HAISEN HD405V-CRH Lighting Central Switch Instruction Manual
- June 12, 2024
- HAISEN
Table of Contents
Detached design
HD405V-CRH
- Dual setting by DIP switch and remote control.
- Suitable for Tri-Proof light.
- Tri-level control by 1-10V output.
- Loop in and loop out for easy installation.
- Sensitive and reliable
- 8-15m High altitude installation.
- 3 year warranty.
On/off control Detection area
Hold time Daylight threshold
Stand-by period Stand-by dimming level
Remote control setting 10-15M Highbay
Detection coverage
This figure indicates the maximum distance at the highest mounting height with
100% sensitivity.
Typical installation height 8-15m
Well covered Covered
Technical data
Operating voltage | 120-277VAC,50Hz/60Hz |
---|---|
Switching capacity | Max,3.0A@120Vac,50/60Hz; |
Max,2.0A@277Vac,50/60Hz
Stand-by power| ≤1W
Control method | On/off / 1-10V Dimming Remote Control
Microwave frequency| 5.8GHz±75MHz
Microwave power| <0.3mW
Detection area| 50%/100%
Hold time| 5s/30s/1min/10min
Daylight threshold| 2Lux/10Lux/50Lux/Disable
Stand-by period | 0s/30s/20min/+∞
Stand-by dimming level | 10%/20%/30%/50%
Mounting height | 8-15m /26.25-49.2ft
Detection range| Max.ø14m/45.93ft
Motion detection| 0.5~1.5m/s
Operating temperature| -30°C~+70°C
IP rating| IP20
Warranty| 3 years
Factory Default Setting: Detection area 100%/ Hold time 5s/ Daylight threshold Disable/Stand-by period 0s/Stand-by dimming level 10%.
Mechanical structure
- +/- 1-10V
- Motion sensor interface RJ1 1
- Detection area
- Hold time
- Daylight threshold
- Stand-by period
- Stand-by dimming level
- Output
- Input
- Installation hole
- Antenna module
- Daylight sensor
- IR Receiver
Specifications subject to change without notice. ©All rights reserved.
Dimensions (Unit: mm)
Note: Motion sensor setting and dimming setting please refer to remote control
HD03R.
HD02VRH Wire diameter 4mm,Standard Version Cable Length 48.5cm(can be
customized).
Wiring diagram
Settings
- Switch UP
- Switch DOWN
- Detection area
- Hold-time
- Daylight threshold
- Stand-by period
- Stand-by dimming level
• | 100% |
---|---|
Ο |
50%
Detection area
In this area, movement will be detected and able to trigger the sensor.100%
detection area is also known as the strong sensitivity.
• | • | 5s |
---|---|---|
Ο | • |
30s
•| Ο| 1min
Ο| Ο|
10min
Hold-time
The period of light keeping 100% brightness after moving objects leave the
detection area.
• | • | Disable |
---|---|---|
Ο | • |
50lux
•| Ο| 10lux
Ο| Ο|
2lux
Daylight threshold
Definition of the ambient brightness; only when the ambient brightness is
lower than the preset specific lux amount, the sensor will work; when it’s
preset as “disable”, the sensor works every time it detects motion regardless
the ambient brightness.
• | • | 0s |
---|---|---|
Ο | • |
30s
•| Ο| 20min
Ο| Ο|
+∞
Stand-by period
The period of light keeping low output before it’s completely switched off.
When it’s preset as”∞“, the light always keep at low output if no movement in
the detection area and doesn’t turn off.
• | • | 10% |
---|---|---|
Ο | • |
20%
•| Ο| 30%
Ο| Ο|
50%
Stand-by dimming level
The definition of low output in the standby period.
Application
1. Automatically ON/OFF function:
Light on when detect movement and off after people leave at night. Applications: Corridor, Staircase.
With sufficient daylight, even when motion detected, light remains OFF.
With insufficient daylight, when motion detected, light ON.
After the last detection and the present hold time elapsed, light OFF.
2. No daylight function
The daylight threshold is set to “Disable”.
Light on when detect movement, After people leave, Light off after stand-by
period.
Applications: Dim places such as Basement Parking, Underpass.
When motion is detected, the sensor will switch on the light to 100% brighteness.
After people leave the detection area, light remains 100% brightness within hold time.
After the last detection and the present hold time elapsed, light OFF.
3. Function Demo – Dimmable control/Corridor function
With sufficient daylight, even when motion detected, light remains OFF.
With insufficient daylight, when motion detected, light ON.
After last detection, the light will be dimmed down to the stand-by dimming level (10%,20%,30% or 50%) after holdtime.
After the stand-by period, light OFF.
Installation Method
4 styles of installation
(1) (2) (3) (4)
Cable on center
(1)
(2)
(3)
Please ensure no any metal is thielding the sensor antenna.
Cable on tip side
(1)
(2)
(3)
Please ensure no any metal is thielding the sensor antenna.
Attention
- Please read the instructions carefully before using this product and keep it well for all users to read at any time.
- The sensor should be installed by qualified electrician and ensure power is off before the installation.
- We reserve the right to modify any incorrect text, image and necessary technical parameters.
- Any unauthorized modification is forbidden, otherwise all guarantees will be immediately invalid.
Installation precautions
- Microwave sensor can be installed in any lamp except the one with full metal shell.
- The detected surface cannot be shielded by metal objects.
- Make sure the microwave module is completely exposed outside.
- The detection surface of the sensor module shall be installed facing the detection area.
- Should be kept away from the driver to avoid interference generation and lamp flashing.
- Wiring must be strictly in accordance with the wiring diagram to avoid short circuit.
Application Environment
- Suitable for indoor installation to avoid false triggering due to external factors such as rain, wind or tree swing.
- Shall not be installed in the place with all four metal shelters and small space (such as galvanized-iron roof ).
- Shall note be mounted installation, so as to avoid false trigger caused by the lamp itself shaking.
- Shall not be installed next to large operating machines such as ventilator/ceiling fan to avoid false triggering caused by machine vibration.
User Notes
- Microwave can penetrate walls or glass thinner than 20cm and attenuate if thicker than 20cm.
- The driver voltage shall be stable and float within 10%.
- Detection area will be affected by speed of motion, mounting height and movement volume.
- Conduct test on sunny days without the lampshade which will affect the tested lux value.
HD05R Remote Control Applications
1. ON/OFF
2.
1. “ON/OFF” key only functions as a switch of the light.
2. If press this button to turn off the lamp before it’s short-circuited, the
lamp will remain off after power-on
3. WM/PIR
Change from the microwave sensor function to PIR sensor function, and the
other around.
4. Scene
Press “Reset” button, products with DIP switch will be controlled by DIP
switches; otherwise all the setting will be just initial, that is 100%
detection range, hold time 5S, no stand-by time and daylight threshold
disabled.
Start Press the button before choosing the parameters.
Memory Press the button after choosing all the parameters to save them.
Apply Press the button to deliver the saved settings to the other sensors
directly.
5. Hold time
The period of light keeping 100% brightness after moving objects leave the
detection area.
6. Stand-by period
The period of light keeping low output before it gets completely off. When
it’s preset as –, the light always keep at low output even no movement in the
detection area.
7. Power %
Press the button to change the output power from 0% to 100%, it changes 5%
every press.
8. Test (2s)
The button “Test (2s)” is for testing purpose after commissioning. Pressing
this button, the sensor goes to test mode (hold time is only 2s ).
9. **** Increase or decrease the parameters.
10. Daylight Threshold
Definition of the ambient brightness; only when the ambient brightness is
lower than the preset specific lux amount, the sensor will work; when it’s
preset as “disable”, the sensor works every time it detects motion regardless
of the ambient lux level.
11. Stand-by dimming level
The definition of low output during the standby period.
12. Detection Rarea
The area in which movement will trigger the sensor, 100% detection area also
means strong sensitivity.
Memory & Apply Mode
1. Press “ON/OFF button” to turn on the light or off.
2. To reset the parameters, Please follow the steps as below:
Step 1 – Press ON, to turn on the light if it was off at the start.
Step 2 – Press “Start” to the well-setting sensor.
Step 3 – Press the button of Detection range, Hold time, Stand-by dimming
level, Stand-by period and Daylight threshold one after the other in sequence
(Press “+/-” to set parameters).
Step 5 – Press “Memory” to memorize the settings.
Note: The interval of each parameter setting shall be controlled within
30s.
3. To programme other lights in the array that have similar sensors to the
same programme.
Step 1 – Press “ON” to the second sensor
Step 2 – Press “Apply”
Isolated Setting Mode
1. Press “ON/OFF button” to turn on the light or off. Press “Scene”, the remote will activate settings that were saved last or remain at the factory default settings.
2. To reset the parameters, Please follow the steps as below:
Step 1 – Press ON, to turn on the light if it was off at the start.
Step 2- Press any button of “Scene”, Test” and “Apply” to begin the sensor
detection mode.
Step 3 – Press the button of Detection range, Hold time, Stand-by dimming
level, Stand-by period and Daylight threshold one after the other in sequence.
Notes:
1. Settings will be saved automatically and remain until you press reset
again.
2. Light will flicker when setting each parameter.
3. The icon will flash when setting the corresponding parameter.
Shenzhen Haisen Technology Co., Ltd., Tel: +86-755-82598105 丨Fax: +86-755-82598106丨Email: info@haisensz.com 丨www.haisensz.com Haisen Technology
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>