Schneider Electric JYT65471 Circuit Breaker Instruction Manual

June 12, 2024
Schneider Electric

Instruction Bulletin

JYT65471
Rev. 02, 06/2023
Replaces JYT65471 Rev. 01, 07/2022
PowerPacT™ H- and J-Frame Circuit Breakers and Switches

JYT65471 Circuit Breaker

Retain for future use.
Before starting the installation read and understand all instructions.

https://www.se.com/us/en/download/document/JYT65471

Scan the QR code on the product for additional product information.
For information about other products, see our website: https://www.se.com:
For application assistance, please call 1-888-778-2733.

Necessary Tools
Screwdriver, Phillips ® #1 and 2 Screwdriver, long-shanked slotted Torque wrench:

  • H-frame lug—3/16 in. hex bit
  • J-frame lug—5/16 in. hex bit
  • Bus connection— 5/32 in. hex bit

Precautions

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462, or NOM-029-STPS.
  • This equipment must be installed and serviced only by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Replace all devices, doors and covers before turning on power to this equipment.

Failure to follow these instructions will result in death or serious injury.

WARNING: This product can expose you to chemicals including DINP, which is known to the State of California to cause cancer, and DIDP which is known to the State of California to cause birth defects or other reproductive harm. For more information go to: www.P65Warnings.ca.gov.
The product has been designed for environment A (Class A, IEC 60947-1). Use of this product in environment B (Class B, IEC 60947-1) may cause unwanted electromagnetic disturbances in which case the user may be required to take adequate mitigation measures.

Installation

  1. Turn off all power supplying this equipment before working on or inside equipment.
  2. Trip the circuit breaker (Figure 1, a–c).
  3. Use a properly rated voltage sensing device to confirm power is off.
  4. Remove the handle extension (d). FIG. 1 :
    Schneider Electric JYT65471 Circuit Breaker - Installation
1 Visi-Trip™
    The Visi-Trip LED handle aids in quickly locating a circuit breaker that requires attention. Inspect the handle position for circuit breaker trip indication. The VisiTrip handle will flash an LED light as described in Table
  5. NOTE: When performing annual maintenance in accordance with MCCB Field Testing and Maintenance Guide (0600IB1201), operate the push to trip button (if equipped) to verify the Visi-Trip functionality. Cycle the circuit breaker from tripped to OFF, and then from OFF to ON and take not of the battery health. See Table 2.
    Wait five seconds between handle operation and push-totrip button operation to ensure that the Visi-Trip handle is on standby mode. Tripping the circuit breaker too soon after toggling may result in the VisiTrip handle not operating as intended.

TABL. 1 :

Light Pattern Indicator
Fast flash for two seconds. Battery low (20% remaining).
Long duration slow flash (continuous flash up to for six hours). Inspect the

handle position for circuit breaker trip indication.

1. Refer to the Schneider Electric Frequently Asked Questions page. https://www.se.com/us/en/faqs/home/for more information.
2. If a nuisance LED flashing occurs on ON or OFF position, it can be reset by toggling the circuit breaker. If toggling the circuti breaker is not desired, LED flashing will reset after six hours.

Individually-Mounted Circuit Breaker Installation

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Install circuit breaker so minimum clearance distance to grounded metal is maintained.
Failure to follow these instructions will result in death or serious injury.

  1. Check the electrical clearances (Figure 2, a). Insulate the circuit breaker if necessary (b–c).
    FIG. 2 :
    Enclosure Clearances
    Schneider Electric JYT65471 Circuit Breaker - Installation
2 Fiber Insulating Plate
    Enclosure Dimensions
    | Schneider Electric JYT65471 Circuit Breaker - Installation
5
    ---|---
    Frame| Standard (8070) Rated| 100% Rated
    HD| 15-150 A| 15.6 x 6.12 x 3.49 in.
    (396 x 155 x 89 mm)| 15.6 x 6.12 x 3.49 in.
    (396 x 155 x 89 mm)
    HR| 18.13 x 8.63 x 4.13 in.
    (461 x 219 x 105 mm)| 62 x 22.5 x 14 in.
    (1575 x 572 x 356 mm)
    JD| 150-250 A| 18.72 x 6.12 x 3.49 in.
    (476 x 155 x 89 mm)| 18.72 x 6.12 x 3.49 in.
    (476 x 155 x 89 mm)
    JR| 28.5 x 12.38 x 5.38 in.
    (724 x 314 x 137 mm)| 62 x 22.5 x 14 in.
    (1575 x 572 x 356 mm)

J-Frame Enclosure Insulation2/

1. If dimension “A” is less than 0.56 in. (14.2 mm), attach fiber insulating plate (not provided) to enclosure cover.
2. Insulation required if circuit breaker side is < 4.13 in. (105 mm) from metal.

  1. Install the circuit breaker (Figure 3, a–b).
    FIG. 3 :
    Schneider Electric JYT65471 Circuit Breaker - Installation
6Schneider Electric JYT65471 Circuit
Breaker - Installation 7

I-Line™ Circuit Breaker Installation

NOTICE
HAZARD OF EQUIPMENT DAMAGE

  • Do not adjust jaws.
  • Do not remove joint compound.
  • If necessary, use Square D joint compound PJC7201.

Failure to follow these instructions can result in equipment damage.

  1. Rack the circuit breaker onto the bus (Figure 4 (a–c).
  2. Tighten the mounting bracket screw (d–e).
    FIG. 4 :
    Schneider Electric JYT65471 Circuit Breaker - Circuit Breaker
1

Cable Installation **

**

NOTE: If the circuit breaker has terminal nuts installed, remove terminal nuts and install lugs as directed in the instructions shipped with the lug kit.

NOTICE
HAZARD OF FALSE TORQUE INDICATION
Do not allow conductor strands to interfere with threads of wire binding screw.
Failure to follow these instructions can result in equipment damage. 

TABL. 2 : Lug Information

| | Schneider Electric JYT65471 Circuit Breaker - Cable Installation
3| |
---|---|---|---|---
AL150HD| H| 15-150A| (1)A(Cu| #14—#10 AWG
(2.5-6 mm2)| 0.65 in. (16 mm)| 50 lb-in.
(5 N•m)

8-3/0 AWG

(10-95 mm2)| 0.65 in. (16 mm)| 120 lb-in.
(14 N•m)
CU150HD| H| 15-150 A| (1) Cu| #14-2/0 AWG
(2.5-70 mm2)| 0.65 in. (16 mm)| 120 lb-in.
(14 N•m)
AL175JD| J| 150-175 A| (1) Al/Cu| #4-4/0 AWG
(25-95 mm2)| 1 in. (25 mm)| 225 lb-in.
(26 N•m)
AL250JD| J| 200-250 A| (1)Al/Cu| #3/0-350 kcmil
(95-185 mm2)| 1 in. (25 mm)| 225 lb-in.
(26 N•m)
CU250JD| J| 150-250 A| (1) Cu| #1/0-300 kcmil
(50-150 mm2)| 1 in. (25 mm)| 250 lb-in.
(28 N•m)

  1. Conductors must be cut square for secure termination.

NOTE: See Table 2 for strip lengths and torques.

  1. Preform the conductors to their final configuration. Strip the conductor ends (Figure 5, a). Do not nick strands.
  2. Install the cables in the lugs and torque the wire binding screws (b–c).
    • Install wire larger than 12 AWG in the center of the channel (d).
    • Install 14–12 AWG wire on the side of channel (e) on all lugs to avoid damage to the  wire.

FIG. 5 :

Schneider Electric JYT65471 Circuit Breaker - Cable Installation
5

Bus Installation

NOTE: If terminal nut inserts are not installed, install the terminal nut inserts as directed in the instructions shipped with the terminal nut kit.

  1. Install the bus using the supplied hardware (Figure 6, a–c).
    FIG. 6 : Bus and Bus Insulation Dimensions

Schneider Electric JYT65471 Circuit Breaker - Bus Installation
1

Dimension H-frame J-frame
A 0.250 in.
(6.4 ) 0.250

(6.4)
B| 0.125–0.375
(3.2–9.5)| 0.125–0.375
(3.2–9.5)
C| 0.50
(12.7)| 0.50–0.75
(12.7–19.1)
D| 0.3
(7.6)| 0.625
(15.9)
E| 0.3 in
(7.6)| 0.375
(9.5)

Accessory and Control Wiring Installation

  1. Remove accessory cover (a).

  2. Remove the accessory devices from the corresponding accessory compartments (b).
    NOTE: Installation of overcurrent trip switch (SDE) requires installation of the SDE actuator, not provided.

  3. Install control wiring (c) to the accessories.
    NOTE: All diagrams show the circuit breaker in tripped position.
    FIG. 7 :
    Function| Connector| Description
    ---|---|---
    Auxiliary contacts| OF/AX| Open/closed circuit breaker or switch position contacts
    SD/AL| Bell alarm
    Remote operation| MN/UVR| Under voltage trip device
    MX/SHT| Shunt Trip
    MCH| Motor operator

Schneider Electric JYT65471 Circuit Breaker - Bus Installation
3 NOTICE
HAZARD OF EQUIPMENT DAMAGE
• Tighten all accessory cover screws to stated torque.
• Do not over torque screws.
• Do not use power equipment to torque screws.
Failure to follow these instructions can result in equipment damage.

  1. Route the wiring (Figure 8, a).

  2. Replace the accessory cover, being careful not to pinch the wires when installing the cover.

  3. Replace Visi-Trip handle on the proper orientation, or handle extension (d).
    FIG. 8 :
    Individually-Mounted Circuit Breakers
    Schneider Electric JYT65471 Circuit Breaker - Bus Installation
4I-Line Circuit Breakers
    Schneider Electric JYT65471 Circuit Breaker - Bus Installation
5Plug-On and Drawout Circuit Breakers
    See wiring information provided with plug-in base. If accessories are field installed, follow instructions provided with 9-wire connector.
    NOTE: Confirm that the catalog number printed on the side of the accessory label (Figure 9, a) matches catalog number printed on the accessory cover (b).

  4. Mark on the side accessory label (a) which device was installed.
    FIG. 9 :
    Schneider Electric JYT65471 Circuit Breaker - Bus Installation
6

Circuit Breaker Removal

  1. Turn off all power supplying this equipment before working on or inside equipment.
  2. Remove circuit breaker in reverse order of installation.

Operation

  • Press push-to-trip button (Figure 10, a) at installation to check operation.
  • Repeat once a year to exercise circuit breaker.

NOTE: Push-to-trip button will not trip the circuit breaker if it is in the off (O) position.
FIG. 10 :
Trip Unit Adjustment

For J-frame circuit breakers only, adjust instantaneous trip (Im) by turning dial (Figure 11, a).
FIG. 11 :

Schneider Electric JYT65471 Circuit Breaker - Bus Installation
8

Troubleshooting

DANGER
If problems occur during installation, refer to the following guide. If trouble persists, contact the local field office.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462, or NOM-029-STPS.
  • This equipment must be installed and serviced only by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Replace all devices, doors and covers before turning on power to this equipment.
  • Qualified persons performing diagnostics or troubleshooting that require electrical conductors to be energized must comply with NFPA 70 E – Standard for  Electrical Safety Requirements for Employee Workplaces and OSHA Standards – 29 CFR Part 1910 Subpart S – Electrical.

Failure to follow these instructions will result in death or serious injury.

Condition Possible Causes Solution
Circuit breaker fails to stay closed. Short circuit or overload on system.

heck system for short circuit or overload
Circuit beaker trips, but no short circuit or overload is evident.| Voltage is below undervoltage trip setting.| Check system for low voltage.
Push-to-trip button will not trip circuit breaker.| Circuit breaker already tripped.| over circuit breaker handle to reset then to on (I)
Circuit breaker cannot be opened manually.| Damage to current path.| Contact local field office.

TABL. 3 : PowerPacT H- and J- Frame DC Wiring Diagrams

Ground Negative1 Grounded Middle Point Ungrounded Source
250 Vdc ≤ 250 Vdc ≤ 250 Vdc

Circuit Breaker Specifications (UL®)

ircuit Breaker Type 250 Vdc
Circuit Breaker Type 250 Vdc1
 D, G, J, L 20 kA
  1. 250 Vdc ratings only available with Power Pac T H or J circuit breakers with thermal-magnetic trip units (not including MCP).

Electrical equipment should beinstalled, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
Schneider Electric, Square D, and PowerPacT are trademarks owned by Schneider Electric Industries SAS or its affiliated companies. All other trademarks are the property of their respective owners.


Schneider Electric Limited

Stafford Park 5
Telford TF3 3BL
United Kingdom
www.se.com/uk

Schneider Electric USA, Inc.
800 Federal Street
Andover, MA 01810 USA
888-778-2733
www.se.com/us/en/


Printed on recycled paper.
© 2007–2023 Schneider Electric All Rights Reserved

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals