APC BR1200SI Sinewave, AVR, LCD, 8 IEC outlets User Manual

June 4, 2024
APC

BR1200SI Sinewave, AVR, LCD, 8 IEC outlets
User Manual

Safety and General Information

Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.
SAVE THESE INSTRUCTIONS – This section contains important instructions that should be followed during the installation and maintenance of the UPS and batteries.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • This ups is intended for indoor use only.
  • Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
  • Connect the UPS power cable directly to a wall outlet.
  • Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
  • Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions.
  • A battery can present a risk of electric shock and burns by high short−circuit current.
  • Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces.

Failure to follow these instructions will result in death or serious injury.

Inventory

APC BR1200SI Sinewave AVR LCD 8 IEC outlets -
Inventory

Connect the Battery

The UPS is shipped with the battery disconnected.

  1. Lay the UPS with the battery door facing up.
    The arrows point to the locking tabs of the battery compartment.

  2. Press the tabs downwards and pull the battery door away from the unit to access the battery modules.

  3. Using the handles on both sides of the battery, lift the battery 30 degrees upward to expose the battery connector. Connect the red wire as shown above.

  4. Push the battery into the unit.
    APC BR1200SI Sinewave AVR LCD 8 IEC outlets - Battery
4

  5. Replace the battery door.

Install PowerChute™ Personal Edition Software

Use PowerChute Personal Edition software to configure the UPS settings. During a power outage, PowerChute will save any open files on your computer and shut it down.
When power is restored, it will restart the computer.
Note: PowerChute is only compatible with a Windows operating system. If you are using Mac OSX, use the native shutdown feature to protect your system. See the documentation provided with your computer.

Installation

Use the USB communication cable supplied with the Back-UPS to connect the data port on the Back-UPS to the USB port on your computer. On the computer, go to www.apc.com Search for “PowerChute Personal Edition” then click on “View Details”  to download the latest version of PCPE software. Click the download link and select Software product. Select the appropriate operating system. Follow the directions to download the software.

Connect the Equipment

Battery backup and surge-protected outlets
When the Back-UPS is receiving input power, the Battery Backup with Surge Protection outlets will supply power to connected equipment. During a power outage or other AC
problems, the Battery Backup outlets receive power for a limited time from the BackUPS.
Connect equipment such as printers, fax machines, scanners, or other peripherals that do not need battery backup power to the Surge Protection Only outlets. These outlets provide full-time protection from surges even if the Back-UPS is switched OFF.

APC BR1200SI Sinewave AVR LCD 8 IEC outlets -
Equipment

1| USB and
Serial
Data port| To use PowerChute Personal Edition,
connect the supplied USB cable or an
optional serial cable (not supplied).
---|---|---
2| Telephone Cable Surge
Protected ports| Connect the ground lead from an additional surge suppression device such as a stand-alone data line surge protector.
3| AC Power
Input| Use a power cable to connect the unit to
AC power.
4| Battery
Backup
outlets
with Surge
Protection| During a power outage or other AC
problems, the Battery Backup outlets
receive power for a limited time from
the Back-UPS. Connect critically
equipment such as desktop computers,
computer monitor, modem, or other data
sensitive devices into these outlets.
5| Circuit
Breaker| Use to reset the system after an overload
the condition has occurred causing the circuit breaker to trip.
6| In/Out
Ethernet
surge protected
ports| Use an Ethernet cable to connect a cable
modem to the IN port, and connect a
computer to the OUT port.
7| Surge
Protected
outlets| These outlets provide full-time protection from surges, even if the  BackUPS is off.
Connect equipment such as printers and scanners that do not require battery backup protection.

Operation

Power saving display

The display interface can be configured to be continuously illuminated or to save energy, it can be configured to darken after a period of inactivity.

  1. Full-Time Mode: Press and hold DISPLAY for two seconds. The display will illuminate and the Back-UPS will beep to confirm the Full-Time mode.
  2. Power Saving Mode: Press and hold DISPLAY for two seconds. The display will darken and the Back-UPS will beep to confirm the Power Saving mode. While in Power  Saving Mode, the display will illuminate if a button is pressed, it then darkens after 60 seconds of no activity.

Unit sensitivity

Adjust the sensitivity of the Back-UPS to control when it will switch to battery power; the higher the sensitivity, the more often the Back-UPS will switch to battery power.

  1. Ensure the Back-UPS is connected to AC power but is OFF.
  2. Press and hold the POWER button for six seconds. The LOAD CAPACITY bar will flash on and off, indicating that the Back-UPS is in programming mode.
  3. Press POWER again to rotate through the menu options. Stop at selected sensitivity. The Back-UPS will beep to confirm the selection.

Generator Sensitivity

Default

Sensitive Loads

Low sensitivity

156-300 Vac
Input voltage is extremely low or high. (Not recommended for computer loads.)

Medium sensitivity (Default)
176-294 Vac
The Back-UPS frequently switches to battery power.

High sensitivity
176-288 Vac
The connected equipment is sensitive to voltage fluctuations.

Front panel buttons and display interface

Use the three buttons on the front panel of the Back-UPS and the display interface to configure the Back-UPS.

Front panel

APC BR1200SI Sinewave AVR LCD 8 IEC outlets - Front
panel

  1. Display button
  2. Power On/Off button
  3. Mute button
  4. Display interface
  5. USB charging ports:
    The 2 USB ports provide a total of 15W  of DC power and will provide power even when the UPS is on battery.

| Online: The Back-UPS is supplying conditioned AC power to connected equipment
---|---
| Load Capacity: The load is indicated by the number of sections illuminated, one to five. Each bar represents 20% of the load.
| Battery Capacity: The battery charge level is indicated by the number of sections illuminated. When all five blocks are illuminated, the Back-UPS is at full charge. When one block is filled, the Back-UPS is near the end of its battery capacity,  the indicator will flash and the Back-UPS will beep continuously.
| Low Battery: When battery capacity reaches the empty level, the Back- UPS is nearing shutdown and the indicator will flash accompanied by a continuous beep.
| Replace Battery: The battery is nearing the end of its useful life. When the display shows a flashing Replace Battery icon and an empty Battery Capacity icon, replace the battery as early as possible.
| On Battery: The Back-UPS is supplying battery backup power to the connected equipment, it will beep four times every 30 seconds.
EVENT| Event: The event counter shows the number of events that occurred that caused the Back-UPS to switch to an on-battery operation.
| System Error Detected: The system has an error. The error number will illuminate on the display interface. See “System errors” on page 7.
| Overload: The power demand from the load has exceeded the capacity of the Back-UPS.
| Mute: If the line through the speaker icon is illuminated, the audible alarm has been turned off.
| Out: Output voltage, frequency
In : Input voltage.
| Automatic Voltage Regulation:
When illuminated, the Back-UPS is compensating for low input voltage
When illuminated, the Back-UPS is compensating for high input voltage.
| Estimated Run Time: This indicates the battery runtime minutes that remain if the Back-UPS switches to battery power.
LOAD| Load: The total load in watts (W) or percentage (%) used by the devices connected to the Battery Backup outlets.

Alarms and System Errors

Audible indicators

Four Beeps Every 30 Seconds| Back-UPS is running on battery. You should consider saving any work in progress.
---|---
Continuous Beeping| Low battery condition and battery run-time are very low.
Promptly save any work in progress, exit all open applications, and shut down the operating system.
Continuous tone| Battery Backup outputs are overloaded.
Chirps every 2 Seconds| The battery is disconnected.
Continuous chirping| The battery did not pass the automatic diagnostic test and should be replaced as early as possible. Pressing the MUTE button pauses the chirping.

Status icons

If these icons are flashing… This may be the problem.
The Back-UPS is overloaded. Disconnect one of the items connected to

the Back-UPS. If the Overload icon stops flashing, the Back-UPS is no
longer overloaded and will continue to operate normally.
| The Back-UPS is operating on AC power, but the battery is not functioning properly. Contact Schneider Electric IT (SEIT) Customer Service to order a replacement battery. See “Battery Replacement” on page 10.
| The Back-UPS is operating on battery power and the battery power is getting low.  Shut down all connected equipment to avoid losing unsaved data. When possible, connect the Back-UPS to AC power to recharge the battery.
| The battery is not connected. See “Connect the Battery” on page 2 to make sure battery wires are connected properly.

System errors
The Back-UPS will display these error messages. Except for errors F01 and F02, contact SEIT Technical Support.

| F01 On-Battery Overload| Turn the Back-UPS off.
Disconnect non-essential equipment from the Battery
Backup outlets and turn Back-UPS on.
---|---|---
F02 On-Battery Output Short| Turn the Back-UPS off.
Disconnect all equipment from the Battery Backup outlets and the turn Back-UPS on.
Re-connect equipment one item at a time. If the output is tripped again, disconnect the device that caused the error.
F04 Clamp Short| Errors F04-F09 cannot be corrected by the user, contact
SEIT Technical Support for assistance.
F05 Charge Error
F06 Relay Welding
F07 Temperature
F08 Fan Error
F09 Internal Error

Function Button Quick Reference

Function| Button| Timing (seconds)| UPS Status| Description
---|---|---|---|---
Power
Power On| | 0.2| Off| Press POWER to start receiving input AC power. If AC
input power is not available, the Back-UPS will run on
battery power.
Power Off| | 2| On| The Back-UPS is not receiving input AC power, but is
providing surge protection.
Display
Status
Inquiry| | 0.2| On| Verify the status or condition of the Back-UPS. The
LCD will illuminate for 60 seconds. Press the button
the toggle into various information.
Full-Time/
PowerSaving
mode| | 2| On| The LCD will illuminate and the Back-UPS will beep to confirm the Full-Time mode. The LCD will darken and the Back-UPS will beep to confirm the PowerSaving mode. While in Power-Saving  Mode, the LCD  will illuminate if a  button is pressed, then darkens after 60 seconds of no activity.
Mute
Enable/
Disable
mode| | 2| On| Enable or disable the audible alarms. The Mute icon
will illuminate and the Back-UPS will beep one time.
Sensitivity| | 6| Off| The Load Capacity icon will blink, indicating that the
Back-UPS is in programming mode. Use the POWER
button to scroll through Low, Medium, and High, and stop at the selected sensitivity. The Back-UPS will beep toconfirm selection. See “Unit sensitivity” for details.
Self-Test
(manual)| | 6| on| The Back-UPS will perform a test of the internal
battery. Note: This will happen automatically when the
Back-UPS is turned ON or when the Back-UPS previously detected a bad battery.
Event
Reset| | 0.2| on| When the Event screen is visible, press and hold
DISPLAY, then press POWER, to clear the detected error
event counter.
Error
Reset| | 2| Error| After an error has been identified, press POWER to
remove the visual indication and return to standby status.

Troubleshooting

Problem Possible Cause Corrective Action
flack-UPS will not switch on. The Back-UPS is not connected to AC power.

Ensure that the Back-UPS is securely connected to an AC outlet.
The circuit breaker has been tripped.| Disconnect non-essential equipment from the Back-UPS. Reset the circuit breaker. Re-connect equipment one item at a time. If the circuit breaker is tripped again, disconnect the device that caused the trip.
The internal battery is not connected.| Connect the battery.
The AC input voltage is out of range.| Adjust the transfer voltage and sensitivity range.
The Back-UPS does not provide power during an AC power outage.| Ensure that essential equipment is not plugged into a SURGE ONLY outlet.| Disconnect equipment from the SURGE ONLY outlet and re-connect to a Battery Backup outlet.
The Back-UPS is operating on battery power, while connected to AC power.| The plug has partially pulled out of the wall outlet, the wall outlet is no longer receiving AC power, or the
circuit breaker has been tripped.| Ensure that the plug is fully inserted into the wall outlet. Ensure that the wall outlet is receiving AC power by checking it with another device.
The Back-UPS is performing an automatic self-test.| No action is necessary.
The AC input voltage is out of range, the frequency is out of range, or the waveform is distorted.| Adjust the transfer voltage and sensitivity range.
The Back-UPS does not provide the expected amount of backup time| Battery Backup outlets may be fully or improperly loaded.| Disconnect non-essential equipment from the Battery Backup outlets and connect the equipment to SURGE outlets.
The battery was recently discharged due e to a power outage and has not fully recharged.| Charge the battery cartridge for 16 hours.
The battery has reached the end of its useful life.| Replace the battery.
The REPLACE
BA I [‘FRY indicator is illuminated.| The battery has reached the end of its useful life.| Replace the battery as early as possible.
The OVERLOAD
indicator is illuminated.| The equipment connected to the Back-UPS is drawing more power than the Back-UPS can provide.| Disconnect non-essential equipment from the Battery Backup outlets and connect the equipment to SURGE outlets.
The SYSTEM ERROR indicator is illuminated, and all the front panel indicators are flashing.| There is an internal error.| Determine which internal error
the message is displayed by matching the number displayed on the LCD with the corresponding Error Message (see “System errors”) and contacting SEIT Technical Support.

Specifications

| BR1200SI| BR1600SI
---|---|---
VA| 1200 VA| 1600 VA
Maximum Load| 720W| 960W
Nominal Input Voltage| 220 – 240 Vac
Online Input Voltage Range| 176 – 294 V
Automatic Voltage Regulation| Boost by +11.5% when input voltage drops below the limit
Trim by -10.2% when input voltage exceeds the limit
Frequency Range| 50/60 Hz ± 3%
On-battery Waveshape| sine-wave
USB charging port| Type C1, Type A1 (15W in total)
Typical Recharge Time| 16 hours
Transfer Time| 8 ms (typical), 10 ms (maximum)
Operating Temperature| 32 to 104 ° F (0 — 40 °C)
Storage Temperature| 23 to 113 °F (-15 — 40 °C)
IP Rating| IP20
Battery Type| Lead acid, 12V x 2 batteries
Unit Dimensions| 11.9 x4.4 x15.0 in (368 x100 x260 mm)
Unit Weight| 25.8 lb (11.7 kg)| 27.6 lb (12.5 kg)
Interface| USB and Simple Signal
On-Battery Runtime| Go to: http://www.apc.com/product

Battery Replacement

CAUTION

RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE

  • Replace the battery at least every 5 years.
  • Replace the battery immediately when the UPS indicates battery replacement is necessary.
  • Replace the battery at the end of its service life.
  • Replace batteries with the same number and type of batteries as originally installed in the equipment.
  • Replace the battery immediately when the UPS indicates a battery over−temperature condition or UPS internal over−temperature, or when there is evidence of electrolyte leakage.
    Power off the UPS, unplug it from the AC input and disconnect the batteries. Do not operate the UPS until the batteries have been replaced.

Failure to follow these instructions can result in minor or moderate injury and equipment damage.

The battery typically lasts for 3 to 5 years, a shorter period if subjected to frequent outages or elevated temperatures. Battery replacement parts for Back- UPS Pro BR1200SI is  APCRBC161, and for BR1600SI are APCRBC163. Delaying the replacement of parts may corrode the batteries in the cartridge. Recycle spent battery cartridges.

Warranty

The standard warranty is three (3) years from the date of purchase, valid in the European Community. For all other regions, the standard warranty is two (2) years from the date of purchase. Schneider Electric IT (SEIT) standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with a SEIT Technical Support representative. SEIT will ship the replacement unit once the defective unit has been received by the repair department or cross-ship it upon the receipt of a valid credit card number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement unit to the customer.

APC by Schneider Electric IT Customer Support Worldwide

For country-specific customer support, go to the APC by Schneider Electric Web site, www.apc.com.

© 2019 APC by Schneider Electric. APC, the APC logo, Back-UPS, and PowerChute are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are the property of their respective owners.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals