xtemp UXP 8011-HC090 Immersion Heating Circulators Instruction Manual

June 12, 2024
xtemp

xtemp UXP 8011-HC090 Immersion Heating Circulators Instruction Manual
Immersion Heating Circulators

Preface

In order to make the equipment fully functional and ensure safety of the operator, the equipment, property and specimen, read this manual carefully and completely. When you have any question that cannot be explained by this manual, consult your local distributors orsupporting technicians. It is our pleasure to provide service for you.

General safety notes
The equipment is designed for operation with non-flammable heat transfer liquids only!
No silicone oil is allowed for use with this series of the equipment. The internal silicone rubber parts may swell when in contact with silicone oil resulting in leakage of the liquid! For engineering change related to the use of silicone oil or other liquid, consult Xtemp engineer!
The equipment is intended for heating, conditioning of specimen and/or application system by immersion in or external circulating of the liquids. This leads to potential hazards of high or low temperatures, fire, and the general hazards related to the application of electrical energy.
The operator is largely protected through the application of the appropriate standard specifications.
Further hazard sources may arise from the type of material being treated, e.g. mixing, dissolving, reacting and resultant excessive energy, liquid spillage resulting from immersion or removal of the specimen, and by the fracture or rollover of the container and reaction with the heat transfer liquid.
It is not possible to cover all possibilities; they remain largely within the responsibility and the judgment of the operator!
The equipment must only be used as intended and described in these Operating Instructions. This includes operation by suitably trained qualified personnel.
The maximum temperature deviation both in normal condition and in electro- magnetic interference field according to IEC 61326-1 is ±0.2 °C.

Classes of the EMC standard IEC 61326-1
Class A: Equipment for operation only on networks without connected domestic areas;
Class B: Equipment for operation on networks with connected domestic areas.

Caution, Class A equipment must not be operated on power networks with connected domestic areas!

Important symbols
For your safety, pay attention to these important symbols as follows, during moving, installing operating and maintenance. The equipment is designed for safe operation because of your attention!

Warning, possibility of electric shock!
Inappropriate operation may cause hazard of electric shock and result in serious personal injury or death!

Caution , hot surface or area! Accidental touching or approaching may cause burn hazard!

Caution , important note, and always refer to Operating Instructions (this document) for detailed information! The equipment must be operated by well-trained qualified personnel only! Wrong operation may cause personal injury, damage and/or mal-function of the equipment!

Symbols on the equlpment
****Observe operating instructions!

Warranty
Requirements for warranty
Xtemp Environments warrants the operational safety and functions of the equipment only under the conditions that:

  • the equipment is operated and serviced exclusively in accordance with its intended purpose and as described in these Operating Instructions;
  • the equipment is not modified;
  • only original spare parts and accessories that have been approved by Xtemp Environments are used;
  • inspections and maintenance are performed at the specified intervals.

The warranty is valid from the date of delivery to the operator

Chapter 1 Safety Warning and Instructions

Normal operating environment
The equipment is designed for safe operation under ambient conditions as follows:

  • indoor use;
  • altitude up to 2,000 m;
  • temperature 5 °C to 40 °C;
  • maximum relative humidity 80 % for temperatures up to 31 °C decreasing linearly to 50 % relative humidity at 40 °C;
  • mains supply voltage fluctuations up to ±10 % of the nominal voltage;
  • transient overvoltage up to the levels of overvoltage category II;
  • temporary overvoltages occurring on the mains supply;
  • Pollution degree 2 or less of the intended environment;
  • Wet location

****Excessive high or low temperature and/or humidity will significantly degrade electric safety of the equipment!
Note the effect of the altitude on the boiling point of the heat transfer liquids!

Safety warning

**** When heating and conditioning with specimen or application system which is intrinsically explosive, flammable or toxic or, which liberates hazardous substances as result of reacting, dissolving or mixing under operating temperature range for normal use, safety acts and regulations for the particular chemicals and experimental laboratory shall be observed!Not applicable for specimen or application system which develops tremendous energy as result of reacting, dissolving or mixing under operating temperature range for normal use!

**** The dielectric strength of the equipment may be degraded if after transport or storage in humid conditions. The equipment shall be powered as for normal use and conditioned at its maximum operating temperature or 105°C, whichever is smaller, for at least 1h before commissioned for normal use. Warning, hazard of electric shock during the dry-out!

Caution

Caution, Risk of burn hazard! Do not touch or approach parts or area with high temperature, for example, bath cover and the heat transfer liquid when maintained at operating temperature over 60°C!

Pull the temperature of the heat transfer liquid as close as possible to the ambient before attempting to shut down the equipment, except when operations as such are prohibited for the specimen! Warning, Hazards of burn and possible electric shock resultant from unattended hot temperature or condensing and degraded dielectric strength!
The minimum distance away from the ventilating holes at the back of the equipment to the wall, furniture or other installations shall be 300mm! The inlets of fresh air and outlets of exhausting air of the equipment shall be kept clear of any obstacles.
Keep the equipment away from hot-air emitting source, direct sunshine, strong magnetic field and electric sparks!Neither contamination of high concentration dust or corrosive gas, nor strong airflow surrounds!
Voltage, frequency and current for power supply must meet the requirements as designated on the nameplate! Use power socket matching the power plug of the equipment. Hot line(L) and neutral line(N)for single phase equipment must not be reversed!For possible wet location conditions, where cycle of evaporating and condensing, overflowing or spillage may occur and for protection against hazard of possible electric shock, use power socket with appropriate IP protection and additional residual current circuit breaker (RCD) with rated breaking capacity!
Grounding Icon  Socket for power supply must be equipped with protective ground (PE) to prevent against hazard of possible electric shock!
Connect the power from behind the equipment. Plug in and remove the cable by directly holding the plug. No dragging of cable in any part. Protect the cable from being damaged by contacting with the hot surface of the equipment or mouse etc!
Caution, Hazard of overflowing or low level! Never attempt to initiate the equipment if no heat transfer liquid is filled or filling volume is lower than the minimum level as specified; Never move the equipment if the bath tank is fully filled with the heat transfer liquid; The liquid level may change with the heating and cooling of the equipment, and with the immersion or removal of the specimen!
 Class I /NFL           Caution, Risk of fire! The Class I/NFL series of the equipment is designed for operation with non-flammable heat transfer liquids only! Water and mixture of water and glycol are the most popular non- flammable heat transfer liquids appropriate for the equipment.No silicone oil is allowed for use with this series of the equipment. The internal silicone rubber parts may swell when in contact with silicone oil resulting in leakage of the liquid!
Class III /FL            Caution, Risk of fire!The Class III/FL series of equipment are designed for operation with non-flammable and flammable heat transfer liquids! Alcohol and silicone oils are the most common flammable heat transfer liquids. Use special care when using with these flammable liquids, including the proper setting of the adjustable overheating protection device.
 The circulation of the heat transfer liquid is important for performance and safety! The kinematic viscosity, immersion and distribution of the specimen and, flow resistance of the application system and the circulating tubing significantly influence the circulation of the liquid!The first time commissioned for use or when exchange of the heat transfer liquid and, immediately after startup of the circulating pump, check if any liquid leakage exists in the external circulating tubing and fitting, if head pressure of the pump and flow of the heat transfer liquid are in their rated range and, if the liquid level is in its range for safe operation!Mixing and use of heat transfer liquids with different physical and/or chemical properties may adversely affect the performance and safety of the equipment! The liquid shall be completely drained and removed before attempting to charge the other. When necessary, consult Xtemp or supplier of the liquid for particular application!Never touch or attempt to handle the heat transfer liquid with temperature higher than +60°C! Caution, burn hazard!No draining of the heat transfer liquid with potential of chemical or biological hazard! Collect and identify the heat transfer liquid for future use! Consult Xtemp or manufacturer of the liquid for proper disposal!
Install an extraction system over the bath opening, if the operating of the equipment could lead to liberation of hazardous air or gas mixture, for example the evaporation of the heat transfer liquid! The rating of the fume hood shall be at least the maximum possible exhausting temperature! If necessary for safety, additional temperature limiting and warning devices, condensate accumulator shall be installed for the extraction system!
Caution: Note the following when connecting the equipment to an external application system: 1.     The external circulating pipe, including flexible tubing and hose, shall be connected only after the equipment and application system are well seated and installed. The length and distribution path shall be as short as possible and be so arranged that no kink and other mechanical stress develops during normal use which otherwise may result in thermal and/or liquid hazards!2.     Flexible hose, fitting and coupling are important for the safe operation of the equipment; Use only hose, fitting and coupling provided with the equipment or recommended by Xtemp!3.     The ratings of pressure and temperature for the hose, fitting and their resistance to the chemicals shall meet the requirements of the operating temperature, pressure range of the heat transfer liquid to be delivered for the jacket, container or heat exchanger of the application system!4.     Thermal insulation for hose, fitting, coupling and the application system are important for performance and safety! The materials of the insulation shall meet the requirements of the maximum operating temperature range!5.     If no external circulating is necessary, use hose, fitting and coupling to short-circuit the liquid connections as for an external application!Keep the cables and wiring protected by conduit and/or hose and well secured; keep them clearly away from direct contact with any exposed heated/cooled parts of the equipment and application system!
 The maximum filling volume or cooling capacity of an open bath or refrigerated bath for movable immersion circulator shall be 25L and 600W. The fixing and connection for the immersion circulator, external circulating adaptor and the bath must be secured and hydraulically tight. Bath cover should be used where necessary to reduce the effect of evaporation of the liquid on the electronics of the circulator.Caution: smaller bath may develop hazard of overflowing, and leakage or slipping-off of the circulating tubes may cause hazard of spillage or spray! Excessive volume or capacity may degrade specifications for temperature control!Before attempting to remove the immersion circulator away from the bath, always unplug the equipment and wait until the temperature recovers close to ambient and note the following:1. Don’t touch the heated surface or any parts with hot residual liquid or, put it on surface of flammable or temperature sensitive materials! Warning, Risk of burn hazard!2.     Don’t touch the frozen surface or any parts with cold residual liquid! Warning, Hazard of frostbite!Caution, Hazard of possible electric shock when removed and placed in horizontal or up-side down conditions and if the heat transfer liquid penetrates to electrical assembly resulting in deterioration of the insulation!
 Caution: Risk of frozen hazard! When water is employed as heat transfer liquid, and when intended for standstill for long period and when experiencing low ambient is possible, run the equipment at operating temperature close to ambient for at least 1hr. Empty the bath containing water, and remove the water completely. Disconnect the equipment and remove the mains plug from power source.
 Do not disassemble or exchange assembly parts and electric circuits by unauthorized personnel! Hazard of possible electric shock! In case of repairing, contact your local distributors or supporting technicians.Always remove the mains plug from the socket before cleaning, moving, maintenance or repairing!
 The first time powering up after repairing or standstill for long period, or at designated intervals under normal use, check the functionality of the following parts or components:Hydraulic tightness and fastening of drain device at three months intervals; Cutoff capability of the safety temperature limiter (STB) at 6 months intervals.

Chapter 2 Installing and Operating

Installing
Unpacking
Unpack the equipment and sort the accessories respectively and carefully. The packing carton, pallet, packing buffering stuffs etc., are designed for one shipment only. For future shipment, prepare the packing materials as well as the way of packing as received. Check the equipment and accessories for potential transport damages. If there is any damage visible on the equipment, a claim must be filled in writing with the freight forwarder; a notification to the freight forwarder is obligatory so that the shipment can be examined. Inform your local distributor or supplier for any missing accessories and servicing or repairing.

Accessories lists (UXP8011-HC090)

Part Number Qty Descriptions Remarks
DSGO0708-2 1 Operating instructions This document
ERSG0202 1 Fuse (250V~, 15A), D5L20 Breaking capacity 1500A
BJGW0002 1 External circulating kit Assembled
SZGJ0104 1 Flow adaptor L silicone Assembled
SZGJ0115 1 Bypassing U tube silicone Assembled
BJGW0143 1 Bath cover assembly

Accessories lists(UXP8011-HC130)

Part Number Qty Descriptions Remarks
DSGO0708-2 1 Operating instructions This document
ERSG0202 1 Fuse (250V~, 15A), D5L20 Breaking capacity 1500A
BJGW0002 1 External circulating kit Assembled
SZGJ0104 1 Flow adaptor L silicone Assembled
SZGJ0115 1 Bypassing U tube silicone Assembled
BJGW0142 1 Bath cover assembly

Accessories lists(UXP8011-HC250)

Part Number Qty Descriptions Remarks
DSGO0708-2 1 Operating instructions This document
ERSG0202 1 Fuse (250V~, 15A), D5L20 Breaking capacity 1500A
BJGW0002 1 External circulating kit Assembled
SZGJ0104 1 Flow adaptor L silicone Assembled
SZGJ0115 1 Bypassing U tube silicone Assembled
BJGW0141 1 Bath cover assembly

Do not disassemble or exchange assembly parts and electric circuits by unauthorized personnel!
Hazard of electric shock! In case of damaged shipment and dent, deformation or distortion of the enclosure, contact your local distributor or supplier.

Installing
Install the equipment on a rigid, nonflammable surface and well-ventilated place. The bench should be 600~800mm high for ease of operation. Keep enough space between wall and back of the equipment, and keep clear of obstacles around the bottom of the equipment for better ventilation. If the equipment is installed on an unstable surface or floor, abnormal noise may be generated.
The voltage, frequency and current of the power supply must be rated at least the same as those designated on the name plate of the equipment. The switch board is recommended to be on the back right side of the equipment and equipped with outlet matching the power plug of the equipment with protective ground (PE).
For possible wet location conditions, where cycle of evaporating and condensing, overflowing or spillage may occur and for protection against hazard of possible electric shock, use power socket with appropriate IP protection and additional residual current circuit breaker (RCD) with rated breaking capacity!
Power socket, switchboard with circuit breaker or residual current circuit breaker for the equipment shall be located closest to the equipment with good clearance for easy access, so that immediate interruption is possible under emergent circumstance.

 The minimum distance away from the ventilating holes at the back of the equipment to the wall, furniture or other installations shall be 300mm! The inlets of fresh air and outlets of exhausting air of the equipment shall be kept clear of any obstacles.

 Keep the equipment away from hot-air emitting source, direct sunshine, strong magnetic field and electric sparks!Neither contamination of high concentration dust or corrosive gas, nor strong airflow surrounds!
 Voltage, frequency and current for power supply must meet the requirements as designated on the nameplate! Use power socket matching the power plug of the equipment. Hot line(L)and neutral line(N)for single phase equipment must not be reversed!
Grounding Icon Socket for power supply must be equipped with protective ground (PE) to prevent against hazard of possible electric shock.

Connecting to an application system where necessary
The external circulating pipe, including flexible tubing and hose, shall be connected only after the equipment and application system are well seated and installed. The length and distribution path shall be as short as possible and be so arranged that no kink and other mechanical stress develops during normal use which otherwise may result in thermal and/or liquid hazards! Flexible hose, fitting and coupling are important for the safe operation of the equipment; Use only hose, fitting and coupling provided with the equipment or recommended by Xtemp! The ratings of pressure and temperature for the hose, fitting and the jacket, container or heat exchanger of the application system, their chemical resistance to the heat transfer liquid shall meet requirements of the operating temperature and/or pressure range of the heat transfer liquid to be delivered by the equipment! Thermal insulation for hose, fitting, coupling and the application system is important for performance and safety! The materials of the insulation shall meet the requirements of the maximum operating temperature range!  Keep the cables and wiring protected by conduit and/or hose and well secured; keep them clearly away from direct contact with any exposed heated parts of the equipment and application system!

Descriptions

Fig 1 Front view
Front View

02 Controller panel and power switch
05 Feet
18 Handle
20 Liquid connection, return
21 Liquid connection, outlet
76 Bath cove

Back view
Back View

03 Fresh-air inlets
04 Exhausting-air outlets
18 Handle
22 Power cable cord
23 Drain device

The inlets of fresh air and outlets of exhausting air of the equipment shall be kept clear of any obstacles, so that no close-loop of the air circulating may develop. If no external circulating is necessary, use hose, fitting and coupling to short-circuit the liquid connections as for an external application system! The equipment is not applicable for specimen or application system which develops tremendous energy as result of reacting, dissolving or mixing under operating temperature range for normal use! However for temperature below ambient until minimum temperature range of the controller, optional cooling coil must be employed with additional external cooling source available.

The immersion controller

42 Temperature sensor Pt100
43 Circulating return
44 Circulating discharge outlet
45 Heating coil
47 STB (independent overheating device)

External circulating kit

101 Liquid connection assembly, XT5618A
102 U-type silicone liquid shortcut
103 L-type silicone adaptor, LL
104 L-type silicone adaptor, SL

The connection to the pump outlet and external circulating kit shall be hydraulically tight! Loose connection may result in hazard of liquid spray!
The pump inlet shall be clear of any obstacles! The minimum distance for the pump inlet to the bath bottom shall be 20 mm. Sometimes a piece of paper mark from the specimen, gauze or collection of dirt may block the flow of the pump and circulation, resulting in degradation of performance and overheating!
The flow rate and direction at the external circulating return may also influence the performance and safety of the equipment! Reduced flow may produce an uneven circulating of the liquid and temperature distribution, while strong circulating may lead to overflow or splash of the adaptor or limiter may be used for proper adjustment of the flow rate and direction.
Regular check of the STB and, level switch if equipped, is requirement for safety. Refer to 4.2 for detailed procedures.

The first time powering up after repairing or standstill for long period, or at 6 months intervals under normal use, check the functionality of the following parts or components: Cutout capability of the safety temperature limiter (STB)! Low level cut-out if equipped!

Accessory cooling coil (Optional)

**Fig 5 Cooling coil

**

For immersion heating bath (GP series) and circulators completed with open bath tank, the minimum operating temperature of the equipment is limited to 5-10 °C above ambient temperature, dependent on the pump pressure and flow rate, as well as the immersed specimen or connected application system. For operating temperature close to or below ambient, cooling coil is recommended to extend the temperature range and optional accessory.

Put into operation
Use non-flammable heat transfer liquid only!
Fill the bath tank with applicable heat transfer liquid to a level appropriate for operation. Keep in mind that the level may change with the heating and cooling of the equipment, and immersion and removal of the specimen.
If an application system is connected, additional liquid may be necessary for appropriate level once initiated.

Class I/NFL Caution, Risk of fire!

The Class I/NFL series of the equipment is designed for operation with non- flammable heat transfer liquids only! Water and mixture of water and glycol are the most popular non-flammable heat transfer liquids appropriate for the equipment.No silicone oil is allowed for use with this series of the equipment. The internal silicone rubber parts may swell when in contact with silicone oil resulting in leakage of the liquid!


Class III /FL Caution, Risk of fire!The Class III/FL series of equipment are designed for operation with non-flammable and flammable heat transfer liquids! Alcohol and silicone oils are the most common flammable heat transfer liquids. Use special care when using with these flammable liquids, including the proper setting of the adjustable overheating protection device.
 Caution, Hazard of overflowing or low level!
Never attempt to initiate the equipment if no heat transfer liquid is filled or filling volume is lower than the minimum level as specified; Never move the equipment if the bath tank is fully filled with the heat transfer liquid; The liquid level may change with the heating and cooling of the equipment!Disconnect the application system from the equipment only after proper draining of the heat transfer liquid, especially when the application system is charged to maximum volume by additional filling of the liquid! The liquid level will change significantly with the immersion or removal of the specimen!

Chapter 3 Controller Descriptions and Operation

Controller panel

60 Reset button (for resetting when alarming, the
circle indicating the location)
61 Display for temp and working parameters
62 Status indicators
63 Key board
64 Power switch

Display for temperature and working parameters
Normally it displays the equipment temperature once switched on and initiated or oFF when standstill.

Other possible symbols include: SEt, Ht, Lt, CooL, Auto, Atc AS, ASd, cF, dEFt, ESc, Stb. Related definitions are as follows:

SEt: Setting of working temperature, must be 5 °C higher than low limit Lt and 5 °C lower than the high limit Ht. The temperature setting beyond the scope will not be accepted.

Ht: This parameter is an absolute value and used for reminding only. When temperature in the equipment is higher than the SEt value, Ht is displayed. The controller will trigger a beeping alarm and disable the heating. While the actual temperature is higher than the Ht setting, the Ht may be set to a higher value by pressing so that Ht beeping can be cleared. If the actual temperature is recovered to lower than the Ht setting, the Ht alarm will disappear automatically with seconds of delay, or may be cleared immediately by pressing . The heating is possible only if the Ht is cleared.

Lt: This parameter is an absolute value and used for reminding only. When temperature in the equipment is lower than the SEt value, Lt is displayed. The controller will trigger a beeping alarm. While the actual temperature is lower than the Lt setting, the Lt may be set to a lower value by pressing so that Lt beeping can be cleared. If the actual temperature is recovered to higher than the Lt setting, the riptions and Operation Lt alarm will disappear automatically with seconds of delay, or may be cleared immediately by pressing .

CooL : Control parameter for compressor, and select among three modes, Auto, on and oFF:

on :Compressor cooling with counter heating by PID, provided that the actual temperature is below 40 °C.

Auto :Compressor on and off automatically. During heating up, once full heating is necessary, the compressor will be turned off, until the actual temperature close to set temperature. if the set temperature over 40 °C, and no cooling is required, the compressor will also be turned off. If the set temperature is lower than the actual temperature, and when the actual temperature below 40 °C, the compressor will be switched on and keep working continuously.

oFF: The compressor is disabled, and the heater is regulated by PID.

Auto: Select between AoFF and Aon, which means manually starting and automatically starting.

Atc: Absolute temperature calibration (ATC), when the temperature displayed differs from the temperature measured by a standard thermometer, ATC is used to calibrate the display.

AS: Timer for automatic startup. Valid only when the equipment is in standby mode. The equipment will be initiated automatically once the set time elapses. The equipment may be started immediately if is operated regardless of the remaining AS time.

ASd: Timer for automatic shutdown. Valid only when equipment is in operating mode. The equipment will be terminated automatically once the set time elapses. The equipment may be terminated immediately if is operated regardless of the remaining ASd time.

cF: Shifting of the temperature measurement units. c means Centigrade and F means Fahrenheit. cF setting affects all the parameters related to temperature, such as the display temperature, setting temperature, Ht, Lt and so on. Relationship between c and F is as follows

°F=32+1.8×°C, °C=(°F-32)/1.8

For example : 0 °C=32 °F, 212 °F=100 °C.

dEFt :Return to the factory default setting. It may be used when system halts or any other abnormal situation occurs.

ESc: Exit the SEt menu.

Working status indicating

Heater: Press for more than 2 seconds to initiate the circulating pump. Orange LED will be steadily lit with full power heating; When LED flashes, the heating power is automatically adjusted to meet actual need. LED flashing frequency keeps constant when temperature is stabilized.

Compressor: Not applicable for this series of equipment.

Circulating pump: Press for more than 2 seconds to initiate the circulating pump with LED on, after which the heating operation is possible.

Alarm: Red LED is on, when there is beeping and warning for safety or error is triggered.

The warning or error of the sensor may be accompanied by the following:

Ht :When temperature in the bath is higher than the set value, Ht is displayed

Lt :When temperature in the bath is lower than the set value, Lt is displayed

Er01: Warning of temperature sensor short-circuit.

Er02: Warning of temperature sensor open-circuit.

ourh: Warning of the bath temperature far beyond Ht.

Stb: The independent safety temperature limiter (STB) is triggered; Press (Fig 6-60) and to reset.

The key functions and navigate the menu
There’re 6 keys as follows. The function and their operation are summarized and listed in the table:

KEY NO FUNCTION OPERATION REMARKS

|

1

| Initiate or terminate the temperature control| Press and hold the key for more than 2 seconds| Temperature regulating is possible only if the circulating pump is activated and temperature control is initiated.
|

2

| Set the working temperature| Press the button for less than 1 second| SEt is first displayed, then press             to enter,change the digits by pressing , accept the setting by pressing       .

|

3

| Display the parameters of temperature programming| Press the button for less than 1 second| When the programming is in progress, it displays the segment number, temperature, remaining time and cycles of active program. The parameters are cycled and displayed for 2 times with each delay of about 2 seconds, and then exit automatically.
|

4

| Set the working parameters| Press and hold the key for more than 2 seconds| Ht is first displayed, press  for Lt, cooL, Auto, Atc, AS, ASd, cF, dEFt, ESc Press   to enter for change of a definitesetting of the working parameter, for exampleHt. Change the digits or setting by pressing, accept the setting by pressing, or confirm and exit automatically in 4 seconds.
+|

5

| Set the programming parameters| Press    andat the same time then release the buttons| 1)        The function is optional. The parameter of first segment t1 is displayed. Press                                 to display original time, press                 for anew value, confirm the setting by pressing to display temperature of the first segment M1; Press      to display the originaltemperature, press     for a newvalue, confirm the setting by pressing  to enter the setting of second segment.2)        Following the steps as for the first segment for segments 2, 3 … to 6 maximum. If segments of less than 6 are desired, for example only 2 segments are necessary, use 00:00 for t3 after confirmation of M2.3)        Press   to display n, which means the number of program circles.1~99 means 1cycle to 99 circles maximum and 0 meansunlimited circles. Press   to confirm and exist.4)        Default parameters: t= 00:00, M=25, n=99
|

6

| Initiate or terminate programming| Press  and at the same time and release the buttons| The temperature program may be initiated either in standby mode or running mode. If Auto setting is Aon, the equipment will automatically resume to the mode before the program is initiated once the program is terminated automatically. The setting of Auto=Aon is recommended, if continuous operation is desired after unexpected interruption of short power failure.
+|

7

| Initiate or terminate the timer| Pressand atthe same time, then release the buttons| The timer function is optional. When the equipment is in running mode, timer for ASd is valid, while the equipment is in standby mode, timer for AS is valid. The time is set by AS and ASd.
|

8

| Move between settings or increase the value| Press the key shortly for slow movement and continuously for fast changing|
Down Button|

9

| Move between settings or decrease the value| Press the key shortly for slow movement and continuously for fast changing|

Set the working parameters

  1. Set the working temperature
    Refer to item No.2 in the table.

  2. Set high temperature limit value
    Press for more than 2 seconds until Ht is displayed. Press to enter Ht setting. Original Ht value is displayed, and press to get the desired value. Press to confirm and exit the SEt screen or exit automatically in 4 seconds.

  3. Set low temperature limit value
    Press for more than 2 seconds until Ht is displayed. Scroll the menu by until screen displays Lt. Press to enter Lt setting. Original Lt value is displayed, press to get the desired value. Press to confirm and exit the SEt screen or exit automatically in 4 seconds.

Constant temperature control

  1. Connect the power by inserting the power plug, or engage the circuit breaker on the switch board. Turn on power switch and the controller runs self-check to display: 88888, LED on, software version number, AoFF (Aon will show up if Auto is set to Aon) settings for Ht, Lt. Refer to 3.5 for procedures about Aon and AoFF setting. The software version number may change with technique updates.
  2. Check and/or set the working temperature, refer to item No.2 in the table.
  3. If the equipment is in the standby state, press for more than 2 seconds, the circulating pump will start to operate and the heater is on if the setting is higher than the actual temperature.
  4. When the temperature in the bath is lower than the set value, heating LED is on and the equipment is in operation and start to heat. When the set temperature and actual temperature are quite different, heating LED will be steadily lit with full power heating and the temperature will go up with full speed. As the temperature approaches the set point, the LED flashes as desired and the controller decreases the power for the heater. With the actual temperature equals to the set temperature, the controller keeps the temperature by constant power output.
  5. To terminate the temperature control, press for more than 2 seconds. The circulating pump and heater are stopped. The LEDs go off, and the display shows oFF.

Connect the power from behind the equipment. Plug in and remove the cable by directly holding the plug. No dragging of cable in any part. Protect the cable from being damaged by contacting with hot surface of the equipment or mouse etc!

Caution, Hazard of overflowing or low level!
Never attempt to initiate the equipment if no heat transfer liquid is filled or filling volume is lower than the minimum level as specified; Never move the equipment if the bath tank is fully filled with the heat transfer liquid; The liquid level may change with the heating and cooling of the equipment, and with the immersion or removal of the specimen!
Class I /NFL       Caution, Risk of fire!
The Class I/NFL series of the equipment is designed for operation with non- flammable heat transfer liquids only! Water and mixture of water and glycol are the most popular non- flammable heat transfer liquids appropriate for the equipment.No silicone oil is allowed for use with this series of the equipment. The internal silicone rubber parts may swell when in contact with silicone oil resulting in leakage of the liquid!
Class III /FL       Caution, Risk of fire!The Class III/FL series of equipment are designed for operation with non-flammable and flammable heat transfer liquids! Alcohol and silicone oils are the most common flammable heat transfer liquids. Use special care when using with these flammable liquids, including the proper setting of the adjustable overheating protection device.
The circulation of the heat transfer liquid is important for performance and safety! The kinematic viscosity, immersion and distribution of the specimen and, flow resistance of the application system and the circulating tubing significantly influence the circulation of the liquid!The first time commissioned for use or when exchange of the heat transfer liquid and, immediately after startup of the circulating pump, check if any liquid leakage exists in the external circulating tubing and fitting, if head pressure of the pump and flow of the heat transfer liquid are in their rated range and, if the liquid level is in its range for safe operation!Mixing and use of heat transfer liquids with different physical and/or chemical properties may adversely affect the performance and safety of the equipment! The liquid shall be completely drained and removed before attempting to charge the other. When necessary, consult Xtemp or supplier of the liquid for particular application!Never touch or attempt to handle the heat transfer liquid with temperature higher than +60°C! Caution, burn hazard!No draining of the heat transfer liquid with potential of chemical or biological hazard! Collect and identify the heat transfer liquid for future use! Consult Xtemp or manufacturer of the liquid for proper disposal!
Install an extraction system over the bath opening, if the operating of the equipment could lead to liberation of hazardous air or gas mixture, for example the evaporation of the heat transfer liquid! The rating of the fume hood shall be at least the maximum possible exhausting temperature! If necessary for safety, additional temperature limiting and warning devices, condensate accumulator shall be installed for the extraction system!

Absolute temperature calibration (ATC)

  1. If the temperature display is deviated away from the actual temperature as measured by standard thermometer, the display temperature needs to be calibrated by this function.
  2. Set the bath at temperature of 40.0°C for calibration. Wait until temperature is stabilized. Read the temperature of the standard thermometer.
  3. Press for more than 2 seconds until screen displays Ht. Scroll the menu by until screen displays Atc. Press to enter. Original value will show up, then press to modify the value as available from the standard thermometer. Press to confirm and exit the SEt screen or exit automatically in 4 seconds.

The temperature in the bath must be kept in constant and the standard thermometer be kept in the bath center for at least 30 minutes, before performing calibration. During heating up or cooling down, the temperature distribution is not even and the readings both from thermometer and the controller are not typical thus not appropriate for calibration.

Setting for restart mode after power failure, Auto
Press for more than 2 seconds until screen displays Ht. Scroll the menu by until Auto is displayed, then press to enter. Use to select between Aon and AoFF. For automatic power-on function, use Aon, and press to confirm and exit the setting. In this case, the equipment will automatically resume to the status before power being interrupted. If the mode is set to AoFF, press for more than 2 seconds to start the equipment where necessary.

Auto mode setting is designed to protect the equipment from power failure and make it efficient, uninterrupted operation. You are recommended to set Aon mode if operating for more than 24 hours is desired.

Timer for automatic starting (optional)

  1. The function of timer is optional.
  2. Press for more than 2 seconds to display Ht, scroll the menu by until AS is displayed, then press to enter. Press to get the desired value, press to confirm and exit the SEt screen or exit automatically in 4 seconds.
  3. When the equipment is in standstill mode, press + at the same time and then release to initiate timing. The timer starts to count down. When the time of AS elapses, the circulation fans will start automatically to initiate constant temperature control. Heating and constant temperature control executed automatically according to the difference between SEt value and actual temperature.
  4. The equipment may be initiated immediately when is operated regardless of the remaining AS time.

Timer for automatic terminating (optional)

  1. The function of timer is optional.
  2. Press for more than 2 seconds to display Ht, scroll the menu by until ASd is displayed, then press to enter. Press to get the desired value, press to confirm and exit the SEt screen or exit automatically in 4 seconds.
  3. When the equipment is in running mode, press + at the same time and then release to initiate timing. The timer starts to count down. When the time of ASd elapses, the circulation pump and heating will stop automatically to terminate constant temperature control.
  4. The equipment may be terminated immediately when is operated regardless of the remaining ASd time.

Temperature Programming (optional)

  1. The function of temperature programming is optional.
  2. Press and at the same time and then release. The parameter of first segment t1 is displayed. Press to display original time, press for a new value, confirm the setting by pressing to display temperature of the first segment M1; Press to display the original temperature, press for a new value, confirm the setting by pressing to enter the setting of second segment.
  3. Following the steps as for the first segment for segments 2, 3 … to 6 maximum. If segments of less than 6 are desired, for example only 2 segments are necessary, use 00:00 for t3 after confirmation of M2.
  4. Press to display n, which means the number of program circles.1~99 means 1 cycle to 99 circles maximum and 0 means unlimited circles. Press to confirm and exist.
  5. Press and at the same time to initiate or terminate programming. The program may be terminated immediately when is operated regardless of the remaining program segments.
  6. When the programming is in progress, press shortly to display the segment number, temperature, remaining time and cycles of active program. The parameters are cycled and displayed for 2 times with each delay of about 2 seconds, and then exit automatically.

Set default parameters

  1. It may be used to recover data and functional parameters when system halts or any other abnormal situation occurs.
  2. Press for more than 2 seconds until screen display Ht. Scroll the menu by until dEFt is displayed, then press for less than 1 second ,the dEFt flashes. Press again for more than 2 seconds and release, once donE is displayed, it exits automatically.

Accidental power failure or interference, the abnormal situation will happen such as the equipment may not be able to achieve normal temperature controlling, alarm may not be cleared or abnormal temperature displays etc. Try dEFt command first to recover default settings.

Terminate operating

  1. Press for more than 2 seconds. The circulating pump and the heater stop simultaneously, and the screen displays oFF.
  2. Disconnect the power by turning off the power switch, removing the power plug, or disengaging the residual current circuit breaker (RCD).

Pull the temperature of the heat transfer liquid as close as possible to the ambient before attempting to shut down the equipment, except when operations as such are prohibited for the specimen!
Warning, Hazards of burn and possible electric shock resultant from unattended hot temperature or condensing and degraded dielectric strength!

Caution: Risk of freezing hazard!
When water is employed as heat transfer liquid, and when intended for standstill for long period and when experiencing low ambient is possible, run the equipment at operating temperature close to ambient for at least 1hr. Drain the bath containing water, and remove the water completely. Disconnect the equipment and remove the mains plug from power source.

No draining of the heat transfer liquid with potential of chemical or biological hazard! Collect and identify the heat transfer liquid for future use! Consult manufacturer or supplier of the liquid for proper disposal!

Unit of temperature

  1. The default unit for temperature measurements and setting is degree centigrade.
  2. The unit of temperature may be changed to Fahrenheit or Centigrade as desired. Refer to Table and item No. 4, use cF and similar steps for procedures.

Chapter 4 Maintenance

Regular maintenance

  1. Clean the bath interior and exterior of the equipment periodically to keep the equipment clean;
  2. Check for hydraulic tightness and fastening of the connections for flexible hose, fitting and coupling;
  3. If the immersion heating circulator is removable for convenience of operation, check the fixing device and bridge to make sure the equipment is secured in place and safe;
  4. Check fixing screws periodically, and if any loose, fix it.

Remove the plug from power line before cleaning. Use soft dry tissue to clean the bath interior and avoid any splashing or washing!
If any water or other conductive material fall into the equipment containing electric and/or electronic parts and components, disconnect the power immediately. Power on only after water or foreign material is completely evaporated or removed.

Regular check of the STB
Regular check of the STB is required for safe operation. Intervals of six months for normal use, or the first time powering up after repairing or standstill for long period, are recommended for regular check of the functionality. Check the STB as follows:

  1. Fill the tank with water to level just over the highest point of the heating coil;
  2. Set the temperature at 10°C above the ambient and/or the liquid, so that it keeps heating, LED is continuously on;
  3. Initiate the temperature control as for normal use, i.e. the pump is circulating and heating is in full capacity;
  4. Drain the bath so that the heater and the STB are exposed to the air completely. Make sure no liquid spraying out from the circulating return, dripping from the drain device on the bench or floor;
  5. The liquid evaporates immediately from hot surface of the heater. Keep running dry for a couple of seconds until the Stb warning is displayed. Caution, Never run dry for more than 90 s!

Caution, Risk of burn hazard and liquid spillage!

Do not touch hot surface of the heater! Keep away from evaporating hot steam! Use protective gloves or glasses if necessary!

Never run dry for more than 90 s! Overheating of the coil may damage the heater or degrade its insulation strength!

Checking and replacing the fuse
With the mains plug connected and power switch in “on” position and if no LED and digits display, check the fuse first. If any doubt that checking and replacing fuse is necessary, use a fuse with the same size and capacity as rated and do as follows:

  1. Make sure the mains plug has been removed;
  2. Loosen the two screws on the top and 4 screws at the back of the controller as shown in Fig 7. Remove the cove plate and check or replace the fuse;
  3. Replace the cover and fasten the six screws.

Do not disassemble or exchange assembly parts and electric circuits! Hazard of possible electric shock!

Except for replacing the fuse, there is no other part necessary for customer to disassemble or repair. If repairing is desired, contact with authorized engineer.

Always remove the mains plug from the power socket when performing checking or replacing the fuse, and never use any fuse different from the original one. Secure the fuse once checked or replaced. For servicing or maintenance, call authorized service engineer.

Location of the fuse and Pt100 sensor
Fuse Location And Sensor

81 Mains fuse (15A)
82 Terminal for Pt100

Clear error, warning and alarm
When the equipment displays Er01 or Er02, check the connections of the Pt100 where
necessary.

Er01 and Er02 are indications for short-circuit and open-circuit of the temperature sensor PT100.

For inspection, remove the screws for the controller cover as for checking and replacing of the fuse (Fig 7). Check the wire connecting terminals of the PCBA for the temperature sensor (82), and make sure no short-circuit or open- circuit occurs. If necessary, a multimeter may be used for the resistance of the Pt100. The value of the sensor is 100Ω@0°C and +0.385Ω/°C. At 26°C ambient, the resistance of the sensor is about 110Ω.

In most cases, loose wiring and terminating rather than open-circuit of the Pt100 sensor could trigger an error and alarm. Once fixed, those alarms will disappear when switching on the power again. If alarm still exists with Pt100 checked or replaced, and for servicing or maintenance, call authorized service engineer.

When the equipment displays Stb, try first to pull down the temperature of the heater or the heat transfer liquid and find the cause of the over temperature. The STB resets automatically once temperature resumes to below designated limit value. Press (Fig6-60) and . Reboot the controller by powering off and on again, the normal operation of the temperature control will resume. If warning still exists with STB checked or reset, and for servicing or maintenance, call authorized service engineer.

When the equipment displays alarm ourh, cut off power and deal with the equipment after bath temperature goes down close to ambient, then turn on power again. If alarm still exists with Pt100 checked or replaced, and for servicing or maintenance, call authorized service engineer.

When the equipment displays SPuP, the equipment can’t work normally, cut off power, find the cause of the over temperature. Reboot the controller again, if the equipment displays SPuP again, press (Fig 6-60) and ,the normal operation of the temperature control will resume. If warning still exists, and for servicing or maintenance, call authorized service engineer.

Chapter 5 Equipment Overview and Specifications

Equipment overview

  • SMT assembled and microprocessor-based precise dynamic temperature control with temperature stability up to ±0.05 °C;
  • Independent immersion controller head, DIY for precise temperature system with different bath capacity and style;
  • Immersion bath and external circulator in one unit, helps you to save money and make more space;
  • Absolute temperature calibration (ATC) for accurate temperature control and AUTOrestart after power failure for continuous uninterrupted operation.

Specifications

Models UXP8011-HC090 UXP8011-HC130 UXP8011-HC250
Temperature range °C (°F) RT+10~+100 (RT+18~+212)
Temperature stability ±°C (°F) 0.02~0.05 (0.04~0.09)
Pump flow rate max L/min (gpm) 20 (5.3)
Pump pressure max mbar (psi) 350 (5.1)
Temperature programming 6 segments×99h59min, 99 cycles
Classification for HTL to DIN 12876 Class 1/NFL, non-flammable Heat Transfer

Liquid, No silicone oil
Safety| Protection and warning against short/open-circuit PT100 High- temperature cut off and low temperature alarm, Protection against stalled pump motor & dry heating
Utility function| ATC (Absolute Temperature Calibration), Auto start-up or standby after power failure
Duty cycle| Continuous
Wetted materials| Stainless steel deep drawn Gastro norm pan Heater and pump of SUS316L
Enclosure material| SPCC mild steel with powder coating
EMC for USA and Canada| Class A, for operation only on networks without connected domestic areas
Heater wattage| W| 1,000
Capacity| L (G)| 6.5~9 (1.72~2.38)| 9~13 (2.38~3.43)| 18~25 (4.76~6.60)
Bath size (WDH)| mm (in)| 150×280×200(Gastro N Pan 1/3 – 8)| 240×280×200(Gastro N Pan 1/2 – 8)| 280×480×200(Gastro N Pan 1/1 – 8)
Immersion depth (H)| mm (in)| 200 (8)
Bath opening (WD)| mm (in)| 145×130(5.7×5.2)| 233×150(9.2×5.9)| 295×350(11.6×13.8)
Overall size (WDH)| mm (in)| 186×337×430(7.3×13.3×16.9)| 275×337×430(10.8×13.3×16.9)| 335×538×430(13.2×21.2×16.9)
Packing size (WDH)| mm (in)| 265×455×520(10.4×17.9×20.5)| |
Net weight| Kg (lbs)| 9 (19.8)| |
Gross weight| Kg (lbs)| 11 (24.3)| |
Voltage and frequency| 115V~, 60Hz
Current draw| A| 12

Specifications are subject to change without notice!

XTEMP ENVIRONMENTS (SHANGHAI) CO., LTD.
http://www.xtemp-usa.com
DSGO0708-2-V211119/UXP8011-CD6400/CLASS I/NFL/RT+5~+100°C

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals