xtemp UXP8201-CE030 Refrigerated And Heating Circulators Instruction Manual
- June 12, 2024
- xtemp
Table of Contents
Operating Instructions
Refrigerated and heating circulators
UXP8201-CE030
UXP8201-CE035
Preface
In order to make the equipment fully functional and ensure safety of the
operator, the equipment, property and specimen, read this manual carefully and
completely. When you have any question that cannot be explained by this
manual, consult us directly or your local distributors.
It is our pleasure to provide service for you.
General safety notes
The equipment is designed for operation with non-flammable heat transfer
liquids only!
No silicone oil is allowed for use with this series of the equipment. The
internal silicone rubber parts may swell when in contact with silicone oil
resulting in leakage of the liquid! For engineering change related to the use
of silicone oil or other liquid, consult Xtemp engineer!
The equipment is intended for heating, cooling, conditioning of specimen
and/or application system by immersion in or external circulating of the
liquids. This leads to potential hazards of high or low temperatures, fire,
and the general hazards related to the application of electrical energy.
The operator is largely protected through the application of the appropriate
standard specifications.
Further hazard sources may arise from the type of material being treated, e.g.
mixing, dissolving, reacting and resultant excessive energy, liquid spillage
resulting from immersion or removal of the specimen, and by the fracture or
rollover of the container and reaction with the heat transfer liquid.
It is not possible to cover all possibilities; they remain largely within the
responsibility and the judgment of the operator!
The equipment must only be used as intended and described in these Operating
Instructions. This includes operation by suitably trained qualified personnel.
The maximum temperature deviation both in normal condition and in electro-
magnetic interference field according to IEC 61326-1 is ±0.2 °C.
Classes of the EMC standard IEC 61326-1
Class A: Equipment for operation only on networks without connected domestic
areas;
Class B: Equipment for operation on networks with connected domestic areas.
Caution, Class A equipment must not be operated on power networks with
connected domestic areas!
For your safety, pay attention to these important symbols as follows, during
moving, installing operating and maintenance. The equipment is designed for
safe operation because of your attention!
Warning, possibility of electric shock!
Inappropriate operation may cause hazard of electric shock and result in
serious personal injury or death!
Caution, hot surface or area!
Accidental touching or approaching may cause burn hazard!
Caution, important note, and always refer to operating instructions (this
document) for detailed information!
The equipment must be operated by well-trained qualified personnel only!
Wrong operation may cause personal injury, damage and/or mal-function of the
equipment!
Symbols on the equipment
**Observe operating instructions!
Warranty**
Requirements for warranty
Xtemp Environments warrants the operational safety and functions of the
equipment only under the conditions that:
- the equipment is operated and serviced exclusively in accordance with its intended purpose and as described in these operating instructions;
- the equipment is not modified;
- only original spare parts and accessories that have been approved by Xtemp Environments are used;
- inspections and maintenance are performed at the specified intervals.
The warranty is valid from the date of delivery to the operator.
Chapter 1 Safety Warning and Instructions
The equipment is designed for safe operation under ambient conditions as follows:
- indoor use;
- altitude up to 2,000 m;
- temperature 5 °C to 40 °C;
- maximum relative humidity 80 % for temperatures up to 31 °C decreasing linearly to 50 % relative humidity at 40 °C;
- mains supply voltage fluctuations up to ±10 % of the nominal voltage;
- transient overvoltage up to the levels of overvoltage category II;
- temporary overvoltage’s occurring on the mains supply;
- Pollution degree 2 or less of the intended environment;
- Wet location
Excessive high or low temperature and/or humidity will significantly degrade
electric safety of the equipment!
Note the effect of the altitude on the boiling point of the heat transfer
liquids!
1.2 Safety warning
When heating, cooling and conditioning with specimen or application system
which is intrinsically explosive, flammable or toxic or, which liberates
hazardous substances as result of reacting, dissolving or mixing under
operating temperature range for normal use, safety acts and regulations for
the particular chemicals and experimental laboratory shall be observed!
Not applicable for specimen or application system which develops tremendous
energy as result of reacting, dissolving or mixing under operating temperature
range for normal use!
The dielectric strength of the equipment may be degraded if after transport or
storage in humid conditions. The equipment shall be powered as for normal use
and conditioned at its maximum operating temperature or 105°C, whichever is
smaller, for at least 1h before commissioned for normal use. Warning, hazard
of electric shock during the dry-out!
1.3 Caution
Caution, Risk of burn hazard!
Do not touch or approach parts or area with high temperature, for example,
bath cover and the heat transfer liquid when maintained at operating
temperature over 60°C!
Pull the temperature of the heat transfer liquid as close as possible to the
ambient before attempting to shut down the equipment, except when operations
as such are prohibited for the specimen! Warning, Hazards of burn and
possible electric shock resultant from unattended hot temperature or
condensing and degraded dielectric strength!
Caution, Hazard of overflowing or low level!
Never attempt to initiate the equipment if no heat transfer liquid is filled
or filling volume is lower than the minimum level as specified; Never move the
equipment if the bath tank is fully filled with the heat transfer liquid; The
liquid level may change with the heating and cooling of the equipment, and
with the immersion or removal of the specimen!
Disconnect the application system from the equipment only after proper
draining of the heat transfer liquid, especially when the application system
is charged to maximum volume by additional filling of the liquid!
Class I/NFL Caution, Risk of fire!
The Class I/NFL series of the equipment is designed for operation with non-
flammable heat transfer liquids only! Water and mixture of water and glycol
are the most popular non-flammable heat transfer liquids appropriate for the
equipment.
No silicone oil is allowed for use with this series of the equipment. The
internal silicone rubber parts may swell when in contact with silicone oil
resulting in leakage of the liquid!
Class III/FL Caution, Risk of fire!
The Class III/FL series of equipment are designed for operation with non-
flammable and flammable heat transfer liquids! Alcohol and silicone oils are
the most common flammable heat transfer liquids. Use special care when using
with these flammable liquids, including the proper setting of the adjustable
overheating protection device.
The circulation of the heat transfer liquid is important for performance and
safety! The kinematic viscosity, immersion and distribution of the specimen
and, flow resistance of the application system and the circulating tubing
significantly influence the circulation of the liquid!
The first time commissioned for use or when exchange of the heat transfer
liquid and, immediately after startup of the circulating pump, check if any
liquid leakage exists in the external circulating tubing and fitting, if head
pressure of the pump and flow of the heat transfer liquid are in their rated
range and, if the liquid level is in its range for safe operation!
Mixing and use of heat transfer liquids with different physical and/or
chemical properties may adversely affect the performance and safety of the
equipment! The liquid shall be completely drained and removed before
attempting to charge the other. When necessary, consult Xtemp or supplier of
the liquid for particular application!
Never touch or attempt to handle the heat transfer liquid with temperature
higher than +60°C!
Caution, burn hazard!
No draining of the heat transfer liquid with potential of chemical or
biological hazard! Collect and identify the heat transfer liquid for future
use! Consult Xtemp or manufacturer of the liquid for proper disposal!
Install an extraction system over the bath opening, if the operating of the equipment could lead to liberation of hazardous air or gas mixture, for example the evaporation of the heat transfer liquid! The rating of the fume hood shall be at least the maximum possible exhausting temperature! If necessary for safety, additional temperature limiting and warning devices, condensate accumulator shall be installed for the extraction system!
Caution: Note the following when connecting the equipment to an external application system:
- The external circulating pipe, including flexible tubing and hose, shall be connected only after the equipment and application system are well seated and installed. The length and distribution path shall be as short as possible and be so arranged that no kink and other mechanical stress develops during normal use which otherwise may result in thermal and/or liquid hazards!
- Flexible hose, fitting and coupling are important for the safe operation of the equipment; Use only hose, fitting and coupling provided with the equipment or recommended by Xtemp!
- The ratings of pressure and temperature for the hose, fitting and their resistance to the chemicals shall meet the requirements of the operating temperature, pressure range of the heat transfer liquid to be delivered for application system!
- Thermal insulation for hose, fitting, coupling and the application system are important for performance and safety! The materials of the insulation shall meet the requirements of the maximum operating temperature range!
- If no external circulating is necessary, use hose, fitting and coupling to short-circuit the liquid connections as for an external application!
Keep the cables and wiring protected by conduit and/or hose and well secured; keep them clearly away from direct contact with any exposed heated/cooled parts of the equipment and application system!
Caution: Risk of frozen hazard!
When water is employed as heat transfer liquid, and when intended for
standstill for long period and when experiencing low ambient is possible, run
the equipment at operating temperature close to ambient for at least 1hr.
Empty the bath containing water, and remove the water completely.
Disconnect the equipment and remove the mains plug from power source.
Do not disassemble or exchange assembly parts and electric circuits by
unauthorized personnel!
Hazard of possible electric shock! In case of repairing, contact your local
distributors or supporting technicians.
Always remove the mains plug from the socket before cleaning, moving,
maintenance or repairing!
****The first time powering up after repairing or standstill for long period,
or at designated intervals under normal use, check the functionality of the
following parts or components:
Hydraulic tightness and fastening of flexible tubing for circulating, status
of insulation, at three months intervals; Aging, resistance to chemical stress
from the heat transfer liquid and its temperature and pressure of flexible
hose, at 6 months intervals; Cutoff capability of the safety temperature
limiter (STB) at 6 months intervals.
Chapter 2 Installing and Operating
2.1 Installing
2.1.1 Unpacking
Unpack the equipment and sort the accessories respectively and carefully. The
packing carton, pallet, packing buffering stuffs etc., are designed for one
shipment only. For future shipment, prepare the packing materials as well as
the way of packing as received.
Check the equipment and accessories for potential transport damages. If there
is any damage visible on the equipment, a claim must be filled in writing with
the freight forwarder; a notification to the freight forwarder is obligatory
so that the shipment can be examined. Inform your local distributor or
supplier for any missing accessories and servicing or repairing.
Accessories lists(UXP8201-CE030)
Part Number | Qty | Descriptions | Remarks |
---|---|---|---|
DSG00709-2 | 1 | Operating Instructions | This document |
ERSG0202 | 2 | Fuse (250V-, 15A), D5L20 | Breaking capacity, 1500A |
BJGW0002 | 1 | External circulating kit | Assembled |
SZGJO105 | 1 | Flow adaptor L silicone | Assembled |
SZGJO115 | 1 | Bypassing U tube silicone | Assembled |
BJGW0105 | 1 | Bath cover assembly | UXP8201-CE030 |
Accessories lists(UXP8201-CE035)
Part Number | Qty | Descriptions | Remarks |
---|---|---|---|
DSG00709-2 | 1 | Operating Instructions | This document |
ERSG0202 | 2 | Fuse (250V-, 15A), D5L20 | Breaking capacity, 1500A |
BJGW0002 | 1 | External circulating kit | Assembled |
SZGJO105 | 1 | Flow adaptor L silicone | Assembled |
SZGJO115 | 1 | Bypassing U tube silicone | Assembled |
BJGW0105 | 1 | Bath cover assembly | UXP8201-CE035 |
Do not disassemble or exchange assembly parts and electric circuits by
unauthorized personnel! Hazard of possible electric shock! In case of
repairing, contact your local distributors or supporting technicians.
In case of damaged shipment and dent, deformation or distortion of the
enclosure, contact authorized local distributor or Xtemp personnel.
2.1.2 Installing
Install the equipment on a rigid, nonflammable surface and well-ventilated
place. The bench should be 600~800mm high for ease of operation. Keep enough
space between wall and back of the equipment, and keep clear of obstacles
around the bottom of the equipment for better ventilation. If the equipment is
installed on an unstable surface or floor, abnormal noise may be generated.
The voltage, frequency and current of the power supply must be rated at least
the same as those designated on the name plate of the equipment. The switch
board is recommended to be on the back right side of the equipment and
equipped with outlet matching the power plug of the equipment with protective
ground (PE).
For possible wet location conditions, where cycle of evaporating and
condensing, overflowing or spillage may occur and for protection against
hazard of possible electric shock, use power socket with appropriate IP
protection and additional residual current circuit breaker (RCD) with rated
breaking capacity!
Power socket, switchboard with circuit breaker or residual current circuit
breaker for the equipment shall be located closest to the equipment with good
clearance for easy access, so that immediate interruption is possible under
emergent circumstance.
The minimum distance away from the ventilating holes at the back of the
equipment to the wall, furniture or other installations shall be 300mm! The
inlets of fresh air and outlets of exhausting air of the equipment shall be
kept clear of any obstacles.
Keep the equipment away from hot-air emitting source, direct sunshine, strong
magnetic field and electric sparks!
Neither contamination of high concentration dust or corrosive gas, nor strong
airflow surrounds!
Voltage, frequency and current for power supply must meet the requirements as
designated on the nameplate! Use power socket matching the power plug of the
equipment. Hot line (L)and neutral line(N)for single phase equipment must not
be reversed!
Socket for power supply must be equipped with protective ground
(PE) to prevent against hazard of possible electric shock.
2.1.3 Connecting to an application system where necessary
The external circulating pipe, including flexible tubing and hose, shall be
connected only after the equipment and application system are well seated and
installed. The length and distribution path shall be as short as possible and
be so arranged that no kink and other mechanical stress develops during normal
use which otherwise may result in thermal and/or liquid hazards!
Flexible hose, fitting and coupling are important for the safe operation of
the equipment; Use only hose, fitting and coupling provided with the equipment
or recommended by Our company! The ratings of pressure and temperature for
the hose, fitting and the jacket, container or heat exchanger of the
application system, their chemical resistance to the heat transfer liquid
shall meet requirements of the operating temperature and/or pressure range of
the heat transfer liquid to be delivered by the equipment!
Thermal insulation for hose, fitting, coupling and the application system are
important for performance and safety! The materials of the insulation shall
meet the requirements of the maximum operating temperature range!
Keep the cables and wiring protected by conduit and/or hose and well secured;
keep them clearly away from direct contact with any exposed heated/cooled
parts of the equipment and application system!
2.2 Descriptions
2.2.1 Front view
Fig 1 Front view
02 Controller panel and power switch
03 Fresh-air inlets
20 Liquid connection, return
21 Liquid connection, outlet
76 bath cover
2.2.2 Back view
Fig 2 Back view
04 Exhausting openings
18 Handle
22 Power cord
23 Drain device
29 IEC socket and cable for compressor
The inlets of fresh air and outlets of exhausting air of the equipment shall
be kept clear of any obstacles, so that no close-loop of the air circulating
may develop.
If no external circulating is necessary, use hose, fitting and coupling to
short-circuit the liquid connections as for an external application system!
The equipment is not applicable for specimen or application system which
develops tremendous energy as result of reacting, dissolving or mixing under
operating temperature range for normal use!
2.2.3 External circulating kit (assembled)
Fig 4 External circulating kit
101 Liquid connection assembly
102 U-type silicone liquid shortcut
103 L-type silicone adaptor, LL
104 L-type silicone adaptor, SL
The flow rate and direction at the external circulating return may also
influence the performance and safety of the equipment! Reduced flow may
produce an uneven circulating of the liquid and temperature distribution,
while strong circulating may lead to overflow or splash of the liquid! Flow
adaptor or limiter may be used for proper adjustment of the flow rate and
direction.
The independent safety temperature limiter (STB) and liquid level cut out
(LLCO) are important for safety. Class I/NFL equipment is incorporated with
fixed STB for non-flammable heat transfer liquid only, while Class III/FL
with adjustable STB and liquid level cut-out for flammable heat transfer
liquid.
The pump inlet shall be clear of any obstacles! The minimum distance for the
pump inlet to the bath bottom shall be 20mm. Sometimes a piece of paper mark
from the specimen, gauze or collection of dirt may block the flow of the pump
and circulation, resulting in degradation of performance and overheating!
Regular check of the STB and, level switch if equipped, is requirement for
safety. Refer to 4.2 for detailed procedures.
****Caution, flammable liquid, no fire!
Flammable heat transfer liquid may be used for Class III/FL equipment. Use
special care when using with flammable liquids!
If any flammable liquid is put into the equipment, apply warning mark of
flammable hazard visible to the operator and responsible body.
WARNING: Keep clear of obstruction all ventilation openings in the enclosure,
the application system or in the structure for building-in.
WARNING: No smoking! No flame! Do not use electrical parts which may produce
spark when operating around the equipment and the application system.
WARNING: Drain and recover the liquid when the equipment idles, if the
flammable heat transfer liquid is used with open bath tank and, if it is
highly volatile at ambient.
The first time powering up after repairing or standstill for long period, or
at designated intervals under normal use, check the functionality of the
following parts or components:
Cutoff capability of the safety temperature limiter (STB) at 6 months
intervals;
Cutoff capability of the low liquid level cut out (LLCO), at 6 months
intervals!
2.2.4 Put into operation
Use heat transfer liquid only as designated for the equipment. Use non-
flammable heat transfer liquid for Class I/NFL equipment only. No silicone oil
may be used with Class I/NFL equipment.
Flammable heat transfer liquid may be used for Class III/FL equipment. Use
special care when using with flammable heat transfer liquid!
Fill the bath tank with applicable heat transfer liquid to a level appropriate
for operation. Keep in mind that the level may change with the heating and
cooling of the equipment, and immersion and removal of the specimen.
If an application system is connected, additional liquid may be necessary for
appropriate level once initiated.
Class I/NFL
Caution, Risk of fire!
The Class I/NFL series of the equipment is designed for operation with non-
flammable heat transfer liquids only! Water and mixture of water and glycol
are the most popular non-flammable heat transfer liquids appropriate for the
equipment.
No silicone oil is allowed for use with this series of the equipment. The
internal silicone rubber parts may swell when in contact with silicone oil
resulting in leakage of the liquid!
Class III/FL Caution, Risk of fire!
The Class III/FL series of equipment are designed for operation with non-
flammable and flammable heat transfer liquids! Alcohol and silicone oils are
the most common flammable heat transfer liquids. Use special care when using
with these flammable liquids, including the proper setting of the adjustable
overheating protection device.
Caution, Hazard of overflowing or low level!
Never attempt to initiate the equipment if no heat transfer liquid is filled
or filling volume is lower than the minimum level as specified; Never move the
equipment if the bath tank is fully filled with the heat transfer liquid; The
liquid level may change with the heating and cooling of the equipment, and
with the immersion or removal of the specimen!
Disconnect the application system from the equipment only after proper
draining of the heat transfer liquid, especially when the application system
is charged to maximum volume by additional filling of the liquid!
Chapter 3 Controller Descriptions and Operation
3.1 Controller panel
Fig 5 Controller panel
60 Reset button (for resetting when alarming, the
circle indicating the location)
61 Display for temp and working parameters
62 Status indicators
63 Key board
64 Power switch
3.1.1 Display for temperature and working parameters
Normally it displays the bath temperature once switched on and initiated or
oFF when standstill.
Other possible symbols include: SEt, Ht, Lt, CooL, Auto, Atc AS, ASd, cF,
dEFt, ESc, Stb. Related definitions are as follows:
Ht: This parameter is an absolute value and used for reminding only. When
temperature in the bath is higher than the set value, Ht is displayed. The
controller will trigger a beeping alarm and disable the heating. While the
actual temperature is higher than the Ht setting, the Ht may be set to a
higher value by pressing so that Ht beeping can be cleared. If the actual
temperature is recovered to lower than the Ht setting, the Ht alarm will
disappear automatically with seconds of delay, or may be cleared immediately
by pressing heating is possible only if the Ht is cleared.
Lt: This parameter is an absolute value and used for reminding only. When
temperature in the bath is lower than the set value, Lt is displayed. The
controller will trigger a beeping alarm.
While the actual temperature is lower than the Lt setting, the Lt may be set
to a lower value by pressing . The so that Lt beeping can be cleared. If the
actual temperature is recovered tohigher than the Lt setting, the Lt alarm
will disappear automatically with seconds of delay, or may be cleared
immediately by pressing .
CooL: Control parameter for compressor, and select among three modes, Auto, on
and oFF:
on:Compressor cooling with counter heating by PID, provided that the actual
temperature is below 40 °C.
Auto:Compressor on and off automatically. During heating up, once full heating
is necessary, the compressor will be turned off, until the actual temperature
close to set temperature. if the set temperature over 40 °C, and no cooling
is required, the compressor will also be turned off. If the set temperature is
lower than the actual temperature, and when the actual temperature below 40
°C, the compressor will be switched on and keep working continuously.
oFF:The compressor is disabled, and the heater is regulated by PID.
Auto: Select between AoFF and Aon, which means manually starting and
automatically starting.
Atc: Absolute temperature calibration (Atc), when the temperature displayed
differs from the temperature measured by a standard thermometer, Atc is used
to calibrate the display.
AS: Timer for automatic startup. Valid only when the equipment is in standby
mode. The equipment will be initiated automatically once the set time elapses.
The equipment may be started immediately if is operated regardless of the
remaining AS time.
ASd: Timer for automatic shutdown. Valid only when equipment is in operating
mode. The equipment will be terminated automatically once the set time
elapses. The equipment may be terminated immediately if is operated
regardless of the remaining ASd time.
cF: Shifting of the temperature measurement units. c means degree Centigrade
and F means degree Fahrenheit. cF setting affects all the parameters related
to temperature, such as the display temperature, setting temperature, Ht, Lt
and so on. Relationship between c and F is as follows °F=32+1.8×°C,
°C=(°F-32)/1.8
For example: 0°C=32°F, 212°F=100°C.
dEFt:Return to the factory default setting. It may be used when system halts
or any other abnormal situation occurs.
ESc: Exit the SEt menu.
°F=32+1.8×°C, °C=(°F-32)/1.8
For example: 0°C=32°F, 212°F=100°C.
dEFt:Return to the factory default setting. It may be used when system halts
or any other abnormal situation occurs.
ESc: Exit the SEt menu.
3.1.2 Working status indicating
Heater: Press for more than 2 seconds to initiate the circulating pump. Orange
LED will be steadily lit with full power heating; When LED flashes, the
heating power is automatically adjusted to meet actual need. LED flashing
frequency keeps constant when temperature is stabilized.
Compressor: Press for more than 2 seconds to initiate the circulation. If
cooling is desired, blue LED lights with about 2min delay, after which
refrigeration is possible.
Circulating pump: for more than 2 seconds to initiate the circulating pump
with LED on, after which the heating operation is possible.
Alarm: Red LED is on, when there is beeping and warning for safety or error is
triggered.
The warning or error of the sensor may be accompanied by the following:
Er01: Warning of temperature sensor short-circuit.
Er02: Warning of temperature sensor open-circuit.
ourh: Warning of the bath temperature far beyond Ht.
lEuL: Class III/FL only, the liquid level in the bath is below the minimum.
Once LEuL alarm is triggered, LED flashes for warning and both the heating and
circulating pump are disabled. The warning and protection against heating and
circulating are locked even if the level is recovered. For resetting, press
the RESET button (invisible button, Fig 5-60), followed by. Since the RESET
button is invisible, make sure that the operation is valid.
Stb: In case Stb or LLCO is triggered and an alarm is activated, the alarm
will be locked with a continuous beeping even if the temperature is recovered
or level is resumed. For clearance of the alarm, depress the RESET button as
shown in Fig 5-60 followed by. Since the RESET button is invisible, make sure
that the operation is valid.
KEY | NO | FUNCTION | OPERATION | REMARKS |
---|---|---|---|---|
1 | Initiate or terminate the circulating pump | Press and hold the key for | ||
more than 2 seconds | Temperature regulating is possible only if the |
circulating pump is activated and temperature control is initiated.
| 2| Set the working
temperature| Press the button for
less than 1 second| SEt is first displayed, then press to enter change the
digits by pressing accept the setting by pressing
| 3| Display the parameters of temperature programming| Press the button for
less than 1 second| When the programming is in progress, it displays the
segment number, temperature, remaining time and cycles of active program.
The parameters are cycled and displayed for 2 times with each delay of about 2
seconds, and then exit automatically.
| 4| Set the working parameters| Press and hold the key for more than 2
seconds| Ht is first displayed, press for Lt, Cool, Auto, Atc , AS, ASd, cF,
dEFt, ESc Press to enter for change of a definite setting of the working
parameter, for example Ht.
Change the digits or setting by pressing , accept the setting by pressing to
enter, or confirm and exit automatically in 4 seconds.
+| 5| Set the programming parameters| Press and at the same time then release
the buttons| The function is optional. The parameter of first segment t1 is
displayed. Press to display original time, press for a new value, confirm the
setting by pressing to display temperature of the first segment M1; Press to
display the original temperature, press the setting by pressing for a new
value, confirm to enter the setting of second segment. 5 Following the steps
as for the first segment for segments 2, 3 … to 6 maximum. If segments of
less than 6 are desired, for example only 2 segments are necessary, use
00:00 for t3
after confirmation of M2.
Press to display n, which means the number of program circles.1 ~99 means 1
cycle to 99 circles maximum and 0 means unlimited circles.
Press to confirm and exist.
Default parameters: t= 00:00, M=25, n=99
+| 6| Initiate or
terminate
programming| Press
and at the same time and release the buttons| The temperature program may be
initiated either in standby mode or running mode. If Auto setting is Aon, the
equipment will automatically resume to the mode before the program is
initiated once the program is terminated automatically. The setting of
Auto=Aon is recommended, if continuous operation is desired after unexpected
interruption of short power failure.
+| 7| Initiate or terminate the timer| Press and at the same time, then
release the buttons| The timer function is optional. When the equipment is in
running mode, timer for ASd is valid, while the equipment is in standby mode,
timer for AS is valid. The time is set by AS and ASd.
+| 8| Move between settings or increase the value| Press the key shortly for
slow movement and continuously for fast changing|
| 9| Display scanning for internal and external temperatures| Press the
button shortly| Touch the button to shift the temperature display, touch again
or wait for 5 seconds to resume the temperature display. For internal
temperature, symbol of c is fixed, while for external temperature, symbol of c
flashing
3.2 Set the working parameters
- Set the working temperature Refer to No.2 in the table.
- Set high temperature limit value Press for more than 2 seconds until Ht is displayed. Press to enter Ht setting. Original Ht value is displayed, and press to get the desired value. Press and exit the SEt screen or exit automatically in 4 seconds.
- Set low temperature limit value
Press for more than 2 seconds until Ht is displayed. Scroll the menu by displays Lt. Press to enter Lt setting. Original Lt value is displayed, press get the desired value. Press 4 seconds.
3.3 Constant temperature control
- Connect the power by inserting the power plug, or engage the circuit breaker on the switch board.
- Turn on power switch and the controller runs self-check to display: 88888, LEDs on, software version number, AoFF (Aon will show up if Auto is set to Aon) settings for Ht、Lt. Refer to 3.5 for procedures about Aon and AoFF setting. The software version number may change with technique updates.
- Check and/or set the working temperature, refer to No. 2 in the table.
- If the equipment is in the standby state, press for more than 2 seconds, the circulating pump will start to operate and the heater temperature. is on if the setting is higher than the actual
- When the temperature in the bath is lower than the set value, heating LED is on and the equipment is in operation and start to heat. When the set temperature and actual temperature are quite different, heating LED will be steadily lit with full power heating and the temperature will go up with full speed. As the temperature approaches the set point, the LED flashes as desired and the controller decreases the power for the heater. With the actual temperature equals to the set temperature, the controller keeps constant power output.
- To terminate the temperature control, press for more than 2 seconds. The circulating pump and heater are stopped. The LEDs go off, and the display shows oFF
Connect the power from behind the equipment. Plug in and remove the cable by
directly holding the plug. No dragging of cable in any part. Protect the cable
from being damaged by contacting with the hot/cold surface of the equipment
or mouse etc!
Caution, Hazard of overflowing or low level!
Never attempt to initiate the equipment if no heat transfer liquid is filled
or filling volume is lower than the minimum level as specified; Never move the
equipment if the bath tank is fully filled with the heat transfer liquid; The
liquid level may change with the heating and cooling of the equipment!
Disconnect the application system from the equipment only after proper
draining of the heat transfer liquid, especially when the application system
is charged to maximum volume by additional filling of the liquid! The liquid
level will change significantly with the immersion or removal of the
specimen!
The circulation of the heat transfer liquid is important for performance and
safety! The kinematic viscosity, immersion and distribution of the specimen
and, flow resistance of the application system and the circulating tubing
significantly influence the circulation of the liquid!
The first time commissioned for use or when exchange of the heat transfer
liquid and, immediately after startup of the circulating pump, check if any
liquid leakage exists in the external circulating tubing and fitting, if head
pressure of the pump and flow of the heat transfer liquid are in their rated
range and, if the liquid level is in its range for safe operation!
Mixing and use of heat transfer liquids with different physical and/or
chemical properties may adversely affect the performance and safety of the
equipment! The liquid shall be completely drained and removed before
attempting to charge the other. When necessary, consult manufacturer or
supplier of the liquid for particular application!
Never touch or attempt to handle the heat transfer liquid with temperature
higher than +60°C!
Caution, burn hazard!
No draining of the heat transfer liquid with potential of chemical or
biological hazard! Collect and identify the heat transfer liquid for future
use! Consult manufacturer or supplier of the liquid for proper disposal!
Install an extraction system over the bath opening, if the operating of the equipment could lead to liberation of hazardous air or gas mixture, for example the evaporation of the heat transfer liquid! The rating of the fume hood shall be at least the maximum possible exhausting temperature! If necessary for safety, additional temperature limiting and warning devices, condensate accumulator shall be installed for the extraction system!
3.5 Setting for restart mode after power failure, Auto
Press for more than 2 seconds until screen displays Ht. Scroll the menu by
displayed, then press until Auto is to enter. Use automatic power-on function,
use Aon, and press to select between Aon and AoFF. For to confirm and exit
the setting. In this case, the equipment will automatically resume to the
status before power being interrupted. If the mode is set to AoFF, press for
more than 2 seconds to start the equipment where necessary.
Other settings
- The default unit for temperature measurements and setting is degree centigrade. It may be changed to Fahrenheit or Centigrade as desired. Refer to Table and item No. 4, use cF and similar steps for procedures.
- The compressor is set to Auto as default, it works automatically when the cooling is required, and stop when full heating is desired, at or below temperature of 40 °C. The compressor may be disabled not to work at any time by setting Coolto oFF, or to work continuously by setting Coolto on. The compressor will not work at any time at temperature over the limit. Refer to Table and item No. 4, use Cool and similar steps for procedures.
Use special care to change Cool setting. The compressor will never work with Cool set to oFF, and will work continuously even if full heating is desired with Cool set to on.
Chapter 4 Maintenance
4.1 Regular maintenance
- Clean the bath interior and exterior of the equipment periodically to keep the equipment clean;
- Check for hydraulic tightness and fastening of the connections for flexible hose, fitting and coupling;
- Check fixing screws periodically, and if any loose, fix it.
Remove the plug from power line before cleaning. Use soft dry tissue to clean
the bath interior and avoid any splashing or washing!
If any water or other conductive material fall into the equipment containing
electric and/or electronic parts and components, disconnect the power
immediately. Power on only after water or foreign material is completely
evaporated or removed.
4.2 Regular check of the STB
Regular check of the STB is required for safe operation. Intervals of six
months for normal use, or the first time powering up after repairing or
standstill for long period, are recommended for regular check of the
functionality. Check the STB as follows:
- Fill the tank with water to level just over the highest point of the heating coil;
- Set the temperature at 10°C above the ambient and/or the liquid, so that it keeps heating, LED is continuously on;
- Initiate the temperature control as for normal use, i.e. the pump is circulating and heating is in full capacity;
- Drain the bath so that the heater and the STB are exposed to the air completely. Make sure no liquid spraying out from the circulating return, dripping from the drain device on the bench or floor;
- The liquid evaporates immediately from hot surface of the heater. Keep running dry for a couple of seconds until the Stb warning is displayed. Caution, Never run dry for more than 90s!
- Close the drain device, and fill the tank with water. The STB resets automatically once temperature resumes to below designated limit value.
Caution, Risk of burn hazard and liquid spillage!
Do not touch hot surface of the heater! Keep away from evaporating hot steam!
Use protective gloves or glasses if necessary!
Never run dry for more than 90s! Overheating of the coil may damage the heater
or degrade its insulation strength!
The first time powering up after repairing or standstill for long period, or
at 6 months intervals under normal use, check the functionality of the safety
temperature limiter (STB)!
4.3 Checking and replacing the fuse
With the mains plug connected and power switch in “on” position and if no LED
and digits display, check the fuse first. If any doubt that checking and
replacing fuse is necessary, use a fuse with the same size and capacity as
rated and do as follows:
- Make sure the mains plug has been removed;
- Loosen the two screws on the top and 4 screws at the back of the controller as shown in Fig 6- 80. Remove the cove plate and check or replace the fuse;
- Replace the cover and fasten the six screws.
Do not disassemble or exchange assembly parts and electric circuits! Hazard of
possible electric shock!
Except for replacing the fuse, there is no other part necessary for customer
to disassemble or repair. If repairing is desired, contact with authorized
engineer.
Always remove the mains plug from the power socket when performing checking or
replacing the fuse, and never use any fuse different from the original one.
Secure the fuse once checked or replaced. For servicing or maintenance, call
authorized service engineer.
Fig 6 Location of the fuse and Pt100 sensor
81 Mains fuse (15A)
82 Terminal for Pt100
4.4 Checking and charging of the refrigerated equipment If the compressor
LED is on, while the equipment does not cool down, check function of the
refrigerated equipment as follows:
- Set the operating temperature at 20°C, while keeping the compressor running (for example, the ambient temperature is higher than 25°C while keep the refrigerating running);
- Check if fresh air intakes and exhausting air leaves freely. Use one piece of A4 size paper and put it over surface of the inlet (Fig 1-3) with ventilating openings for checking intake of the fresh air. If the paper is hold by the intake air, it is indication of free air movement. Otherwise check the cleanness of the condenser inlet and the function of the condenser fan;
- After continuous operation of the compressor for about 20 min, check the outlets of the exhausting air. Warm or even hot air flow indicates regular function of the refrigerated equipment. Otherwise there exists a leakage or malfunction of the refrigerating system;
- If any doubt that checking and charging of the refrigerating system is necessary, consult an authorized local distributor or engineer!
Chapter 5 Equipment Overview and Specifications
5.1 Equipment overview
- SMT assembled and microprocessor-based precise dynamic temperature control with temperature stability up to ±0.05°C;
- Independent immersion controller head, DIY for precise temperature system with different bath capacity and style;
- Immersion bath and external circulator in one unit, helps you to save money and make more space;
- Absolute temperature calibration (ATC) for accurate temperature control and AUTO-restart after power failure for continuous uninterrupted operation.
5.2 Specifications
Models | UXP8201-CE030 | I UXP8201-CE035 |
---|---|---|
Temp range @20 °C (68 °F) ambient | °C (°F) | -26-+100 (-14.8+212) |
Temperature stability | ±°C (°F) | 0.02-0.05 (0.04-0.09) |
Cooling Capacity ambient | +20 °C (68 °F) | W |
0 °C (32 °F) | @ 20°C (68 °F) | |
W | 200 | 220 |
-20 °C (-4 °F) | W | 50 |
ACC temperature | °C (°F) | 40 (104) |
Pump flow rate max | L/min (gam) | 20 (5.3) |
Pump pressure max | mbar (psi) | 350 (5.1) |
Temperature programming | 6 segmentsx99h59min, 99 cycles | |
Refrigerant | HFC 134a | |
Bath material | TIG welded, SUS 304 | |
Wetted materials | Welded bath tank of SUS 304 |
Heater, pump and evaporator of SUS 316L
House materials| SPCC steel with powder coating
Liquid connections for external circulating| Nipple, 1/2″, 12.7mm (od)
Classification for HTL to DIN 12876| Class 1/NFL, non-flammable
Heat Transfer Liquid, No silicone oil
Safety features & auxiliary functions| Protection and warning against short
/open-circuit PT100,
High-temperature cut off and low temperature alarm,
Protection against stalled pump motor or dry heating,
ATC (Absolute Temperature Calibration),
Auto start-up or standby after power failure
EMC for USA and Canada| Class A
(for operation only on networks without connected
domestic areas)
Duty cycle| Continuous
Capacity| L(G)| 6.5-9 (1.72-2.38)| 9-13 (2.38-3.43)
Bath size (WDH)| mm On)| 170x350x190 (6.7×13.8×7.5)| 300x350x190
(11.8×13.8×7.5)
Immersion depth| mm (in)| 160 (6.3)
Bath opening (WD)| mm On)| 170×180
(6.7×7.1)| 300×180
(11.8×7.1)
Overall size WxDxH| mm On)| 265x570x640
(10.4×22.4×25.2)| 395x570x640 (15.6×22.4×25.2)
Heater wattage| W| 1,000
Packing size (WDHJ| mm (in)| 340x625x 735
(13.4×24.6×28.9)|
Net weight| Kg (Ibs)| 37 (81.6)|
Gross weight| Kg (Ibs)| 39 (86.0)|
Voltage and frequency| 115 V-, 60 Hz
Current draw| A| 14| 15
Specifications are subject to change without notice!
XTEMP ENVIRONMENTS (SHANGHAI) CO., LTD.
http://www.xtemp-usa.com/
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>