SAGlnoMIYA FQS-U30G Flow Switch Instructions
- June 12, 2024
- SAGlnoMIYA
Table of Contents
Read all instructions thoroughly
INSTRUCT IONS
FLOW SWITCH Type F Q S
A. Failure to read and follow all instructions carefully before installing or operating this water regulating valve could cause personal injury and/or property damage. Save these instructions for future use.
NOTE FOR SAFETY
Warning
- Never remove the cover when power is applied. This can result in electric shock.
- Connect wiring after turning off power. This can result in electric shock.
- Do not sprinkle water over the microswitch. This can result in electric shock.
- Do not connect a load exceeding the electric rating. This can result in bad contacts.
- Do not turn screws other than the operating value setting screw. Incorrect operations or water leakage can occur.
- Install the switch so that the arrow indication and the fluid flow match. The switch does not work if fluid flows in the opposite direction. In addition, paddles can be damaged.
- Use fluid that does not corrode the liquid contacting material. In addition, use fluid in liquid form. Gas or liquid mixed with gas causes unstable operations.
- Connect the switch to ground. Do not connect the grounding wire to a gas pipe, water pipe, lightning rod or the grounding wire of a telephone line. If the grounding is not appropriate, this can result in electric shock.
- Use fluid with flow velocity of 2m/s or less. In addition, avoid strong pulsating fluid and vibration. Paddle can be damaged.
SPECIFICATIONS
S)ccification table
Model| Structure| Liquid contacting materials| Ambient
humidity
---|---|---|---
FQS-0| | Copper alloys| 80%RH or less
FQS-U| Non-water proof
FQS-W| | |
FQS-M| Drip proof| Bronze, stainless steel| 95MH or less
FQS-T| Stainless steel(0-ring NBR)|
- Maximum operating pressure : 0.98
- Allowable fluid temperature :MPa 5 to 80 00 (FQS-030GQ9: 5 to 100°C)
- Endurance operations : 100,000 operations
- Mounting screw : R1(MPT) or NPT(option)
- Ambient temperature : -25 to +80 ‘t (FQS-030GQ9: -25 to 50°C)
- Contact structure :Single-pole double-throw
Electrical ratings
Unit:A
Type name, symbol| Voltage| Resistive load| Lamp load|
Motor load
---|---|---|---|---
Standard (G)| 125V AC| 15| 2.| 5
250V AC| 15| 1.| 3
30V DC| 6| 2.|
125V DC’| 0.5| 0.5| 0.05
high load type (D)| 125V DC| 10| 2.| 5
250V DC| 3| 2.| 2
Typo name, symbol| Voltage| Dull load amp.| Locked rotor amp.| Non-inductive
amp.| Note
---|---|---|---|---|---
l’QS-U (G)| 125V AC| 4.| 21| 15| UL
listed
250V AC| 3.| 15| 15
Type name, symbol| Voltage| Minimum applicable load| Maximum current load
---|---|---|---
Small load type (K)| 24V DC| 0.01| 0.1
100V AC| 0.01| 0.1
INSTALLATION METHOD
- Provide a straight pipe section of more than 5 times the piping diameter in front and back of the flow switch. This is used to prevent hunting due to turbulent flow.
- Basically install the switch in horizontal piping with the cover facing upward but it can be installed in vertical piping. However, in the case of a vertical pipe installation, the operating value may change about 20% compared to the horizontal pipe installation.
- For piping of the flow switch, use a commercially available Tee joint (conforming to JIS B 2301). If the available Tee joint cannot be installed, you can use a welded half coupling.
- When installing the flow switch to piping, the depth of the flow switch screwed in shall be 12±1.2mm.
- For wiring, follow the instructions written on the insulation plate of the microswitch.
OPERATING VALUE SETTING
- When the operating value is not specified, the flow switch is shipped with the operating value set around the minimum flow rate. *When you turn the flow adjusting screw 0 clockwise, the operating point goes up. When you turn it counterclockwise, the operating point goes down. But if you turn the screw counterclockwise too much, the operation becomes unstable and if you turn it further, the setting screw breaks off. elf you have changed the setting value, make sure to operate the paddles and check the operation of the microswitch.
- Never remove the metal fitting CD because this is used to prevent the flow adjusting screw CD from loosening.
- The adjusting screw e is exclusively used by our service personnel. Do not use this screw for adjustment.
- When setting the operating value, refer to either decreasing flow setting value or increasing flow setting value.