TRIO Expansion Unit TRIO Expansion
Controller Relays
Ag/MIS/UmGb-2835-01/22 Rev 1.0
P/N: 117789

TRIO Expansion Unit

User and Installation Manual
Rev 1.0, 02/2022
Product Software: N/A
This manual for use and maintenance is an integral part of the apparatus together with the attached technical documentation.
This document is destined for the user of the apparatus: it may not be reproduced in whole or in part, committed to computer memory as a file or delivered to third parties without the prior authorization of the assembler of the system.
Munters reserves the right to effect modifications to the apparatus in accordance with technical and legal developments.

Introduction

1.1 Disclaimer
Munters reserves the right to make alterations to specifications, quantities, dimensions etc. for production or other reasons, subsequent to publication. The information contained herein has been prepared by qualified experts within Munters. While we believe the information is accurate and complete, we make no warranty or representation for any particular purposes. The information is offered in good faith and with the understanding that any use of the units or accessories in breach of the directions and warnings in this document is at the sole discretion and risk of the user.
1.2 Introduction
Congratulations on your excellent choice of purchasing a TRIO Expansion! In order to realize the full benefit from this product it is important that it is installed, commissioned and operated correctly. Before installation or using the  controller, this manual should be studied carefully. It is also recommended that it is kept safely for future reference. The manual is intended as a reference for installation, commissioning and day-to-day operation of the Munters  Controllers.
1.3 Notes
Date of release: May 2021
Munters cannot guarantee to inform users about the changes or to distribute new manuals to them.
All rights reserved. No part of this manual may be reproduced in any manner whatsoever without the expressed written permission of Munters. The contents of this manual are subject to change without notice.

Unit Installation

The following sections detail how to mount and wire the TRIO Expansion Unit.
NOTE Munters recommends that a trained technician perform the following operations.

  • Preliminary Information
  • Mounting the Unit
  • Layout
  • Wiring Diagrams
  • Key
  • Product Symbols

2.1 Preliminary Information

  • Precautions
  • Safety Precautions
  • What Comes in the Package

2.1.1 PRECAUTIONS

  • Protection provided by the equipment can be impaired if the equipment is used in a manner not specified by the manufacturer!
  • There is a risk of explosion if the lithium battery is replaced with an incorrect type. Replace the battery using the same type and manufacturer only.
  • Keep the Expansion Unit as far as possible from heavy contactor boxes and other sources of electrical interference.

2.1.2 SAFETY PRECAUTIONS
CAUTION These units must be installed by an authorized electrician. Disconnect the power to avoid electrical shock and damage.
NOTE Installation Category (Over voltage Category) II

  • The power supply to the controller should be protected by 1 amps circuit breaker.
  • All electrical connections should comply with National Electrical code (NEC).

2.1.2.1 Grounding and Shielded Wiring

  • From the ground terminal, run a heavy wire directly to the ground rod. If necessary, run a heavy ground wire to the electrical service grounding system rather than directly to the ground rod.
  • Do not use light wires for these ground connections. They must carry heavy lightning currents, sometimes exceeding thousands of amperes. Certainly, do not use the shielding of sensor and low voltage wiring for this purpose.
  • Every low power device (digital, analog, or communication) must have a shield cable connected to the unit ground strip.

2.1.2.2 Installation and Electrical Connections

  • Install computerized electronic controls at least three feet (one meter) away from interference sources such as high voltage wiring to motors, variable speed, light dimmers, relays.
  • Install electronic controls in a separate ventilated control room that is protected from extreme temperatures and dirty environments. Place the controls so that the operators can conveniently use the control and read indicators and displays.
  • Keep low voltage wires separate from high voltage wires.
  • Use shielded wiring for low level signals. For buried wiring (building to building runs) use high grade jell filled cables that are impervious to moisture.
  • Seal cable entry points and control boxes to prevent contamination and corrosion. If you use silicon sealant with acetic acid cure, keep the control open and ventilated until cured.
    Otherwise, the acetic acid will attack the metal parts, including circuitry.

2.1.3 WHAT COMES IN THE PACKAGE

  • One expansion unit
  • One hanging bracket
  • Two screws

2.2 Mounting the Unit

  • Knockouts
  • Hanging the Unit

2.2.1 KNOCKOUTS

  1. Using the supplied clips and screws, mount the TRIO Expansion.

  2. On the bottom the unit are knockouts used to route the low and high voltage cables.
    Munters 117789 TRIO Expansion Controller Relays - Figure
1o Using a screwdriver and a hammer, gently apply pressure to the knockouts.
    o Only open up the holes that you require.
    o Munters recommends removing the knockouts before mounting the unit.

  3. Place the required cables through the cable holders at the bottom of the unit.
    CAUTION Run low voltage cables through one knockout and high voltage relay cables through a separate knockout. Do not place them in the same knockout!

  4. Close the Expansion Unit enclosure lid carefully and tightly. Use RTV silicon or equivalent sealant to seal the cable holders.
    CAUTION Munters strongly recommends that you seal all entry spots with RTV silicon. Failure to do so can lead to damage to the unit.

  5.  After installation is completed, operate the Expansion Unit for a few hours and re- check for proper operation.

2.2.2 HANGING THE UNIT

  1. Attach the bracket to the wall (customer supplies the screws).
  2. Hang the TRIO on the bracket.
  3. Secure the unit to the wall using the two screws provided (optional).

2.3 Layout

Munters 117789 TRIO Expansion Controller Relays - Figure
4

1 10 relays
2 RS-485 ports
3 Power ports
4 Ground strip

2.4 Wiring Diagrams

  • TRIO to TRIO Expansion Wiring
  • High Voltage Relays
  • Power

2.4.1 TRIO TO TRIO EXPANSION WIRING

Munters 117789 TRIO Expansion Controller Relays - Figure
5

  • The cable between the controller and the expansion unit should be a 4 wire twisted shielded cable (22 or 24 AWG).
  • 1: Red wire
  • 2: Black wire

2.4.2 HIGH VOLTAGE RELAYS

Munters 117789 TRIO Expansion Controller Relays - Figure
6

1 Example of devices

NOTE The relays control motors and heating devices via contactors, not directly. Munters 117789 TRIO Expansion Controller Relays - Figure
7

2.5 TRIO / TRIO Expansion Termination
When TRIO is wired to a TRIO Expansion unit, the termination dipswitch in both units must be set to ON. Munters 117789 TRIO Expansion Controller Relays -
Figure 8

When the TRIO is not wired to an Expansion device, the termination dipswitch must be set to OFF.
2.6 Key
Ensure that the unit remains locked to prevent unauthorized access to internal components.

2.7 Product Symbols
The following labels appear on your controller:
Caution! Hazardous voltage
Caution: Refer to the manual
Main Protective Earthing Terminal
CAUTION IF THE UNIT IS USED IN A MANNER NOT SPECIFIED BY THE MANUFACTURER, THE PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED.

Mapping Devices

Install and wire the Expansion unit to the TRIO and to the external devices before beginning.

After wiring devices to the TRIO Expansion Unit, each device must be mapped and then defined.
Mapping and defining devices enables the system software to control each device’s functionality.
CAUTION Mapping MUST match the physical wiring! An error message appears if the physical device is not wired to the relay or port as defined on the mapping screen..
To map the devices:

  1. Go to System > Device and Sensors.
    Munters 117789 TRIO Expansion Controller Relays - Figure
11

  2. Click Expansion.
    Munters 117789 TRIO Expansion Controller Relays - Figure
12

  3. Map the devices as detailed in the TRIO manual. Refer to the manual for more information.

Specifications

Input Power Voltage 115/230 VAC, 50/60 Hz
Input AC Power 0.2A
Maximum number of relays operating simultaneously 10

Note: Running relays at the above current levels provides between 50,000 – 100,000 switching operations.
Communication| RS-485: 115 Kbps, 8 bit, even parity
Operating Temperature Range| -10° to +50° C (+14° to +125° F)
Storage Temperature Range| -20° to +80° C (-4° to +176° F)
Environmental Specifications| • Altitude: -400 m to 2000 m
• Relative Humidity: 20% – 90%
• Main supply voltage fluctuation up to +10 – 20%
• Overvoltage category II
Enclosure| • Water and dust tight
• Indoor use only
Dimensions (H/W/D)| 403 x 324 x 141 mm/16 x 13 x 5.6 inches
Fuses| Fuse F2 on PS card: 3.15A, 250V
Certification| Munters 117789 TRIO Expansion Controller Relays - Figure
13

  • Disconnection device/overcurrent protection: In the building installation, use a certified 2pole circuit breaker rated 10A, certified in accordance with the IEC standard 60947-2 (in the US and Canada use a Listed Brach Circuit protective circuit breaker). This step is required to provide overcurrent protection and mains disconnection. The circuit breaker must be easily accessible and marked as the controller disconnect device.
  • Main Supply Voltage: Permanently connect the controller to the mains in accordance with the relevant national code. Provide fixed wiring inside a flexible conduit. Relays must be suitably protected against overcurrent, using a circuit breaker rated at 10A.

Spare Parts

  • Preliminary Information
  • TRIO 10 Expansion Enclosure Spare Parts
  • TRIO 10 Expansion Main Container Spare Parts
  • Main Container Card Spare Parts

5.1 Preliminary Information

| TRIO 10 EXP
---|---
Container| A
Main Container Cards| B
MPN| Munters Part Number
DPN| Dealer Part Number

5.2 TRIO 10 Expansion Container Spare PartsMunters 117789 TRIO
Expansion Controller Relays - Figure 14

ID No. Description Order Catalog Number
A1.1 TRIO FRONT DOOR EXP PLASTIC PART V1.0.0 (SP : 207129) MPN: 940-99-00028

DPN:
A1.2| TRIO-20 PLASTIC BOX BASE| MPN: 940-99-00007
DPN:
A1.3| TRIO HINGE PLASTIC PIN V1.0.0 (SP-207128)| MPN: 940-99-00019
DPN:
| TRIO-20 PLASTIC BLUE PANEL (MUNTERS LOGO)| MPN: 940-99-00001
DPN:
A3.1| GENERAL PLASTIC LATCH| MPN: 900-99-00216
DPN:
A3.2| ONE/ONE PRO LATCH GENERAL LOCK PLASTIC PART + LOCK FOR LATCH| MPN: 900-99-00217
DPN:
Z| MID-RANGE MAIN GASKET V1.0.0 (SP-207122)| MPN: 940-99-00021
DPN:

5.3 TRIO 10 Expansion Main Container Spare Parts

Munters 117789 TRIO Expansion Controller Relays - Figure
16

ID No. Description Order Catalog Number
B1 TRIO-EXP 10 CARD (SP: R-TRIO-EXP10) MPN: 940-99-00029

DPN:
B1.1| SWPS APV-1 6-1 2 Mean Well 1 15V/230V 12V 16W (SP: 370153)| MPN: 999-99-00338
| DPN:

5.4 Main Container Card Spare Parts

Card Description Munters Ordering Number
R-TRIO-EXP10: TRIO EXP
10 CARD 940-9900029
370153: SWPS APV-1612
Mean Well 115V/230V 12V 16W 999-9900338

Warranty

Warranty and technical assistance
Munters products are designed and built to provide reliable and satisfactory performance but cannot be guaranteed free of faults; although they are reliable products they can develop unforeseenable defects and the user must take this  into account and arrange adequate emergency or alarm systems if failure to operate could cause damage to the articles for which the Munters plant was required: if this is not done, the user is fully responsible for the damage which they  could suffer.
Munters extends this limited warranty to the first purchaser and guarantees its products to be free from defects originating in manufacture or materials for one year from the date of delivery, provided that suitable transport, storage,  installation and maintenance terms are complied with. The warranty does not apply if the products have been repaired without express authorisation from Munters, or repaired in such a way that, in Munters’ judgement, their  performance and reliability have been impaired, or incorrectly installed, or subjected to improper use. The user accepts total responsibility for incorrect use of the products.
The warranty on products from outside suppliers fitted to the Expansion Unit, (for example antennas, power supplies, cables, etc.) is limited to the conditions stated by the supplier: all claims must be made in writing within eight days of  the discovery of the defect and within 12 months of the delivery of the defective product. Munters has thirty days from the date of receipt in which to take action, and has the right to examine the product at the customer’s premises or at its  own plant (carriage cost to be borne by the customer).
Munters at its sole discretion has the option of replacing or repairing, free of charge, products which it considers defective, and will arrange for their despatch back to the customer carriage paid. In the case of faulty parts of small  commercial value which are widely available (such as bolts, etc.) for urgent despatch, where the cost of carriage would exceed the value of the parts, Munters may authorise the customer exclusively to purchase the replacement parts  locally; Munters will reimburse the value of the product at its cost price.
Munters will not be liable for costs incurred in demounting the defective part, or the time required to travel to site and the associated travel costs. No agent, employee or dealer is authorised to give any further guarantees or to accept any  other liability on Munters’ behalf in connection with other Munters products, except in writing with the signature of one of the Company’s Managers.
WARNING: In the interests of improving the quality of its products and services, Munters reserves the right at any time and without prior notice to alter the specifications in this manual.

The liability of the manufacturer Munters ceases in the event of:

  • dismantling the safety devices;
  • use of unauthorised materials;
  • inadequate maintenance;
  • use of non-original spare parts and accessories.

Barring specific contractual terms, the following are directly at the user’s expense:

  • preparing installation sites;
  • providing an electricity supply (including the protective equipotential bonding (PE) conductor, in accordance with CEI EN 60204-1, paragraph 8.2), for correctly connecting the equipment to the mains electricity supply;
  • providing ancillary services appropriate to the requirements of the plant on the basis of the information supplied with regard to installation;
  • tools and consumables required for fitting and installation;
  • lubricants necessary for commissioning and maintenance.

It is mandatory to purchase and use only original spare parts or those recommended by the manufacturer.
Dismantling and assembly must be performed by qualified technicians and according to the manufacturer’s instructions.
The use of non-original spare parts or incorrect assembly exonerates the manufacturer from all liability.
Requests for technical assistance and spare parts can be made directly to the nearest Munters office.