5
| ****
0.79
| ****
11,400
| ****
7.4 / 6.3
| 3.60| 12,284| 3.31| 11,281| 2.70| 9,226|
5MHP4-12-121P| 4.80| 16,378| 4.41| 15,042| 3.61| 12,302|
3MHP4-12-181P| ****
16,500 /
16,500
| ****
12.0 / 11.0
| ****
11.9 / 10.0
| ****
0.77
| ****
16,200
| ****
7.4 / 6.3
| 3.60| 12,284| 3.31| 11,281| 2.70| 9,226|
5MHP4-12-181P| 4.80| 16,378| 4.41| 15,042| 3.61| 12,302|
7MHP4-12-181P †| 7.20| 24,567| 6.61| 22,563| 5.41| 18,453|
10MHP4-12-181P †| 9.60| 32,757| 8.82| 30,084| 7.21| 24,604|
5MHP4-12-241P| ****
22,800 /
22,800
| ****
13.0 / 11.0
| ****
11.9 / 10.5
| ****
0.76
| ****
22,800 /
22,200
| ****
7.4 / 6.3
| 4.80| 16,378| 4.41| 15,042| 3.61| 12,302|
7MHP4-12-241P †| 7.20| 24,567| 6.61| 22,563| 5.41| 18,453|
10MHP4-12-241P †| 9.60| 32,757| 8.82| 30,084| 7.21| 24,604|
5MHP4-12-301*P| ****
27,600 /
26,600
| ****
12.5 / 11.0
| ****
11.9 / 10.0
| ****
0.75
| ****
26,200 /
25,400
| ****
7.4 / 6.3
| 4.80| 16,378| 4.41| 15,042| 3.61| 12,302|
7MHP4-12-301P †| 7.20| 24,567| 6.61| 22,563| 5.41| 18,453|
10MHP4-12-301P †| 9.60| 32,757| 8.82| 30,084| 7.21| 24,604|
5MHP4-14-361*P| ****
34,600 /
33,200
| ****
14.0 / 11.0
| ****
13.4 / 11.0
| ****
0.75
| ****
32,400 /
31,000
| ****
8.0 / 6.7
| 4.80| 16,378| 4.41| 15,042| 3.61| 12,302|
7MHP4-14-361P †| 7.20| 24,567| 6.61| 22,563| 5.41| 18,453|
10MHP4-14-361P †| 9.60| 32,757| 8.82| 30,084| 7.21| 24,604|
^ Not a rated value
† Two-stage heat available for 7kW and 10kW units S/T = ratio of sensible
to total cooling load
For most up to date ratings and values, please view AHRI listing
EXTENDED HEATING PERFORMANCE DATA (HEAT PUMP ONLY)
Model
| Outdoor Temperature – DB / WB (°F)
---|---
0 / 0| 17 / 15| 35 / 33| 47 / 43| 62 / 56
Net Capacity (Btu/hr)
| System Power Input (kW)| ****
Net Capacity (Btu/hr)
| System Power Input (kW)| ****
Net Capacity (Btu/hr)
| System Power Input (kW)| ****
Net Capacity (Btu/hr)
| System Power Input (kW)| ****
Net Capacity (Btu/hr)
| System Power Input (kW)
MHP4-12-091P| 3,600| 0.68| 5,200| 0.71| 7,200| 0.74| 8,600| 0.76| 10,300| 0.79
MHP4-12-121P| 6,200| 0.98| 6,800| 0.93| 9,500| 0.98| 11,400| 1.01| 13,800| 1.05
MHP4-12-181P| 7,100| 1.19| 9,200| 1.28| 13,500| 1.38| 16,200| 1.44| 19,600| 1.52
MHP4-12-241P| 9,800| 1.91| 14,000| 1.95| 19,300| 2.00| 22,800| 2.02| 27,100| 2.06
MHP4-12-301P| 11,700| 2.02| 16,400| 2.18| 22,100| 2.27| 26,200| 2.33| 31,300| 2.40
MHP4-14-361P| 16,700| 2.40| 20,400| 2.69| 27,600| 2.80| 32,400| 2.88| 38,400| 2.97
EXTENDED HEATING PERFORMANCE DATA (HEAT PUMP ONLY)
Model
| Outdoor Temperature – DB / WB (°F)
---|---
0 / 0| 17 / 15| 35 / 33| 47 / 43| 62 / 56
Net Capacity (Btu/hr)
| System Power Input (kW)| ****
Net Capacity (Btu/hr)
| System Power Input (kW)| ****
Net Capacity (Btu/hr)
| System Power Input (kW)| ****
Net Capacity (Btu/hr)
| System Power Input (kW)| ****
Net Capacity (Btu/hr)
| System Power Input (kW)
MHP4-12-091P| 3,600| 0.69| 5,200| 0.72| 7,200| 0.75| 8,600| 0.77| 10,300| 0.80
MHP4-12-121P| 6,200| 1.00| 6,800| 0.95| 9,500| 1.00| 11,400| 1.03| 13,800| 1.07
MHP4-12-181P| 7,100| 1.22| 9,200| 1.31| 13,500| 1.41| 16,200| 1.47| 19,600| 1.55
MHP4-12-241P| 9,500| 1.93| 13,600| 1.97| 18,800| 2.02| 22,200| 2.04| 26,400| 2.08
MHP4-12-301P| 11,300| 2.06| 15,900| 2.22| 21,400| 2.31| 25,400| 2.37| 30,300| 2.44
MHP4-14-361P| 16,000| 2.45| 19,500| 2.74| 26,400| 2.85| 31,000| 2.93| 36,700| 3.02
N O T E : V a l u e s b a s e d o n 0 . 3 ” w . c . e x ternal static pressure for MHP4-12-091P, MHP4-12-121P, MHP4-12-181P, MHP4-12-241P, MHP4-12-301P, and 0.5” w.c. external static pressure for MHP4-14-361P
__ COMBINED EXTENDED HEATING PERFORMANCE DATA (HEAT PUMP + ELECTRIC
HEAT)
Tonnage
| ****
Model
| Outdoor Temperature – DB / WB (°F)
---|---|---
17 / 15| 35 / 33
208V| 230V| 208V| 230V
Combined Heating Capacity (Btu/hr)| Combined System Power Input (kW)| Combined
Heating Capacity (Btu/hr)| Combined System Power Input (kW)| Combined Heating
Capacity (Btu/hr)| Combined System Power Input (kW)| Combined Heating Capacity
(Btu/hr)| Combined System Power Input (kW)
0.75
| 3MHP4-12-091P| 14,300| 3.41| 16,400| 4.02| 16,300| 3.44| 18,400| 4.05
5MHP4-12-091P| 17,400| 4.32| 20,200| 5.12| 19,400| 4.35| 22,200| 5.15
1.0
| 3MHP4-12-121P| 15,900| 3.63| 18,000| 4.24| 18,600| 3.68| 20,700| 4.29
5MHP4-12-121P| 19,000| 4.54| 21,800| 5.34| 21,700| 4.59| 24,500| 5.39
1.5
| 3MHP4-12-181P| 18,300| 3.98| 20,400| 4.59| 22,500| 4.08| 24,700| 4.69
5MHP4-12-181P| 21,400| 4.89| 24,200| 5.69| 25,600| 4.99| 28,500| 5.79
7MHP4-12-181P| 27,500| 6.69| 31,700| 7.89| 31,800| 6.79| 36,000| 7.99
10MHP4-12-181P| 33,700| 8.49| 39,200| 10.10| 37,900| 8.59| 43,500| 10.20
2.0
| 5MHP4-12-241P| 26,100| 5.56| 29,000| 6.36| 31,400| 5.61| 34,300| 6.41
7MHP4-12-241P| 32,300| 7.36| 36,500| 8.56| 37,500| 7.41| 41,800| 8.61
10MHP4-12-241*P| 38,400| 9.16| 44,000| 10.77| 43,700| 9.21| 49,300| 10.82
2.5
| 5MHP4-12-301P| 28,500| 5.79| 31,400| 6.59| 34,100| 5.88| 37,100| 6.68
7MHP4-12-301P| 34,600| 7.59| 38,900| 8.79| 40,300| 7.68| 44,600| 8.88
10MHP4-12-301*P| 40,800| 9.39| 46,400| 11.00| 46,400| 9.48| 52,100| 11.09
3.0
| 5MHP4-14-361P| 32,400| 6.30| 35,400| 7.10| 39,600| 6.41| 42,600| 7.21
7MHP4-14-361P| 38,600| 8.10| 42,900| 9.30| 45,700| 8.21| 50,100| 9.41
10MHP4-14-361*P| 44,700| 9.90| 50,400| 11.51| 51,900| 10.01| 57,600| 11.62
COMBINED EXTENDED HEATING PERFORMANCE DATA (HEAT PUMP + ELECTRIC HEAT) 1
Tonnage
| ****
Model
| Outdoor Temperature – DB / WB (°F)
---|---|---
47 / 43| 62 / 56
208V| 230V| 208V| 230V
Combined Heating Capacity (Btu/hr)| Combined System Power Input (kW)| Combined
Heating Capacity (Btu/hr)| Combined System Power Input (kW)| Combined Heating
Capacity (Btu/hr)| Combined System Power Input (kW)| Combined Heating Capacity
(Btu/hr)| Combined System Power Input (kW)
0.75
| 3MHP4-12-091P| 17,700| 3.46| 19,800| 4.07| 19,400| 3.49| 21,500| 4.10
5MHP4-12-091P| 20,800| 4.37| 23,600| 5.17| 22,400| 4.40| 25,300| 5.20
1.0
| 3MHP4-12-121P| 20,500| 3.71| 22,600| 4.32| 22,800| 3.75| 25,000| 4.36
5MHP4-12-121P| 23,500| 4.62| 26,400| 5.42| 25,900| 4.66| 28,800| 5.46
1.5
| 3MHP4-12-181P| 25,200| 4.14| 27,400| 4.75| 28,600| 4.22| 30,800| 4.83
5MHP4-12-181P| 28,300| 5.05| 31,200| 5.85| 31,700| 5.13| 34,600| 5.93
7MHP4-12-181P| 34,400| 6.85| 38,700| 8.05| 37,800| 6.93| 42,100| 8.13
10MHP4-12-181P| 40,600| 8.65| 46,200| 10.26| 44,000| 8.73| 49,600| 10.34
2.0
| 5MHP4-12-241P| 34,800| 5.63| 37,800| 6.43| 39,100| 5.67| 42,100| 6.47
7MHP4-12-241P| 41,000| 7.43| 45,300| 8.63| 45,200| 7.47| 49,600| 8.67
10MHP4-12-241*P| 47,100| 9.23| 52,800| 10.84| 51,400| 9.27| 57,100| 10.88
2.5
| 5MHP4-12-301P| 38,200| 5.94| 41,200| 6.74| 43,200| 6.01| 46,300| 6.81
7MHP4-12-301P| 44,300| 7.74| 48,700| 8.94| 49,400| 7.81| 53,800| 9.01
10MHP4-12-301*P| 50,500| 9.54| 56,200| 11.15| 55,500| 9.61| 61,300| 11.22
3.0
| 5MHP4-14-361P| 44,300| 6.49| 47,400| 7.29| 50,300| 6.58| 53,400| 7.38
7MHP4-14-361P| 50,500| 8.29| 54,900| 9.49| 56,400| 8.38| 60,900| 9.58
10MHP4-14-361*P| 56,600| 10.09| 62,400| 11.70| 62,600| 10.18| 68,400| 11.79
Tonnage| Model| __
__
Indoor Temp DB/WB (°F)
| Outdoor Temperature – DB (°F)
---|---|---|---
65| 85| 95| 105| 115
__
Net Capacity (Btu/hr)
| __
S/T
| System Power Input (kW)| __
Net Capacity (Btu/hr)
| __
S/T
| System Power Input (kW)| __
Net Capacity (Btu/hr)
| __
S/T
| System Power Input (kW)| __
Net Capacity (Btu/hr)
| __
S/T
| System Power Input (kW)| __
Net Capacity (Btu/hr)
| __
S/T
| System Power Input (kW)
0.75| MHP4-12-091P| 85/72| 10,800| 0.64| 0.62| 9,900| 0.68| 0.72| 9,400|
0.70| 0.77| 8,700| 0.74| 0.85| 8,000| 0.77| 0.94
80/67| 10,200| 0.70| 0.61| 9,100| 0.76| 0.72| 8,600| 0.79| 0.77| 7,900| 0.82|
0.84| 7,200| 0.85| 0.91
75/63| 9,500| 0.74| 0.61| 8,400| 0.79| 0.72| 7,900| 0.82| 0.77| 7,100| 0.86|
0.83| 6,400| 0.90| 0.89
75/57| 8,800| 1.00| 0.61| 7,700| 1.00| 0.71| 7,200| 1.00| 0.76| 6,700| 1.00|
0.83| 6,100| 1.00| 0.89
1.0| MHP4-12-121P| 85/72| 15,100| 0.64| 0.82| 13,700| 0.67| 1.01| 13,000|
0.69| 1.10| 12,000| 0.73| 1.21| 11,000| 0.76| 1.32
80/67| 14,100| 0.72| 0.82| 12,700| 0.77| 1.00| 12,000| 0.79| 1.09| 11,000|
0.83| 1.19| 9,900| 0.86| 1.29
75/63| 13,300| 0.74| 0.82| 11,800| 0.79| 0.99| 11,000| 0.81| 1.07| 9,900|
0.86| 1.17| 8,800| 0.90| 1.27
75/57| 12,100| 1.00| 0.81| 10,800| 1.00| 0.98| 10,200| 1.00| 1.06| 9,300|
1.00| 1.16| 8,500| 1.00| 1.26
1.5| MHP4-12-181P| 85/72| 21,200| 0.60| 1.14| 19,300| 0.65| 1.38| 18,400|
0.67| 1.50| 16,900| 0.72| 1.64| 15,400| 0.77| 1.78
80/67| 19,900| 0.67| 1.13| 18,000| 0.74| 1.38| 17,000| 0.77| 1.50| 15,300|
0.82| 1.63| 13,600| 0.86| 1.77
75/63| 18,800| 0.72| 1.13| 16,800| 0.77| 1.36| 15,800| 0.80| 1.48| 14,000|
0.85| 1.61| 12,200| 0.90| 1.74
75/57| 17,100| 1.00| 1.13| 15,300| 1.00| 1.36| 14,400| 1.00| 1.47| 13,300|
1.00| 1.60| 12,100| 1.00| 1.74
2.0| MHP4-12-241P| 85/72| 27,900| 0.60| 1.54| 25,800| 0.65| 1.89| 24,700|
0.67| 2.06| 23,000| 0.70| 2.28| 21,400| 0.73| 2.50
80/67| 26,200| 0.67| 1.55| 23,900| 0.73| 1.90| 22,800| 0.76| 2.07| 20,900|
0.80| 2.29| 19,000| 0.84| 2.50
75/63| 24,800| 0.71| 1.55| 22,400| 0.76| 1.88| 21,200| 0.79| 2.05| 19,100|
0.84| 2.26| 17,100| 0.88| 2.48
75/57| 22,700| 1.00| 1.55| 20,300| 1.00| 1.88| 19,200| 1.00| 2.04| 17,700|
1.00| 2.26| 16,200| 1.00| 2.49
2.5| MHP4-12-301P| 85/72| 33,000| 0.64| 1.92| 31,700| 0.66| 2.37| 31,100|
0.67| 2.59| 29,200| 0.69| 2.90| 27,300| 0.71| 3.20
80/67| 32,000| 0.70| 1.91| 29,500| 0.73| 2.35| 28,200| 0.75| 2.56| 26,600|
0.78| 2.85| 25,100| 0.80| 3.13
75/63| 31,100| 0.72| 1.90| 28,800| 0.76| 2.33| 27,700| 0.78| 2.54| 25,400|
0.81| 2.83| 23,200| 0.84| 3.11
75/57| 27,900| 1.00| 1.87| 26,600| 1.00| 2.30| 25,900| 1.00| 2.51| 24,000|
1.00| 2.80| 22,100| 1.00| 3.10
3.0| MHP4-14-361P| 85/72| 41,300| 0.63| 2.27| 38,400| 0.66| 2.80| 36,900|
0.67| 3.06| 34,500| 0.70| 3.37| 32,200| 0.72| 3.68
80/67| 39,200| 0.69| 2.25| 36,100| 0.73| 2.77| 34,600| 0.75| 3.04| 32,000|
0.78| 3.34| 29,500| 0.81| 3.64
75/63| 37,300| 0.72| 2.25| 33,800| 0.76| 2.75| 32,100| 0.78| 2.99| 29,500|
0.81| 3.29| 27,000| 0.84| 3.59
75/57| 33,900| 1.00| 2.25| 31,100| 1.00| 2.73| 29,700| 1.00| 2.97| 27,600|
1.00| 3.27| 25,500| 1.00| 3.58
BLOWER PERFORMANCE
- Performance based on factory-provided washable filter installed in the
- If a higher resistance filter is field installed in the unit, the added resistance must be included in the external static pressure and must not exceed 5 in. w.c. including ductwork
- Refer to Factory Filter Size and Pressure Drop table for additional details
SUPPLY AIRFLOW PERFORMANCE AS A FUNCTION OF EXTERNAL STATIC PRESSURE
Tonnage| Model| Indoor Blower Speed| 0.1″ w.c.| 0.2″ w.c.| 0.3″ w.c.| 0.4
“w.c.| 0.5″ w.c.
SCFM| Watts| HP| SCFM| Watts| HP| SCFM| Watts| HP| SCFM| Watts| HP| SCFM|
Watts| HP
0.75| MHP4-12-091P| TAP 1 (FAN)| 365| 28| 0.04| 330| 31| 0.04| 275| 35|
0.05| 225| 38| 0.05| 180| 41| 0.05
TAP 2 (COOL / HP)| 375| 28| 0.04| 325| 32| 0.04| 275| 35| 0.05| N/A| N/A| N/A|
N/A| N/A| N/A
TAP 3 (COOL / HP)†| N/A| N/A| N/A| N/A| N/A| N/A| 350| 38| 0.05| 320| 42|
0.06| 280| 46| 0.06
3 kW| TAP 4 (HEAT)| 515| 55| 0.07| 485| 58| 0.08| 450| 62| 0.08| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 600| 73| 0.10| 570| 78| 0.10| 545| 84| 0.11| 515| 88| 0.12| 475|
92| 0.12
5 kW| TAP 4 (HEAT)| 570| 69| 0.09| 545| 73| 0.10| 515| 77| 0.10| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 660| 92| 0.12| 635| 98| 0.13| 605| 104| 0.14| 580| 109| 0.15|
550| 114| 0.15
1.0| MHP4-12-121P| TAP 1 (FAN)| 365| 28| 0.04| 330| 31| 0.04| 275| 35| 0.05|
225| 38| 0.05| 180| 41| 0.05
TAP 2 (COOL / HP)| 490| 50| 0.07| 460| 55| 0.07| 420| 59| 0.08| N/A| N/A| N/A|
N/A| N/A| N/A
TAP 3 (COOL / HP)†| N/A| N/A| N/A| 500| 59| 0.08| 470| 63| 0.08| 440| 68|
0.09| 410| 72| 0.10
3 kW| TAP 4 (HEAT)| 515| 55| 0.07| 485| 58| 0.08| 450| 62| 0.08| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 600| 73| 0.10| 570| 78| 0.10| 545| 84| 0.11| 515| 88| 0.12| 475|
92| 0.12
5 kW| TAP 4 (HEAT)| 570| 69| 0.09| 545| 73| 0.10| 515| 77| 0.10| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 660| 92| 0.12| 635| 98| 0.13| 605| 104| 0.14| 580| 109| 0.15|
550| 114| 0.15
1.5| MHP4-12-181P| TAP 1 (FAN)| 365| 32| 0.04| 335| 35| 0.05| 280| 39| 0.05|
235| 42| 0.06| 175| 46| 0.06
TAP 2 (COOL / HP)| 615| 103| 0.14| 590| 108| 0.14| 555| 112| 0.15| 530| 117|
0.16| 500| 121| 0.16
TAP 3 (COOL / HP)†| 705| 118| 0.16| 680| 124| 0.17| 650| 129| 0.17| 620| 135|
0.18| 595| 140| 0.19
3 kW| TAP 4 (HEAT)| 615| 93| 0.12| 590| 97| 0.13| 555| 101| 0.14| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 715| 127| 0.17| 685| 134| 0.18| 655| 140| 0.19| 630| 146| 0.20|
600| 151| 0.20
5 kW| TAP 4 (HEAT)| 665| 110| 0.15| 635| 114| 0.15| 605| 118| 0.16| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 750| 148| 0.20| 725| 154| 0.21| 700| 160| 0.21| 675| 166| 0.22|
650| 171| 0.23
7 kW| TAP 4 (HEAT)| 725| 137| 0.18| 705| 144| 0.19| 675| 150| 0.20| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| 800| 200| 0.27| 780| 205| 0.27| 755| 209| 0.28|
725| 213| 0.29
10 kW| TAP 4 (HEAT)| 750| 148| 0.20| 725| 154| 0.21| 700| 161| 0.22| N/A|
N/A| N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| N/A| N/A| N/A| 805| 224| 0.30| 780| 228| 0.31|
750| 232| 0.31
2.0| MHP4-12-241P| TAP 1 (FAN)| 460| 43| 0.06| 420| 47| 0.06| 380| 51| 0.07|
350| 54| 0.07| 290| 59| 0.08
TAP 2 (COOL / HP)| 815| 150| 0.20| 785| 161| 0.22| 760| 165| 0.22| 740| 172|
0.23| 715| 178| 0.24
TAP 3 (COOL / HP)†| 855| 124| 0.17| 830| 132| 0.18| 795| 139| 0.19| 775| 145|
0.19| 750| 150| 0.20
5 kW| TAP 4 (HEAT)| 800| 146| 0.20| 775| 152| 0.20| 750| 157| 0.21| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 905| 201| 0.27| 880| 207| 0.28| 855| 212| 0.28| 825| 216| 0.29|
800| 219| 0.29
7 kW| TAP 4 (HEAT)| 855| 174| 0.23| 830| 179| 0.24| 800| 183| 0.25| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| 930| 231| 0.31| 900| 235| 0.32| 875| 239| 0.32|
850| 243| 0.33
10 kW| TAP 4 (HEAT)*| 855| 174| 0.23| 830| 179| 0.24| 800| 183| 0.25| N/A|
N/A| N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| 930| 231| 0.31| 900| 235| 0.32| 875| 239| 0.32|
850| 243| 0.33
SUPPLY AIRFLOW PERFORMANCE AS A FUNCTION OF EXTERNAL STATIC PRESSURE
Tonnage| Model| Indoor Blower Speed| 0.1″ w.c.| 0.2″ w.c.| 0.3″ w.c.| 0.4
“w.c.| 0.5″ w.c.
SCFM| Watts| HP| SCFM| Watts| HP| SCFM| Watts| HP| SCFM| Watts| HP| SCFM|
Watts| HP
0.75| MHP4-12-091P| TAP 1 (FAN)| 365| 28| 0.04| 330| 31| 0.04| 275| 35|
0.05| 225| 38| 0.05| 180| 41| 0.05
TAP 2 (COOL / HP)| 375| 28| 0.04| 325| 32| 0.04| 275| 35| 0.05| N/A| N/A| N/A|
N/A| N/A| N/A
TAP 3 (COOL / HP)†| N/A| N/A| N/A| N/A| N/A| N/A| 350| 38| 0.05| 320| 42|
0.06| 280| 46| 0.06
3 kW| TAP 4 (HEAT)| 515| 55| 0.07| 485| 58| 0.08| 450| 62| 0.08| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 600| 73| 0.10| 570| 78| 0.10| 545| 84| 0.11| 515| 88| 0.12| 475|
92| 0.12
5 kW| TAP 4 (HEAT)| 570| 69| 0.09| 545| 73| 0.10| 515| 77| 0.10| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 660| 92| 0.12| 635| 98| 0.13| 605| 104| 0.14| 580| 109| 0.15|
550| 114| 0.15
1.0| MHP4-12-121P| TAP 1 (FAN)| 365| 28| 0.04| 330| 31| 0.04| 275| 35| 0.05|
225| 38| 0.05| 180| 41| 0.05
TAP 2 (COOL / HP)| 490| 50| 0.07| 460| 55| 0.07| 420| 59| 0.08| N/A| N/A| N/A|
N/A| N/A| N/A
TAP 3 (COOL / HP)†| N/A| N/A| N/A| 500| 59| 0.08| 470| 63| 0.08| 440| 68|
0.09| 410| 72| 0.10
3 kW| TAP 4 (HEAT)| 515| 55| 0.07| 485| 58| 0.08| 450| 62| 0.08| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 600| 73| 0.10| 570| 78| 0.10| 545| 84| 0.11| 515| 88| 0.12| 475|
92| 0.12
5 kW| TAP 4 (HEAT)| 570| 69| 0.09| 545| 73| 0.10| 515| 77| 0.10| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 660| 92| 0.12| 635| 98| 0.13| 605| 104| 0.14| 580| 109| 0.15|
550| 114| 0.15
1.5| MHP4-12-181P| TAP 1 (FAN)| 365| 32| 0.04| 335| 35| 0.05| 280| 39| 0.05|
235| 42| 0.06| 175| 46| 0.06
TAP 2 (COOL / HP)| 615| 103| 0.14| 590| 108| 0.14| 555| 112| 0.15| 530| 117|
0.16| 500| 121| 0.16
TAP 3 (COOL / HP)†| 705| 118| 0.16| 680| 124| 0.17| 650| 129| 0.17| 620| 135|
0.18| 595| 140| 0.19
3 kW| TAP 4 (HEAT)| 615| 93| 0.12| 590| 97| 0.13| 555| 101| 0.14| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 715| 127| 0.17| 685| 134| 0.18| 655| 140| 0.19| 630| 146| 0.20|
600| 151| 0.20
5 kW| TAP 4 (HEAT)| 665| 110| 0.15| 635| 114| 0.15| 605| 118| 0.16| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 750| 148| 0.20| 725| 154| 0.21| 700| 160| 0.21| 675| 166| 0.22|
650| 171| 0.23
7 kW| TAP 4 (HEAT)| 725| 137| 0.18| 705| 144| 0.19| 675| 150| 0.20| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| 800| 200| 0.27| 780| 205| 0.27| 755| 209| 0.28|
725| 213| 0.29
10 kW| TAP 4 (HEAT)| 750| 148| 0.20| 725| 154| 0.21| 700| 161| 0.22| N/A|
N/A| N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| N/A| N/A| N/A| 805| 224| 0.30| 780| 228| 0.31|
750| 232| 0.31
2.0| MHP4-12-241P| TAP 1 (FAN)| 460| 43| 0.06| 420| 47| 0.06| 380| 51| 0.07|
350| 54| 0.07| 290| 59| 0.08
TAP 2 (COOL / HP)| 815| 150| 0.20| 785| 161| 0.22| 760| 165| 0.22| 740| 172|
0.23| 715| 178| 0.24
TAP 3 (COOL / HP)†| 855| 124| 0.17| 830| 132| 0.18| 795| 139| 0.19| 775| 145|
0.19| 750| 150| 0.20
5 kW| TAP 4 (HEAT)| 800| 146| 0.20| 775| 152| 0.20| 750| 157| 0.21| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| 905| 201| 0.27| 880| 207| 0.28| 855| 212| 0.28| 825| 216| 0.29|
800| 219| 0.29
7 kW| TAP 4 (HEAT)| 855| 174| 0.23| 830| 179| 0.24| 800| 183| 0.25| N/A| N/A|
N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| 930| 231| 0.31| 900| 235| 0.32| 875| 239| 0.32|
850| 243| 0.33
10 kW| TAP 4 (HEAT)*| 855| 174| 0.23| 830| 179| 0.24| 800| 183| 0.25| N/A|
N/A| N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| 930| 231| 0.31| 900| 235| 0.32| 875| 239| 0.32|
850| 243| 0.33
SUPPLY AIRFLOW PERFORMANCE AS A FUNCTION OF EXTERNAL STATIC PRESSURE
Tonnage| Model| Indoor Blower Speed| 0.1″ w.c.| 0.2″ w.c.| 0.3″ w.c.| 0.4
“w.c.| 0.5″ w.c.
SCFM| Watts| HP| SCFM| Watts| HP| SCFM| Watts| HP| SCFM| Watts| HP| SCFM|
Watts| HP
2.5| MHP4-12-301P| TAP 1 (FAN)| 590| 43| 0.06| 535| 48| 0.06| 430| 55| 0.07|
380| 60| 0.08| 315| 65| 0.09
TAP 2 (COOL / HP)| 1040| 161| 0.22| 1005| 169| 0.23| 970| 177| 0.24| 935| 185|
0.25| 900| 193| 0.26
TAP 3 (COOL / HP)†| N/A| N/A| N/A| 1030| 162| 0.22| 1005| 171| 0.23| 980| 180|
0.24| 955| 189| 0.25
5 kW| TAP 4 (HEAT)| 1075| 151| 0.2| 1040| 159| 0.21| 1005| 168| 0.23| N/A|
N/A| N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| N/A| N/A| N/A| 1100| 205| 0.27| 1065| 216| 0.29|
1025| 225| 0.30
7 kW| TAP 4 (HEAT)| 1075| 151| 0.2| 1040| 159| 0.21| 1005| 168| 0.23| N/A|
N/A| N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| N/A| N/A| N/A| 1100| 205| 0.27| 1065| 216| 0.29|
1025| 225| 0.30
10 kW| TAP 4 (HEAT)| 1075| 151| 0.2| 1040| 159| 0.21| 1005| 168| 0.23| N/A|
N/A| N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| N/A| N/A| N/A| 1100| 205| 0.27| 1065| 216| 0.29|
1025| 225| 0.30
3.0| MHP4-14-361P| TAP 1 (FAN)| 680| 61| 0.08| 630| 68| 0.09| 575| 74| 0.10|
525| 79| 0.11| 460| 86| 0.12
TAP 2 (COOL / HP)| 1235| 260| 0.35| 1200| 272| 0.36| 1165| 284| 0.38| 1135|
295| 0.40| 1100| 305| 0.41
TAP 3 (COOL / HP)†| N/A| N/A| N/A| N/A| N/A| N/A| 1105| 263| 0.35| 1075| 272|
0.36| 1045| 282| 0.38
5 kW| TAP 4 (HEAT)| 1240| 232| 0.31| 1205| 248| 0.33| 1170| 262| 0.35| N/A|
N/A| N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| N/A| N/A| N/A| 1260| 315| 0.42| 1230| 328| 0.44|
1200| 338| 0.45
7 kW| TAP 4 (HEAT)| 1240| 232| 0.31| 1205| 248| 0.33| 1170| 262| 0.35| N/A|
N/A| N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| N/A| N/A| N/A| 1260| 315| 0.42| 1230| 328| 0.44|
1200| 338| 0.45
10 kW| TAP 4 (HEAT)| 1240| 232| 0.31| 1205| 248| 0.33| 1170| 262| 0.35| N/A|
N/A| N/A| N/A| N/A| N/A
TAP 5 (HEAT)| N/A| N/A| N/A| N/A| N/A| N/A| 1260| 315| 0.42| 1230| 328| 0.44|
1200| 338| 0.45
N/A: Do not operate unit using this blower speed at this external static
pressure.
† As shipped speed for Cooling and Heat Pump operation. Blower speed must
be field adjusted to Speed Tap 2 for lower duct static applications.
* As shipped speed for Heating operation. Blower speed must be field
adjusted to Speed Tap 5 for higher duct static applications.
SCFM = standard cubic feet per minute
__
215 Metropolitan Drive | West Columbia, SC
29170800-448-5872
Product Support 866-282-7257 www
.magic-pak.com