KEENSTAR EG-M54-HLV EGING Solar PV Modules Installation Guide
- June 12, 2024
- KEENSTAR
Table of Contents
KEENSTAR EG-M54-HLV EGING Solar PV Modules Installation Guide
INTRODUCTION
Thanks for choosing high quality modules from Changzhou EGing Photovoltaic
Technology Co., Ltd(Hereinafter referred to as “Egging”)This Installation
Manual contains essential information for the electrical and mechanical
installation that you must know before installing EGING PV modules. This also
contains safety information youneed to be familiar with. All the information
described in this manual are the intellectual property of EGING and based on
the technologies and experiences that have been acquired and accumulated in
the history of EGING This document does not constitute a warranty, expressed
or implied. EGING.
does not assume responsibility and expressly disclaims liability for loss,
damage, or expense arising out of or in anyway connected with installation,
operation, use or maintenance of the PV modules. No responsibility is assumed
by EGING for any infringement of patents or other rights of third parties that
may result fromuse of PV module. EGING reserves the right to make changes to
the product, specifications or installation manual without prior notice.
RULES AND REGULATIONS
The mechanical and electrical installation of the module should obey local regulations, including electrical law, construction law and electricity connection requirements. These regulations are different in different installation site, such as the installation on the building roof, different installation environment of the power station. Requirements may also differ with the system voltage, the use of AC or DC. For the specific terms, please contact local authority. Before installing the PV module, contact appropriate authorities to determine permit, installation and inspection requirements that should be followed. Don’t throw away the Modules Waste. Please contact local related departments or authorities.
GENERAL INFORMATION
COMPONENTS OF MOUDLE
The structure of module is shown in the figure below. Each module is pasted
with three kinds of labels to provide the following information:
Nameplate : product type, rated power, rated current, rated voltage, open
circuit voltage, short circuit current under testing conditions, certification
indicator, maximum system voltage, etc.
Current classification label: Rated working current.
Serial Number label: A unique serial number which is laminated inside the
module permanently which can be found in the front of the module.
Regular modules
Bifacial Modules
Figure : 1 Regular Modules Mechanical Drawing
1 | Drain Hole | 7 | Glass |
---|---|---|---|
2 | Grounding Hole | 8 | EVA |
3 | Mounting Hole | 9 | Solar Cell |
4 | Connector/Cable | 10 | Backsheet |
5 | Junction Box | 11 | EVA/POE |
6 | Frame |
GENERAL SAFETY
EGING PV modules are designed in accordance with the international standard IEC61215 and IEC61730. The solar modules have been qualified for application class A(equivalent to safety class requirements)
Installing PV modules and ground frames should be in accordance with
applicable rules and regulations. Only installer/service personnel should have
access to the PV module installation site. in order to avoid a risk of injury
or electrical shock, do not allow anyone to approach the PV module if the
person has little knowledge on PV module or on the measures that should be
taken when PV modules are damaged.
In the case that the PV modules are non-integral type, the module is to be
mounted over a fire resistant
roof. Follow all safety precautions of other components used in the system. Do
not clean the glass surface with chemicals.
Do not let water stay on the glass surface of PV modules for a long time. This
creates aristo white efflorescence (glass disease) which may result in the
deterioration of energy generation. Do not install the PV module horizontally.
It may cause dirt or white efflorescence(glass disease) due to water. Do not
cover the water drain holes of the frame. There is a risk of frost damage when
the frame miss filled with waterhen sliding snow load has to be considered, an
appropriate measure has to be taken so that PV module frames on lower edge of
PV modules will not be damaged.
ELECTRICAL SAFETY
The installation of PV modules requires a great degree of skill and should
only be performed by a qualified
licensed professional, including licensed contractors and licensed
electricians. Please read this manual carefully before installing or using the
modules. Please beware that there is serious risk of various types of injury
occurring during the installation including the risk of electric shock.
All EGINGPV modules are equipped with a permanently attached junction
terminal box that will accept variety of wiring applications or with especial
cable assembly for ease of installation, and they do not require special
assembly. Contact with electrically active parts of a PV module such as
terminals can result in burns, sparks and lethal shock whether the PV modules
is connected or not.
PV modules produce electricity when the sunlight or other sources illuminate
the module surface. When the modules are connected in series, voltage is
cumulative. When the modules are connected in parallel, current
is cumulative. As a result, a large-scale PV system can produce high voltage
and current which could present an increased hazard and may cause serious
injury or death. Do not connect the PV modules directly to the loads since the
variation of the output power dependingonthe solar irradiation causes damage
for the connected load. Do not connect the PV modules directlytotheloads since
the variation of the output power depending on the solar irradiation causes
damage for the connected load. A defective PV module may generate power even
if it is removed from the system. It may be dangerous to handle the PV module
while exposed to sunlight. Place a defective PV module in a carton after Peals
are completely shaded. Do not expose PV module to sunlight concentrated with
mirrors, lenses or similar means. Do not shade portions of the PV module
surface from the sunlight for a long time. The shaded cell may become hot (hot
spot phenomenon) which results in solder joints peeling off.
In case of series connection, the maximum open circuit voltage must not be
greater than the specified.
maximum system voltage. The voltage is proportional to the number of series.
In case of parallel connection, please be sure to take proper measure (e.g.
fuse for protection of module and cable from over current, and/or blocking
diode for prevention of unbalanced strings voltage) to block the reverse
current flow. The current may easily flow in a reverse direction.
INSTALLATION SAFETY
During transportation or storage, unless you reach the installation site,
otherwise, do not open the package of the modules. Please protect the modules’
package. When loading or unloading the modules, please handle with care. Do
not drop the packed pallet of modules down directly. Before open the modules’
package, store the modules in ventilated and dry place.
When opening the modules’ package with knife, be careful not scratching the
module. Do not lift the whole module by grabbing the terminal box or cable
inanysense. Modules are heavy. Handle with care. Do nor
drop PV modules far above ground. Do not dro pone module down on another
module. Do not stand or step on the module. Do not pass by stepping on the
modulee specially when installing, maintain and washingthemodules. Do not hit
or put excessive load on the glass or back sheet. Do not allow objects fall
down on the module. Do not cause an excessive load on the surface of PV module
or twist the frame. Do not scratcher hit at the back sheet. Do not hit on the
terminal box or do not pull the cables. Please notice the ground condition
when the module is placed horizontally with back sheet faced down.
Do not try to unpick the module, remove any parts or the nameplate of the
module. Do not brush oil paint or any other adhesive on the surface of the
module. Do not scratch the insulation coating of the frame (except for
grounding connection). It may cause corrosion of the frame or compromise the
framework strength.
Do not drill holes in the frame. It may compromise the frame strength and
cause corrosion of the frame. Do not repair glass, back sheet or other broken
part of the module. Please install with dry tools in dry condition. Do not
operate when the module is wet, unless wear proper equipment against
electrical shock. Do not grabthe PV module at only one side,the frame may
bend. Grab the PV module at two sides facing eachother. Do not touch the PV
module with bare hands. The frame of PV module has sharp edges and may
causeinjury.
Do not scratch the output cable or bend it with force. The insulation of
output cable can break and may result in electricity leakage or shock.
Do not try artificially to concentrate sunlight on the PV module.Never touch
terminal box or the end of output cables with bare hands when the PV module is
irradiated. Cover the surface of PV module with cloth or other suitable
sufficiently opaque material to isolate the PV module from incident light and
handle the wires with rubber-gloved hands to avoid electric shock.
Always wear protective head gear, insulating gloves and safety shoes (with
rubber soles). Do not touch the PV module unnecessarily during installation.
The glass surface and the frames get hot. There is a risk of burn, or you may
collapse because of electric shock. Do not work under rain, snow or windy
conditions.
Do not touch the terminal box and the end of output cables the cable ends (connectors) with bare hands during installation or under sunlight, regardless of whether the PV module is connected to or disconnected from the system. Lug in the connector tight and ensure the wiring work. Do not unplug the connector if the system circuit is connected to a load. Do not stomp on the glass at work. There is a risk of injury or electric shock if glass is broken. Do not work alone (always work as a team of 2 or more people). When installing modules far above ground, wear a safety belt, do not drop any object (e.g., PV module or tools). Do not wear metallic jewelry which can cause electric shock during installation. Do not wear metallic jewelry which can cause electric shock during installation. Do not damage the back sheet of Modules when fastening the PV modules to a support by bolts.
Do not damage the surrounding PV modules or mounting structure when replacing a Module. Bind cables by the insulation locks. Drooping down of cables from the terminal box could possibly cause various problems such as animal biting, electricity leakage in puddle. Take proper measures for preventing the laminate (consisted of resin, cells, glass, back sheet, etc.) from dropping out of the frame in case the glass is broken. Cables shall be located so that they will not be exposed to direct sunlight after installation to prevent degradation of cables. When installing the module, make sure that the terminal box is on the higher side of the module for better waterproof.
FIRE SAFETY
Consult your local authority for guidelines and requirements for building or
structural fire safety .EGING modules have been listed as Class C according to
IEC 61730-2 standard. For roof installations, modules should be mounted over a
fire resistant covering suitable for this application, with adequate
ventilation between the Modules back sheet and the mounting surface .In order
to maintain the fire class rating ,thedistance between the Modules frame
surface and the roof surface shall be at least 115 mm. Roof constructions and
installations may affect the fire safety of building. Improper installation
may create hazards in the event of a fire. Please install the Modules with
Professional Installers.
INSTALLATION CONDITION
SITE SELECTION AND WORK ENVIRONMENT
In most applications, the PV modules should be installed in a location where
there is no shading throughout
the year. Please make sure that there are no obstructions in the surroundings
of the site of installation. EGING recommend that the PV modules should be
installed in the place where the operating temperature is from -20℃ to46℃.The
operating temperature is the maximum and minimum monthly average temperature
of the installation site. The limit of working temperatures from -40℃ to 85℃.
EGING PV modules must be mounted on proper structure or any other place which is suitable for module installation(such as ground, roof and façade). Make sure flammable gases are not generated near the installation site. The PV modules should not be installed in flooded areas. The junction box should benthic higher side of the module when it is mounted. Lightning protection is recommended for Systems that are to be installed in locations with high probability of lightning strikes.
Take proper steps in order to maintain reliabilityand safety, in case the PV modules are used in areas such
as: Heavy snow areas / Extremely cold areas / Strong wind areas /
Installations over, or near, water / Areas where installations are prone to
salt water damage / Small islands or desert areas.
EGING suggests that modules should not be installed nor operated in areas
where hail, snow, sand, dust, air
pollution, soot, etc., are excessive .Modules must not be sited in locations
where aggressive substances such as salt, salt mist ,salt-water, chemically
active vapors, acid rain, any other type of corrosive agent, could affect the
safely the safely and/or performance of the Modules. EGING PV modules have
also passed salt mist corrosion test according to IEC61701. But corrosion may
occur in the module frame connecting to the bracket portion or the portion of
ground connection, those parts shall be prepared with anti-corrosion treatment
before usage.
TILT ANGLE
The tilt angle of the PV module is the angle between the Module and a
horizontal ground surface. The PV module generates the maximum output power
when it faces the sun directly. IN the Nor thorn Hem is here, the PV modules
should typically face south, and in the Southern Hemisphere, the PV modules
should typically face north. For the detailed installation angle, which is
different in different area, may refer to the recommendation of the
experienced PV modules installation supplier.
Modules mounted flat(0° tilt angle) is not suggested due to dust is easy to be
accumulated and affect power
output. Dust building up on the surface of the modules can impair with modules
performance. EGING recommends installing the modules with a tilt angle of at
least 9 degrees, making it easier for dust to bewished off by rain and more
regular cleaning is not required and water on the surface of module will not
be accumulated, avoiding moldy glass caused to affect the degradation of the
modules because of long timewaster collection on the module surface.
MECHANICAL INSTALLATION
REGULAR REQUIREMENTS
Make sure that module installation mode and bracket system can meet the
expected load, which is requisite assurance that the bracket installer must
provide. Installation bracket system shall be tested and inspected by the
third party testing institution with static mechanical analysis capacity in
accordance with local national standards or international standards. Module
bracket shall be made from durable, corrosion resistant, UV-proof materials.
Modules shall be fixed on the bracket solidly. Use higher brackets in places
with heavy snow accumulations the lowest point of modules will not be shadowed
by snow for a long time. In addition, make the lowest point of modules high
enough so as to avoid shading of vegetation and woods or reduce damage of
sands and stones.
If modules are installed on brackets parallel to the roof or wall, Egging advice the minimum gap between the module frame and the roof/wall shall be 115cm for air ventilation in case of module wire damage. Measure the building is suitable for installation before installing modules on roof. Moreover, seal properlytoprevent leakage. The module frames can appear thermal expansion and cold contraction so Egging advice the frame interval between two adjoining modules shall be no less than 10mm. Make sure that back sheet of modules will not be in contact with bracket or building structures that can pierce into the inside of the modules, especially when the module surface is imposed by pressure.
MOUNTING METHOD
Module and bracket system connection can be realized by mounting holes, clamps or embedded systems. Installation shall follow the demonstration and suggestions below. If installation mode is different, please.
consult Eging and obtain approval. Otherwise, modules may be damaged and
limited warranty will beinvalid. Modules have been certified for maximum
static load on the back side of 2400Pa (i.e. wind load) andamaximum static
load on the front side of either 2400Pa or 5400Pa(i.e. wind and snow load),
dependingonthe modules type (please refer to the following installation
methods for details)
BOLTS MOUNTING
Through the mounting hole on the back frame of the photovoltaic module, the
module can fixed on the support with bolts. One module generally has 4 or 8
mounting holes and is installed with M8 bolts. The details are shown in the
following figure :
-
-
-
-
6 Nut M8X1.25 S35C 5 Gasket 16X1.7 Fe 4 Mount t5 Q235 3 Gasket 16X1.7 Fe 2 Spring gasket 13.5X2.1 Mn65 1 Screw M8X1.25 S35C NO. NAME Size Materia l
-
Installation position and corresponding load of modules:
Installation with bolts into 4 outer holes
Installation with bolts into 4 outer holes
(Beam perpendicular to long sides) | (Beam Parallel to long sides) |
---|---|
Module Type | Mounting hole spacing |
hole spacing | Load Capacities |
EG-XXXM60-HEV | 1200*999 |
+5400/-2400
EG-XXXM72-HEV| 1440999| +5400/-2400| EG-XXXM72-HL/BF-DG| 14401095|
+5400/-2400
EG-XXXM54-HLV| 12001095| +5400/-2400| EG-XXXM60-HU/BF-DG| 14001264|
+5400/-2400
EG-XXXM72-HLV| 14401095| +5400/-2400| EG-XXXM66-HU/BF-DG| 14001264|
+5400/-2400
EG-XXXM60-HUV| 14001264| +5400/-2400| | |
EG-XXXM66-HUV| 14001264| +5400/-2400| | |
CLAMP MOUNTING
Under no circumstances should the clamp touch the glass or deform the
frame. The interface of the clamp to the front of the frame must be smooth and
flat to prevent frame or other components from being damaged. Make sure no
shadowing effect of the fixture. The drain hole cannot be blocked by the
fixture. For framed PV module the clamp must maintain an overlap of 8-11 mm
with the frame of the module (you can change the cross section of the clamp if
the module is securely installed).
| Name| Size| Material
---|---|---|---
1| Bolt| M8| S35C
2| Nut| M8| S35C
3| Gasket| M8| S35C
Installation position and corresponding static loads:
Installation of framed module with fixtures on long sides
Installation of framed module with fixtures on long side
(Beam perpendicular to long sides) | (Beam Parallel to long sides) |
---|---|
Module Type | S(mm) |
Capacities(pa) | Module Type |
Capacities(pa)
EG-XXXM60-HEV| 252-302| +5400/-2400| EG-XXXM72-HE/BF-DG| 302-352| +5400/-2400
EG-XXXM72-HEV| 302-352| +5400/-2400| EG-XXXM72-HL/BF-DG| 397-447| +5400/-2400
EG-XXXM54-HLV| 237-287| +5400/-2400| EG-XXXM60-HU/BF-DG| 361-411| +5400/-2400
EG-XXXM72-HLV| 395-445| +5400/-2400| EG-XXXM66-HU/BF-DG| 467-517| +5400/-2400
EG-XXXM60-HUV| 361-411| +5400/-2400| | |
EG-XXXM66-HUV| 467-517| +5400/-2400| | |
Installation of framed module with fixture on short side
(Beam perpendicular to long sides)
Module Type| S(mm)| Load Capacities(pa)
EG-XXXM60-HEV| L/4(±25)| +1800/-1800
EG-XXXM54-HLV| L/4(±25)| +1800/-1800
Bifacial module can generate power after receiving reflected light on the
back, which can bring additional
power generation gain to the power station. Therefore, for bifacial module, it
is recommended to install the beam parallel to long sides, so that there is no
beam shielding directly below the module. 5.2.3 MOUNTING METHODS WITH
SINGLE-AXIS TRACKER
The bolts and clamps used in this section should follow the requirements in
5.2.1 and 5.2.2. Install and tighten the module clamps to the mounting rails
using the torque stated by the mounting hardware manufacturer. M8 X 1 (1/4”)
bolt and nut are used for this bolting method. Tightening torques
shouldbe16-20 Nm coarse thread bolts, depending on bolt class. Different
tracker systems may have large deviations. Please provide the selected
tracking support supplier and product model and consult Egging for details.
Tracker 1P Bolting/Clamping method:
Module type| Load Capacities(pa)| Module type| Load
Capacities (pa)
---|---|---|---
EG-XXXM72-HEV| 1600-2400| EG-XXXM72-HEV| 1600-2400
EG-XXXM72-HE/BF-DG| 1600-2400| EG-XXXM72-HE/BF-DG| 1600-2400
EG-XXXM72-HLV| 1600-2400| EG-XXXM72-HLV| 1600-2400
EG-XXXM72-HL/BF-DG| 1600-2400| EG-XXXM72-HL/BF-DG| 1600-2400
EG-XXXM60-HUV| 1600-2400| EG-XXXM60-HUV| 1600-2400
EG-XXXM66-HUV| 1600-2400| EG-XXXM66-HUV| 1600-2400
EG-XXXM60-HU/BF-DG| 1600-2400| EG-XXXM60-HU/BF-DG| 1600-2400
EG-XXXM66-HU/BF-DG| 1600-2400| EG-XXXM66-HU/BF-DG| 1600-2400
Tracker 2P Bolting method:
Module type | Load Capacities(pa) |
---|---|
EG-XXXM72-HEV | 1200-2400 |
EG-XXXM72-HE/BF-DG | 1200-2400 |
EG-XXXM72-HLV | 1200-2400 |
EG-XXXM72-HL/BF-DG | 1200-2400 |
EG-XXXM60-HUV | 1200-2400 |
EG-XXXM66-HUV | 1200-2400 |
EG-XXXM60-HU/BF-DG | 1200-2400 |
EG-XXXM66-HUV | 1200-2400 |
EG-XXXM66-HU/BF-DG | 200-2400 |
ELECTRICAL INSTALLATION
WIRINGAND CABLES
To ensure proper system operation and to maintain your warranty, observe
the correct cable connection polarity (Figures 3&4) when connecting the
modules to a battery or to other modules. If not connected correctly, the
bypass diode could be destroyed. PV modules can be wired in series to increase
voltage. Connect wires from the positive terminal of on module to the negative
terminal of the next module. Figure 3 shows modules connected in series.
Connect PV modules in parallel to increase current. Connect wires from the
positive terminal of one module to the positive terminal on the next module.
Figure 4 shows modules connected.
Figure3. SERIES for more voltage
Figure 4.PARALLEL for more current
These junction boxes have been designed to be easily interconnected in series
for their well-connected cable and connector with IP67 protection grad eat
least. Each Modules has two single-conductor wires, one positive and one
negative, which are pre-wired inside the junction box The connectors at the
opposite end of these wires allow easy series connection of adjacent Modules
by firmly inserting the positive connector of a Module into the negative
connector of an adjacent Module until the connector is fully seated.
Use field wiring with suitable cross-sectional areas that are approved for use
at the maximum short-circuit
current of the Modules. EGING recommends installers use only sunlight
resistant cables qualified for direct current(DC)wiring in PV systems. In
general, the maximum number (N) of PV modules in series can be calculated by
dividing the maximum system voltage by the open circuit voltage of the
relevant solar PV modules. When designing the solar PV system, it is necessary
to take into account the characteristic that thevoltage of the solar PV module
changes with the temperature. Considering the voltage increase caused by
temperature drop in extreme environment in winter, the maximum series
connection number of solar PV modules can be calculated by the following
formula.
Maximum system voltage : V ≥ N x Voc x [1 + βx(Tmin − 25)]
V: Maximum system voltage;
N: The number of maximum solar PV modules in series;
Voc: The open circuit voltage of each module ;
β: Temperature coefficient of open circuit voltage of the module;
Tmin: The lowest ambient temperature at installation site;
Cables should be fixed to the mounting structure in such a way that mechanical
damage of the cable and/or
the modules is avoided. While the cables are sunlight resistant and
waterproof, where possible, avoid direct
sunlight exposure and water immersion of the cables.
Maximum parallel strings without proper measures (e.g. fuse and/or blocking
diode): 1 string.
Note: Parallel configuration is not limited in case of taking proper
measure (e.g. fuse for protection of module and cable from overcurrent, and/or
blocking diode for prevention of unbalanced strings voltage) to block the
reverse current flow.
The quantity of string connection for modules should be consulted by the professional institute. Parallel
connection for only 2 pcs modules is not recommended. Type of terminal for field wiring is the same as the Module’s.
Rating required minimum field wiring
Testing standard| Wire size| Temperature Rating
EN 50618:2014| 4mm²| -40℃ to +90℃
CONNECTORS
Keep connectors dry and clean, and ensure that connector caps are hand
tight before connecting the Modules. Do not attempt to make an electrical
connection with wet, soiled, or otherwise faulty connectors. Avoid sunlight
exposure and water immersion of the connectors. Avoid allowing connectors to
rest on the ground. Faulty connections can result in arcs and electrical
shock. Check that all electrical connections are securely fastened. Make sure
that all locking connectors are fully engaged and locked. The Suppliers and
types of connectors should be in accordance with the Standard IEC 62852.
BYPASS DIODES
The junction boxes used with EGING modules contain bypass diodes wired in
parallel with the PV cell strings. In the case of partial shading, the diodes
bypass the current generated by the non-shaded cells, thereby limiting modules
heating and performance losses. Bypass diodes are not over-current protection
devices.
The type and rating of bypass diode to be used must pass the tests (IEC
62790:2014) of the Junction Box. For more details, please see the CDF related
Junction Box.
In the event of a known or suspected diode failure, installers or maintenance
providers should contact Maslar. Never attempt to open the junction box by
yourself .
ELECTRICAL RATINGS
Under normal conditions, a photovoltaic module is likely to experience
conditions that produce more current and/or voltage than reported at Standard
Test Conditions. Accordingly, the values of Sic and Pockmarked on this module
should be multiplied by a factor of 1.25 when determining component voltage
ratings, conductor capacities, fuse sizes and size of controls connected to
the module output.
GROUNDING
The frame grounding is considered within the requirement of local regulation
at the site of installation. When needed this grounding, please refer to below
example of connection. Please be careful in arranging the system ground so
that the removal of one module from the circuit will not interrupt the
grounding of
any other modules. The modules should be grounded to the same electrical
point. Each Module has grounding holes. Do not drill additional grounding
holes on the frame. And the negative pole of the module must be grounded.
Otherwise, the module warranty may be void. An example of acceptable ground
connection using a screw, nut(hardware not provided and washer
retaining a ground screw is shown in figure 5. The size of the grounding cable
should be decided bit professional person who responsible for electrical
installation .In a connection of this type, the hardware(such as a toothed
locked washer / star washer) must score the frame surface to make positive
electrical
contact with the frame. The ground wire must be considered within the
requirement of local and regulation at the site of installation. If steel
parts used for grounding purpose, steel parts must be plated, painted or
enameled for protection against corrosion before usage.
From 1 to 7
7 | Nut | M 4X0.7 |
---|---|---|
6 | Gasket | 9X0.8 |
5 | Toothed lock washer | 8X1.5 |
4 | G round screw | 9X0.8 |
3 | G ask et | 9X0.8 |
2 | Spring gasket | 6 X1.–1 |
1 | Screw | M 4X 0 .7 |
N O. | NAM E | Standard |
Figure: 5.Example of acceptable ground connection
OPERATION AND MAINTENANCE
MODULE APPEARANCE INSPECTION
Check module cosmetic defects with naked eyes , especially:
- Module glass cracks;
- Corrosion at welding parts of the cell main grid;
- Check whether the modules are covered by things;
- Check if any loose or damage screws between the modules and mounting system;
- Check whether there are traces of burning mark on the module back sheet.
CLEANING
Accumulated contaminants on module surface glass will reduce the power
output and lead to local hot spot, such as dust, industrial wasted water and
birds’ droppings. The severity of influence is determined by transparency of
wastes. Small amounts of dust will affect the intensity and evenness of
received solar irradiation but are not dangerous and power will not be reduced
remarkably generally.
During operation of modules, there shall be no environmental factors to shade
modules fully or partially. These environment factors including other modules,
module mounting system, birds dwelling, dust, soil or
plants. These will significantly reduce output power. Egging suggests that the
module surface should not be shadowed in any case. Frequency of cleaning
depends on dirt accumulation speed. In normal situations, rainwater will clean
the module surface and reduce the cleaning frequency.
It is suggested to use sponge dipped with clean water or soft cloth to wipe
the glass surface. Do not use acid and alkaline detergents to clean modules.
Do not use tool with rough surface to clean in any case. When the pressure
water is used, the water pressure on the glass surface of the module must not
exceed 700 KPa. The module must not be subjected to additional external force.
If necessary, use isopropyl alcohol (IPA)
according to the safety instructions to clean and ensure that no IPA flows
into the gap between the edge of
the module and the module frame.
In order to avoid potential risk of electrical shock or burn, Egging suggests cleaning the modules during early morning and evening with low irradiance and low modules temperature especially area within average temperature.
It is forbidden to clean photovoltaic modules under weather conditions with heavy rain, heavy snow or winds greater than class 4.
The back surface of the module normally does not need to be cleaned, but in the event this is deemed necessary, avoid the use of any sharp objects that might damage or penetrating the substrate material.
Water requirements when cleaning:
PH: 5~7;
Chloride or salt content: 0 – 3,000 mg/L;
Turbidity: 0-30 NTU;
Conductivity: 1500~3000 μs/cm;
Total dissolved solids: ≤1000 mg/L;
Water hardness: 0-40 mg/L;
Non-alkaline water must be used, and softened water can be used when
conditions permitted.
INSPECTION OF CONNECTORS AND CABLES
It is suggested to carry out the following preventive inspection twice a year.
Check if any crack or gap of
silicone nearby the junction box. In order to ensure the operation safety of
the power station and modules, the cables and connectors in the modules need
to be fixed accordingly to prevent the harm caused by the continuous impact on
the modules in the strong wind environment. Check whether the sealant at the
junction box is cracked and has gaps.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>