BEKA associates BA368E Counters
Product Information
- The BA368E is a two input, intrinsically safe panel mounting Counter that is compatible with a wide variety of sensors. It has IP66 front of panel protection and IP20 protection at the rear. The Counter is certified with IECEx, ATEX, and UKEX certificates, indicating that special conditions apply for safe use. It is important to note that an electrostatic charge can be generated, so the instrument enclosure should only be cleaned with a damp cloth.
- The Counter comes with terminals for optional 4/20mA output, as well as terminals for optional dual alarms. It also features pulse inputs, pulse outputs, and power supply connections. The display of the Counter shows the units of measurement, which are indicated by a printed scale card visible through a window on the right-hand side of the display.
- The scale card can be easily changed without removing the Counter from the panel or opening the instrument enclosure.
- In addition, the Counter requires specific wiring configurations for specified immunity and recommends using screened twisted pairs with screens earthed at one point within the safe area to ensure EMC compliance.
- For more information and support, contact BEKA associates Ltd. at Old Charlton Rd, Hitchin, Hertfordshire, SG5 2DA, UK. Tel: +44(0)1462 438301. Email: sales@beka.co.uk. Website: www.beka.co.uk
Product Usage Instructions
- To install the BA368E Counter, follow these steps:
- Align the foot and body by turning the screw anticlockwise.
- Position the gasket behind the instrument bezel.
- Insert the instrument into the panel from the front.
- Insert the panel clamp into the recess and gently pull it onto the dovetail.
- Engage the screw and turn it clockwise to tighten the clamp.
- To change the scale card:
- Unlock the Counter.
- Insert the flexible strip carrying the new scale card into the slot at the rear of the Counter.
- Lock the Counter.
- Ensure that all wiring is done according to the specified immunity requirements. Use screened twisted pairs with screens earthed at one point within the safe area for EMC compliance.
DESCRIPTION
- The BA367E is a panel mounting, intrinsically safe, one input Counter which will function with a wide variety of sensors.
- This abbreviated instruction sheet is intended to assist with installation, a comprehensive instruction manual describing safety certification, system design and configuration may be downloaded from the BEKA website or may be requested from the BEKA sales office.
- The BA367E Counter has IECEx, ATEX and UKEX intrinsic safety certification for use in flammable gas atmospheres. ETL and cETL approval permits installation in the USA and Canada. The certification information label, which is located on the top of the instrument enclosure, shows the certification number and codes. Other certifications may be shown.
- Copies of certificates may be down loaded from the BEKA website.
Typical certification information label
Special conditions for safe use
The IECEx, ATEX and UKEX certificates have an ‘X’ suffix indicating that
special conditions apply for safe use.
WARNING
To avoid an electrostatic charge being generated instrument enclosure should
only be cleaned with a damp cloth.
INSTALLATION
The BA368E Counter has IP66 front of panel protection but it should be shielded from direct sunlight and severe weather conditions. The rear of the instrument has IP20 protection.
Cut-out dimensions
Recommended for all installations. Mandatory to achieve IP66 seal between
instrument and panel.
136 +0.5/-0.0 x 66.2 +0.5/-0.0
Abbreviated instructions for
BA368E One input Intrinsically safe Counter
- Align foot and body by turning screw anticlockwise
EMC
For specified immunity all wiring should be in screened twisted pairs with
screens earthed at one point within the safe area. Scale card
The Counters units of measurement are shown on a printed scale card visible
through a window at the right hand side of the display. The scale card is
mounted on a flexible strip that is inserted into a slot at the rear of the
instrument as shown below
Fig:4 Inserting flexible strip carrying scale card into slot at the rear
of Counter.
- Thus the scale card can easily be changed without removing the Counter from the panel or opening the instrument enclosure.
- New Counters are supplied with a printed scale card showing the requested units of measurement, if this information is not supplied when the Counter is ordered a blank card will be fitted.
- A pack of self-adhesive scale cards printed with common units of measurement is available as an accessory from BEKA associates. Custom printed scale cards can also be supplied.
- To change a scale card, unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it out of the enclosure. Peel the existing scale card from the flexible strip and replace it with a new printed card, which should be aligned as shown below. Do not fit a new scale card on top of an existing card.
- Align the self-adhesive printed scale card onto the flexible strip and insert the strip into the Counter as shown.
Fig 5 Fitting scale card to flexible strip
OPERATION
The Counter is controlled by four front panel push buttons. When in operating mode they have the following functions:
- ( ) Access to configuration menu.
- Grand total – shows Lo followed by least significant 8 digits of the 16 digit grand total.
- Grand total – shows Hi followed by the most significant 8 digits of the 16 digit grand total.
- + If Local Grand Total Reset Clr Gtot in the instrument configuration menu has been activated, operating the ) and buttons simultaneously for ten seconds will result in Clr . no being displayed with the no flashing. Operating the or & button will change the display to Clr . YE5, the button will then reset the grand total to zero which will be confirmed by a brief display of Gt Clrd.
- Shows in succession, firmware version number, instrument function counter and any output accessories that are fitted:
- A Dual Alarm Outputs
- C 4/20mA output.
- When optional alarms are fitted provides direct access to the alarm setpoints if A5CP (access to setpoints) has been enabled in the configuration menu.
CONFIGURATION
- Counters are supplied configured as requested at time of ordering, if not specified default configuration will be supplied but can easily be changed on-site.
- Fig 6 shows the location of each function within the configuration menu with a brief summary of the function. Please refer to the full instruction manual for detailed configuration information and for description of optional outputs.
- Access to the configuration menu is obtained by pressing the ( and ) buttons simultaneously. If the Counter’s security code is set to default 0000 the first parameter input will be displayed. If the instrument is protected by a security code, code will be displayed. The four digit code must be entered to gain access to the menu.
Fig 6 Configuration menu Manuals, certificates and data-sheets can be downloaded from http://www.beka.co.uk/ba367e
- The BA67E is CE marked to show compliance with the European Explosive Atmospheres Directive 2014/34/EU and the European EMC Directive 2014/30/EU.
- It is also UKCA marked to show compliance with UK statutory requirements Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations UKSI 2016:1107 (as amended) and with the Electromagnetic Compatibility Regulations UKSI 2016:1091 (as amended).
Issue 3
24th November 2022
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire, SG5 2DA, UK
Tel: +44(0)1462 438301 e-mail: sales@beka.co.uk
web: www.beka.co.uk