Danfoss Type KP 21 Pressure Switch Installation Guide

June 12, 2024
Danfoss

Installation guide
Pressure switch
Type KP 21

Ambient temperatures

Danfoss Type KP 21 Pressure Switch - Figure 1

Caution: Do not mount a switch in a position where dirt, sediment or oil will affect the operation of the switch.

Test pressure (p test)

Danfoss Type KP 21 Pressure Switch - Figure 2

Enclosure

Danfoss Type KP 21 Pressure Switch - Figure 3

CAUTION: The mounting panel must be plane to avoid damage of switch.

Low pressure (LP) side settingDanfoss Type KP 21 Pressure Switch -
Figure 4

CUT-IN minus DIFFERENTIAL equals CUT-OUT

High pressure (HP) side settingDanfoss Type KP 21 Pressure Switch -
Figure 5

CUT-OUT minus DIFFERENTIAL equals CUT-IN

Danfoss Type KP 21 Pressure Switch - Figure 6

CAUTION:
Disconnect power supply before wiring connections are made or service to avoid possible electrical shock or damage to equipment.
Do never touch live parts with your fingers or with any tool.

Contact load
Alternating current:
AC 1: 16 A, 400 V
AC 3: 16 A, 400 V
AC15: 10 A, 400 V
Max. starting current (L.R.): 112 A, 400 V
Direct current:
DC13: 12 W, 220 V control current

Function

Note!

| Load
---|---
Signal option
Bellows movement on pressure rise
Bellows movement on pressure drop

Controls with low pressure (LP) and high pressure (HP) signal
Terminal blockDanfoss Type KP 21 Pressure Switch - Figure
8

CAUTION: Use terminal screws furnished in the contact block.
Use tightening torque (20 lb.) in 2.3 Nm.
Use copper wire only.
Low pressure (LP) side:
A-C close on LP rise
A-C open on LP drop
High pressure (HP) side.
A-C open on HP rise
A-C close on HP drop
LP signal option:
A-B close on LP drop
HP signal option
A-D close on HP rise

© Danfoss | Climate Solutions | 2021.07