inventor CF-ION-10L Comfort Dehumidifier User Manual
- June 4, 2024
- inventor
Table of Contents
- CF-ION-10L Comfort Dehumidifier
- SAFETY & WARNING INSTRUCTIONS
- ELECTRICAL INFORMATION
- SOCIABLE REMARKS ON ENVIRONMENTAL PROTECTION
- SAFETY PRECAUTIONS
- STEPS BEFORE USE
- GETTING TO KNOW YOUR DEHUMIDIFIER
- CONTROL PANEL • FUNCTIONS
- WATER TANK & DRAIN HOSE
- MAINTENANCE & CLEANING
- STORAGE
- FREQUENTLY ASKED QUESTIONS & TROUBLESHOOTING
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
DEHUMIDIFIER
MODELS:
CF-ION-10L
CF-ION-12L
USER’S MANUAL
CF-ION-10L Comfort Dehumidifier
Dear Consumer,
Congratulations on your choice!
The comfort dehumidifier series is an innovative device that ensures both
dehumidifying and purifying capabilities thanks to the function of the
Ionizer. With Comfort series you can enjoy a healthy & comfortable living and
take advantage of all the extra benefits.
Please refer to this manual, to obtain full efficiency of the dehumidifier –
air purifier, through the guidelines included in the following pages and make
savings via clever use of this device.
Please read all the safety instructions carefully before use and keep this instruction manual for future reference.
SAFETY & WARNING INSTRUCTIONS
- No children under the age of 8 should be permitted to operate this electric device. Be certain, that children, handicapped people, or people with a lack of knowledge and experience, must be supervised, depending on the situation, by persons responsible for their well-being and do not undertake procedures such as the cleaning or the maintenance of this device.
- It is important that adequate supervision is provided and that no minors are left unattended with this device.
- This dehumidifier is for domestic and small office use only. Do not use this device for commercial, industrial or marine use, and in areas with wet surfaces such as restrooms or shower rooms.
- This device should always be kept in an upright position to avoid any damage.
- All house exits (windows doors etc) where the dehumidifier is operating, should be shut.
- If water leakage appears within the unit, turn the unit off and disconnect the power cord.
- Before moving, unplug the device and manage to keep it in a vertical position in order to safely be transferred from one area to another.
- Be sure to empty the water whenever the water tank is full or when the device will not be used for a prolonged time.
- Always empty the water tank before storing the unit.
- When the unit has been switched off and instantly switched on, keep in mind that, for operational reasons, there is a 3-minute delay in order to regain normal operation.
- If the unit is misplaced or tipped, unplug the power cord immediately. Make sure the unit is completely dry before resuming operation.
- Disconnect the device, if abnormal sounds, odors or smoke occurs.
- If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons to avoid a hazard. Never attempt to dismantle, repair or modify the device.
- Do not attempt to repair, dismantle or modify this appliance. Contact your authorized service technician for repair or maintenance of this device.
- Do not operate or stop the unit by switching the power supply on or off.
- Do not insert any objects in the unit’s air inlet and exhaust as this may cause damage to the device.
- Do not place heavy objects on the power cord. Make sure that the cord is not compressed.
- Do not place cords under any obstacles (carpets rugs or runners etc). The cord should be arranged away from areas where accidental tripping may occur.
- Casters should be able to move comfortably over any obstacle. Be extra cautious while moving over carpets, since any extra force may cause the tipping of the unit or the spilling of any water collected in the bucket.
- Do not sit or climb on the device.
- Do not place the unit in direct sunlight or near other heating sources.
- Do not use the unit near heat sources, chemicals, radiators, flammable materials, or fire.
- Do not remove the water tank while the device is in use.
- Do not use the device without the filter. Dirt and lint may clog the unit thus reducing performance.
- Do not drink or use the collected water of the unit for any purpose.
- Do not use the unit with wet hands.
- Upon first use, and for proper calibration, please allow the unit to operate continuously for 24 hours.
ELECTRICAL INFORMATION
The nameplate, with all the electrical and technical data of this appliance, is located on the rear panel.
-
The appliance should be installed in accordance with national wiring regulations.
-
Be sure the device is grounded properly. Proper grounding is important as it minimizes the
chance of electric shock or fire. The power cord is equipped with a grounding plug for protection against electric shock hazards. -
The device must be used in a properly grounded wall socket. If the specific socket you intend to use is not adequately grounded or protected by a time delay fuse or circuit breaker, have a qualified electrician install the proper receptacle.
-
Ensure the wall socket is still accessible after the installation of the dehumidifier.
-
Do not use extension cords or adapter plugs with this device. Do not connect the dehumidifier to a multiple socket outlet, which is also being used for other electrical appliances.
-
To avoid personal injury, always disconnect the power supply of the device, before maintenance.
-
The unit’s circuit board (PCB) has an included safety fuse for overcurrent protection. You may find the specifications of the fuse, marked on the circuit board, for example, T 3.15A/250V (or 350V), etc.
Power off the dehumidifier before removing the plug.
SOCIABLE REMARKS ON ENVIRONMENTAL PROTECTION
Disposal of equipment no longer used:
Please follow the instructions below, when using this dehumidifier in European
countries.
-
This appliance requires special treatment for disposal. In the European Union, electronic equipment must not be treated as domestic waste but must be disposed of professionally in accordance with Directive 2002/96/EC of the European Parliament and Council of 27th January 2003 concerning old electrical and electronic equipment.
The disposal of this unit should follow all legal requirements and should not be disposed of as unsorted municipal waste.
The hazardous substances can leak into the groundwater supply thus entering the food chain, endangering your health and the environment. -
Fluorinated Greenhouse Gases are contained in hermetically sealed equipment. For specific information regarding the type the amount and the CO2 equivalent in tons, please
refer to the relevant labels of the unit. -
There are several alternative solutions for disposal:
A) Your local municipality has established free collection systems for electronic waste.
B) Your local retailer upon the purchase of a new product.
C) The manufacturer may accept the old appliance for disposal.
D) Old appliances sometimes contain valuable resources for scrap metal dealers.
SAFETY PRECAUTIONS
Read Safety Precautions before operation and installation
To prevent injury to the user or other people and property damage, the
following instructions must be followed. Incorrect operation due to ignoring
instructions may cause harm or damage.
- The seriousness is classified by the following indications.
WARNING| This symbol indicates the possibility of death or serious
injury.
---|---
CAUTION| This symbol indicates the possibility of injury or damage to
property or serious consequences.
- The meanings of symbols used in this manual are as shown below.
Never do this.
Always do this.
WARNING
Do not exceed the rating of the power outlet or connected device.
Otherwise, it may cause electric shock or fire due to excess heat generation.
Do not operate or stop the unit by switching on or off the power supply.
It may cause electric shock or fire due to heat generation.
Do not damage the power cord or use an unspecified power cord.
It may cause electric shock or fire.
Do not modify the power cord length or share the outlet with other appliances
It may cause electric shock or fire due to heat generation
Do not insert or pull out the plug with wet hands.
It may cause electric shock.
Do not place the unit near a heat source.
Plastic parts may melt and cause a fire.
Disconnect the power if strange sounds, smells, or smoke come from it.
It may cause fire and electric shock.
You should never try to take apart or repair the unit by yourself.
It may cause the failure of the machine or electric shock.
Before cleaning, turn off the power and unplug the unit.
It may cause electrical shock or injury.
Do not use the machine near flammable gas or combustibles, such as gasoline,
benzene, thinner, etc.
It may cause an explosion or fire.
Do not drink or use the water drained from the unit.
It contains contaminants and could make you sick.
Do not take the water bucket out during operation.
Do not use extension cords.
CAUTION
Do not use the unit in small spaces
Do not place the device in areas where water may splash onto the unit.
It may cause an electric shock or fire.
Place the unit on a leveled and sturdy section of the floor.
Do not cover the air intake or exhaust openings.
A lack of airflow can lead to overheating and fire.
Care should be taken when using the unit in a room with the following persons:
Infants, children, elderly people, and people not sensitive to humidity.
Do not use in areas where chemicals are handled.
This will cause the unit to deteriorate due to chemicals and solvents
dissolved in the air.
Never insert your finger or other objects into grills or openings. Take
special care to warn children of these dangers.
It may cause electric shock or failure of the appliance.
Do not place heavy objects on the power cord and take care so that the cord is
not compressed.
There is a danger of fire or electric shock.
Do not climb or sit on the unit.
You may be injured if you fall or the unit could be damaged.
Always insert the air filters securely. Clean the air filters at least once
every two weeks.
Operation without filters may cause low performance and/or damage.
If water enters the unit, turn the unit off and disconnect the power, and
contact a qualified service technician.
Do not place flower vases or other water containers on top of the unit.
Water may spill inside the unit, causing insulation failure and electrical
Shock or fire
CAUTION
- This appliance can be used by children aged 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning the use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision. (be applicable for the European Countries )
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance. (be applicable for other countries except for the European Countries )
- If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a hazard.
- The appliance shall be installed in accordance with national wiring regulations.
- The appliance with an electric heater shall have at least 1-meter space for the combustible materials.
- Contact the authorized service technician for repair or maintenance of this unit.
- Do not use the socket if it is loose or damaged.
- Do not operate your appliance in a wet room such as a bathroom or laundry room.
- Do not use this product for functions other than those described in this instruction manual
- Contact the authorized installer for installation of this unit.
- If the dehumidifier is knocked over during use, turn off the unit and unplug it from the main power supply immediately. Visually inspect the unit to ensure there is no damage. If you suspect the unit has been damaged, contact a technician or customer service for assistance.
- In a thunderstorm, the power must be cut off to avoid damage to the machine due to lightning.
- To reduce the risk of fire or electric shock, do not use this fan with any solid-state speed control device.
- Do not run cord under carpeting. Do not cover the cord with throw rugs, runners, or similar coverings. Do not route cord under furniture or appliances. Arrange the cord away from the traffic area so that it will not be tripped over.
- Do not open the unit during operation.
- When the air filter is to be removed, do not touch the metal parts of the unit.
- Do not operate the unit with a damaged cord. Dispose of the unit or return it to an authorized service facility for proper checking and/or repair.
- Hold the plug by the head of the power plug when taking it out.
Electrical Information
-
The manufactures nameplate is located on the rear or side panel of the unit and contains electrical and other technical data specific to this unit.
-
Be sure the unit is properly grounded. To minimize shock and fire hazards, proper grounding is important. The power cord is equipped with a three-prong grounding plug for protection against shock hazards.
-
Your unit must be used in a properly grounded wall receptacle. If the wall receptacle you intend to use is not adequately grounded or protected by a time delay fuse or circuit
breaker(the fuse or circuit breaker needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the unit), have a qualified electrician install the proper receptacle. -
Ensure the receptacle is accessible after the unit installation.
• Do not use extension cords or adapter plugs with this unit. However, if it is necessary to use an extension cord, use an approved Dehumidifier extension cord only (available at most local hardware stores). -
To avoid the possibility of personal injury, always disconnect the power supply to the unit, before installing and/or servicing.
-
All wirings must be performed strictly in accordance with the wiring diagram located on the middle baffle of the unit (behind the water bucket).
Take note of the fuse specifications
The unit s circuit board (PCB) is designed with a fuse to provide overcurrent
protection. The specifications of the fuse are printed on the circuit board,
such as T 3.15A/250V (or 350V), etc.
NOTE: All the pictures in the manual are for explanation purposes only.
The actual shape of the unit you purchased may be slightly different, but the
operations and functions are the same.
**** | **** |
---|---|
Caution: Risk of fire/ flammable materials (Required for R290 units only) |
IMPORTANT NOTE: Please read this manual carefully prior to installing and operating your device! It is recommended to keep this manual for future reference.
Description of displayed Symbols (*Only applicable to units with R290 Refrigerant)
| WARNING| This symbol indicates the use of a flammable refrigerant. If
any leakage
occurs, or if exposed to an external ignition source, fire risk is possible.
---|---|---
| CAUTION| This symbol indicates that the user’s manual should be read
carefully.
| CAUTION| This symbol indicates that a professional service technician should
handle this unit with reference to the user’s manual
****| CAUTION| This symbol indicates the presence of a user’s or
installation manual
Warnings (for using R290 refrigerant)
-
Transport of equipment containing flammable refrigerants
Determined by local regulations. -
Marking of equipment using signs
See local regulations -
Disposal of appliances supplied with flammable refrigerants
See National Regulations. -
Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer’s instructions. -
Storage of packed (unsold) equipment
Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge.
The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations. -
Information on servicing
-
Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work in the system. -
Work shall be undertaken under a controlled procedure so as to minimize the risk of flammable gas or vapor being present while the work is being performed.
-
General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material. -
Checking for the presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. nonspeaking, adequately sealed, or intrinsically safe. -
Presence of fire extinguisher
If any work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area. -
No ignition sources
No person carrying out work in relation to a refrigeration system that involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removal, and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks.” No Smoking” signs shall be displayed. -
Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. -
Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance.
The following check shall be applied to installations using flammable refrigerants:
–the charge size is in accordance with the room size within which the refrigerant-containing parts are installed;
— The ventilation machinery and outlets are operating adequately and are not obstructed;
–If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of any refrigerant. Any markings on the equipment must be visible and readable.
Markings and signs that are unrecognizable must be corrected;
–Refrigeration pipes or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant- containing components unless the components are constructed of materials that are inherently resistant to being corroded or are suitably protected against being so corroded. -
Checks to electrical devices
Repair and maintenance of electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise the safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include:
–that capacitor is discharged; this shall be done in a safe manner to avoid the possibility of sparking;
–that there no live electrical components and wiring are exposed while charging, recovering, or purging the system;
–that there is continuity of earth bonding.
7. Repairs sealed components
During repairs to sealed components, all electrical supplies shall be
disconnected from the equipment being worked upon prior to any removal of
sealed covers, etc. If it is absolutely necessary to have an electrical supply
to equipment during servicing, then a permanently operating form of leak
detection shall be located at the most critical point to warn of a potentially
hazardous situation.
Particular attention shall be paid to the following to ensure that by working
in electrical components, the casing is not altered in such a way that level
of protection is affected. This shall include damage to cables, an excessive
number of connections, terminals not made to original specification, damage to
seals, incorrect fitting of glands, etc.
Ensure that seals or sealing materials have not degraded such that they no
longer serve the purpose of preventing the ingress of flammable atmospheres.
Replacement parts shall be in accordance with the manufacturer’s
specifications,
NOTE The use of silicon sealant may inhibit the effectiveness of some types of
leak detection equipment. Intrinsically safe components do not have to be
isolated prior to working on them.
8. Repair intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit
without ensuring that this will not exceed the permissible voltage and
currently permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while
living in the presence of a flammable atmosphere. The test apparatus shall be
at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts
may result in the ignition of refrigerant in the atmosphere from a leak.
9. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure,
vibration, sharp edges, or any other adverse environmental effects. The check
shall also take into account the effects of aging or continual leaks. A halide
torch (or any other detector using a naked flame) shall not be used
10. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the
searching for or detection of refrigerant leaks. A halide torch (or any other
detector using a naked flame) shall not be used.
11. Leak detection methods
The following leak detection methods are deemed acceptable for systems
containing flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but
the sensitivity may not be adequate or may need re-calibrated. (Detection
equipment shall be calibrated in a refrigerant-free area.) Ensure that the
detector is not a potential source of ignition and is suitable for the
refrigerant used. Leak detection equipment shall be set at a percentage of the
LFL of the refrigerant and shall be calibrated to the refrigerant employed and
the appropriate percentage of gas(25% maximum )is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use
of detergents containing chlorine shall be avoided as the chlorine may react
with the refrigerant and corrode the copper pipe work.
If a leak is suspected, all naked flames shall be removed/extinguished.
If leakage of refrigerant is found which requires brazing, all of the
refrigerants shall be recovered from the system, or isolated (by means of
shut-off valves) in a part of the system both before and during the brazing
process.
Oxygen-free nitrogen (OFN) shall then be purged through the system both before
and during the brazing process.
12. Removal and evacuation
When breaking into the refrigerant circuit to make repairs- or for any other
purpose – conventional procedures shall be used. However, it is important that
best practice is followed since flammability is a consideration. The following
procedure shall be adhered to:
remove refrigerant;
purge the circuit with inert gas;
evacuate;
purge again with inert gas;
open the circuit by cutting or brazing;
The refrigerant charge shall be recovered into the correct recovery cylinders.
The system shall be “flushed’ with OFN to render the unit safe. This process
may need to be repeated several times. Compressed air or oxygen shall not be
used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and
continuing to fill until the working pressure is achieved, then venting to the
atmosphere, and finally pulling down to a vacuum. This processing shall be
repeated until no refrigerant is within the system.
When the final OFN charge is used, the system shall be vented down to
atmospheric pressure to enable work to take place. This operation is
absolutely vital if brazing operations on the pipe-work are to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition
sources and there is ventilation available.
13. Charging procedures
In addition to conventional charging procedures, the following requirements
shall be followed.
-Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
-Cylinders shall be kept upright.
-Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
-label the system when charging is complete (if not already)
-Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system shall be pressure tested with OFN. The system
shall be leak tested on completion of charging but prior to commissioning. A
follow-up leak test shall be carried out prior to leaving the site.
14. Decommissioning
Before carrying out this procedure, it is essential that the technician is
completely familiar with the equipment and all its detail. It is recommended
good practice that all refrigerants are recovered safely. Prior to the task
being carried out, an oil and refrigerant sample shall be taken is case
analysis is required prior to re-use of reclaimed refrigerant. It is essential
that electrical power is available before the task is commenced.
a) become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that;
Mechanical handling equipment is available and being used correctly; the
recovery process is supervised at all times by a competent person; recovery
equipment and cylinders conform to the appropriate standards.
d) Pump down the refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
f) Make sure that the cylinder is situated on the scales before recovery takes
place.
g) Start the recovery machine and operate in accordance with the
manufacturer’s instructions.
h) Do not overfill cylinders. (No more than 80% volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even
temporarily.
j) When the cylinders have been filled correctly and the process completed,
make sure that the cylinders and the equipment are removed from site promptly
and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration
system unless it has been cleaned and checked.
15. Labeling
Equipment shall be labeled stating that it has been de-commissioned and
emptied of refrigerant. The label shall be dated and signed. Ensure that there
are labels on the equipment stating the equipment contains flammable
refrigerant.
16. Recovery
When removing refrigerant from a system, either for servicing or
decommissioning, it is recommended good practice that all refrigerant into
cylinders, and ensure that only appropriate refrigerant recovery cylinders are
employed. Ensure that the correct number of cylinders for holding the total
system charge is available. All cylinders to be used are designated for the
recovered refrigerant and labeled for that refrigerant(i.e special cylinders
for the recovery of refrigerant). Cylinders shall be complete with a pressure
relief valve and associated shut-off valves in good working order. Empty
recovery cylinders are evacuated and, if possible, cooled before recovery
occurs.
The recovery equipment shall be in good working order with a set of
instructions concerning the equipment that is at hand and shall be suitable
for the recovery of flammable refrigerants.
In addition, a set of calibrated weighing scales shall be available and in
good working order.
Hoses shall be complete with leak-free disconnect couplings and in good
condition. Before using the recovery machine, check that it is in satisfactory
working order, has been properly maintained, and that any associated
electrical components are sealed to prevent ignition in the event of a
refrigerant release. Consult the manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the
correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do
not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have
been evacuated to an acceptable level to make certain that flammable
refrigerant does not remain within the lubricant. The evacuation process shall
be carried out prior to returning the compressor to the suppliers. Only
electric heating to the compressor body shall be employed to accelerate this
process. When oil is drained from a system, it shall be carried out safely.
STEPS BEFORE USE
Please refer to the electronic warranty instructions, on the last page (English section) of this manual.
For warranty purposes, please note the SN (serial number).
The SN is labeled opposite the device.
INSTALLATION TIPS
-
Do not block or restrict the airflow around the unit. Make sure the air inlet exhaust grills are not obstructed. Allow 20cm of clearance around the unit and 40cm above.
-
Place the unit in an area where the temperature levels will not fall below 5ºC (41ºF) There is a possibility the coils will collect frost at temperatures that are under 5ºC (41ºF), which may result in low performance.
(Working conditions: 5°C-32°C, 30%RH–80%RH). -
Place the unit away from the clothes dryer, heater, or radiator
-
Ensure the filter is clean.
-
Place the unit in a vertical operating position and allow 2 hours before initial use in order to avoid malfunctions.
-
Prior to initial use, please remove the water bucket and check if any packaging parts (for example the draining hose) are included. Remove and re-position the water bucket firmly into place.
-
Do not connect the dehumidifier to a multiple socket outlet, which is also being used for other electrical appliances.
GETTING TO KNOW YOUR DEHUMIDIFIER
CONTROL PANEL • FUNCTIONS
POWER
By pressing the “POWER” button the dehumidifier turns on or off. The “POWER”
button and Display will turn on and off as well.
- When the set humidity is reached, the Energy Savings function is automatically activated during which the digital control display of the device may show increased humidity levels. This is because the fan is not operating. After the predetermined timeframe and if the humidity levels have increased, the device will resume dehumidification.
- In the event of a power failure, the unit has an Auto Restart function. Once power is restored, the appliance will automatically restart at the preselected settings prior to the power failure.
In case of a power failure, the dehumidifier will resume the previously set operation after a time period of 3 minutes.
MODE
By pressing the “MODE” button, various operations may be selected (Set, Dryer,
Cont., Smart).
While changing operation modes, the device will make a short beep.
Dryer mode: Press the mode button , until the drying clothes function is
selected. A light indicator marked ‘’Dryer’’ will be activated on the control
panel. The fan speed cannot be adjusted in this mode and will be set
automatically to a high fan speed level. After operating for approximately 2
hours the unit will check the room’s humidity. If under 45%RH, only the fan
will operate for two hours. After 2 hours, the unit will quit dryer mode. If
over 45%RH, the unit will operate at Turbo fan Speed for 1 hour before
checking the room’s humidity again.
The maximum operation time set by this mode is 10 hours and can be reduced
depending on the room size and the dampness of the clothes.
- For drying clothes: place the dehumidifier in a small room and set nearby the clothes rack. Keep doors shut and allow the dehumidifier to dry the clothes.
- For optimal results, manual wringing of the clothes is suggested.
- Allow 30-50cm distance from the moist clothes.
- Thick and heavy fabrics may require more time for more effective results.
Continuous mode (Cont.): Press the mode button , until the continuous
dehumidification function is selected. A light indicator marked ‘’Cont.’’ will
be activated on the control panel. The dehumidifier operates continuously when
the drainage pipe is attached, or until the water tank is full, extracting
humidity from the air. When this function is activated the indicator will turn
on and the device will work constantly, disregarding the relative humidity of
the room.
Under the continuous mode, the desired humidity level cannot be adjusted.
This mode is suggested for special humidity conditions where big amounts of
condensation need to be extracted, such as extremely moist rooms.
Smart Dehumidification (SMD): Press the mode button , until the smart
dehumidification function is selected. A light indicator marked ‘’SMD’’ will
be activated on the control panel. The desired humidity levels cannot be
adjusted under this mode.
- While operating in this mode the manual humidity settings function is unavailable.
When none of the above MODE functions are selected (Dryer, Cont., Smart) and all indication lights are off the desired humidity levels can be set manually by pressing the (+) (-) buttons.
Manual Dehumidification (Set)
Press the mode button until the manual setting of the dehumidifier is
selected. A light indicator marked ‘’Set’’ will be activated on the control
panel. The humidity level can be set within a range of 35%RH (Relative
Humidity) to 85%RH (Relative Humidity) in 5% increments each time one of the
relative buttons is pressed, as long as no other modes (Dryer, Cont. or Smart)
are selected.
- For drier air press the descending arrow (-) button to set a lower percent value (%)
- For damper air, press the ascending arrow (+) pad to set a higher percentage value.
The humidity set control buttons are inactive while the Dryer or Cont. or Smart modes are selected.
TIMER
Press the “TIMER” button to initiate the auto START or auto STOP function in
combination with the PLUS (+) and MINUS (-) buttons. The “TIMER” light
indicator on the control panel will turn on.
- When the unit is on, press the Timer button to activate the auto STOP function. When the unit is off, press this button to activate the auto START function.
- Press the (+) or (-) buttons to change the time by 0.5-hour increments, up to 10 hours, or by 1-hour increments up to 24 hours. The control panel will then count down the time remaining until START or STOP.
- The time selected will be stored within 5 seconds and the main display will automatically return to its previous state.
- Turning the unit ON or OFF at any time or changing the timer setting to 0.0 will terminate the Auto Start/Stop function.
- When the code “P2” appears on the led display, the Auto Start/Stop function will be terminated.
The timer function can either be set to ON or OFF. Setting ON and OFF simultaneously is not possible.
FAN
Press the FAN button to select among the Low, Med, or High fan speeds. A light
indicator will illuminate separately for each fan speed selected.
- Low fan speed: When activated the indicator marked “Low” is turned on. Select the low fan speed for quiet operation in order to enjoy ideal conditions.
- Medium fan speed: When activated the indicator marked “Med” will be turned on. Select this mode for normal operation.
- High fan speed: When activated the indicator marked “High” is turned on. Select this mode when immediate dehumidification is necessary, such as in areas or rooms that are unused for an extended period of time.
FRESH
Press the FRESH button to activate the ionizer of the dehumidifier. A light
indicator will illuminate to inform that this function has been selected. Ions
will be released in the
atmosphere to purify the air and remove unpleasant and unhealthy particles.
INDICATIONS
P2 – Bucket Full Indicator
The indicator “P2” will appear on the led display when the bucket is full,
removed, or misplaced.
A light indicator marked ‘’Full’’ will be activated over the led screen and
will remain lit until the water tank is emptied or placed in the proper
position.
- The dehumidifier will shut down automatically when the water tank is full.
Clean filter reminder
A light indicator marked as ‘’Filter’’ will be activated on the control panel
to remind the need to clean the air filter of the dehumidifier. To eliminate
the reminder press for 3 seconds the fan button.
The filter clean reminder will appear on the control panel each time 250
working hours have been completed. To maintain good performance for your
dehumidifier make sure to check and clean the air filter approximately every
15 days.
Auto Defrost
When the frost builds up on the evaporator coils, the compressor will cycle
off and the fan will continue to run until the frost disappears.
- This function not only ensures the safe and appropriate operation of the dehumidifier but is also more efficient and economical in its performance
- When Auto Defrost is operating, the unit may cause some noise from the refrigerant fluids flowing, this is normal.
- Do not turn the dehumidifier off when auto defrosts is operating.
WATER TANK & DRAIN HOSE
There are two ways to remove collected water. Before proceeding ensure that you have switched off and unplugged the unit.
Usage of the water tank
When the unit is OFF and the tank of the dehumidifier is full, the full
indicator will be lit.
Additionally, when the unit is on and the tank is full, the compressor stops
operation followed by the fan a few minutes later. The full indicator will
flash.
- Slowly remove the bucket. Grip the handle with caution and carefully pull outwards so the water does not overflow. Do not place the tank on the floor because the bottom of the tank is uneven. Doing so the tank will fall and the water will be spilled on the floor.
- Empty the water from the tank and place it again into the device. The water tank must be securely and properly placed, for the dehumidifier to operate.
- When the water tank is re-installed the unit will automatically restart.
- When you remove the tank, do not touch any parts inside the unit, as you may damage the device.
- Be sure to gently place the tank into the dehumidifier.
- Do not drink or use the collected water from the device.
- Wipe any excess water on or in the unit when removing the tank.
Continuous draining
Water automatically can be emptied into a floor drain by attaching the unit
with a water hose.
-
Remove the plastic cover located opposite the unit.
Insert the water hose into the drain outlet and make sure all connections are firmly tightened in order to avoid any possible leaks. -
The dehumidifier should be placed on a flat surface in an upright position.
-
Lead the water hose towards a suitable drainage facility and be certain that the water flows naturally. For correct drainage, make sure the hose stays below the level of the drain hose outlet.
Caution:
The water hose should never be bent or twisted!
When the continuous drainage feature is not being used, remove the drain hose from the drain hose outlet and re-install the plastic cover.
MAINTENANCE & CLEANING
Before performing any maintenance or cleaning of the dehumidifier, make sure that it is unplugged.
Cleaning the Filter:
Use water and mild detergent to clean the filter.
- Do not use abrasive cleaning agents or solvents; use a brush or vacuum attachments for cleaning.
- Do not use a dishwasher to clean the filter.
- Do not apply any water directly on or into the device while cleaning, as it may cause rust, insulation deterioration, or electrical shock.
- To remove the air filter, grip the tab and pull the filter outwards.
- Clean the filter with warm and soapy water for more effective results. Rinse carefully.
- Allow the filter to completely dry before re-installing.
Cleaning the tank:
Partially fill the tank with clean water adding a minimal amount of mild
detergent. Clean thoroughly empty and rinse.
- Clean the tank every 2 weeks to prevent mold, mildew, and bacteria growth.
- After cleaning, make sure the tank is placed back securely for the dehumidifier to operate.
Cleaning the unit
- Clean the unit by using a damp sponge, and dry it with a clean, soft cloth.
- Never use alcohol or any product containing solvents.
- Do not immerse the unit in water.
NEVER USE THE DEVICE WITHOUT THE AIR FILTER
STORAGE
When the unit is inactive for an extended period of time, please make sure you follow the instructions below, for the appropriate storage of your appliance:
- Turn unit off allowing one day before storage.
- Remove the drain hose (if attached).
- Clean the removable parts of the device, water tank, and air filter.
- Position and secure the power cord with its band opposite the dehumidifier.
- Cover the device.
- Store the dehumidifier in an upright position, in a dry, well-ventilated area, and avoid direct sunlight.
FREQUENTLY ASKED QUESTIONS & TROUBLESHOOTING
Are dehumidifiers costly?| For about the first month of use, the dehumidifier
operates intensively. This will gradually decrease over time since the
dehumidifier will have been calibrated in its working environment. Condensed
households may sometime be significantly expensive to heat. The use of a
dehumidifier may lower energy costs.
---|---
Where should the dehumidifier be placed ideally?| For optimal results, it is
suggested that the dehumidifier is placed in a central area. Doors within the
household should be open in order for the dehumidifier to enhance its
operation.
Can the filter be replaced by another type of filter?| The dehumidifier’s
filter cannot be replaced by any other type of filter since it is specifically
designed to operate with this unit.
Which is the appropriate room humidity level?| Maintaining a proper home
humidity level is essential for your well-being and that of your household.
Extreme fluctuations cause adverse effects on both; low humidity may cause
respiratory problems and damage to wooden doors, windows, and furniture, and
make you vulnerable to electric shocks due to increased static electricity. On
the other hand, high humidity may promote mold growth, serving as breeding
grounds for various bacteria and resulting in poor health and also a damaged
home. The ideal humidity levels fluctuate between 40% to 50%.
Why does condensation persist on
windows even with the dehumidifier’s use?| When the desired humidity level is
reached, there is a possibility of partial humidity formation on windows. This
occurs due to the temperature variation between the window and the external
weather conditions.
• Operating the dehumidifier should significantly reduce condensation
formation on windows.
How much time is needed to dry my clothes?| The exact time needed to dry
clothes depends on many factors, the room’s temperature, the humidity level,
the moisture of the clothes, etc., so there is no standard time for these
variable factors mentioned above.
Why does the dehumidifier not operate while the humidity of the room has
increased?| When the set humidity is reached, the Energy Savings function is
automatically activated during which the digital control display of the device
may show increased humidity levels. This is because the fan is not operating.
After the predetermined timeframe and if the humidity levels have increased,
the device will resume dehumidification.
The dehumidifier is not a chilling device. What could be the cause of cold air
being extracted?| The dehumidifier operates by intaking condensed air removing
any moisture and sending it back to the area it operates. If you are standing
near the dehumidifier while operating you may feel that the air coming out of
the fan is cooler due to the diffusion. In reality, it is at the same room
temperature but with less humidity.
The unit does not start
- Make sure the dehumidifier’s plug is placed completely into the socket.
- Check the house fuse/circuit breaker box.
- Check whether the power cord is damaged.
- Check the water tank, if it is full, empty it.
- Check if the dehumidifier has reached its preset level.
- Make sure the water tank is positioned properly.
- Room temperature is lower or higher than the advised operational range.
- Check whether the humidity level has been set at high levels.
A dehumidifier does not dry the air as efficient
- Make sure that the dehumidifier has been operating for enough time to remove the moisture.
- Make sure there are no curtains, blinds, or furniture blocking the front or back of the dehumidifier.
- The humidity selector may not be set low enough.
- Make sure you have cleaned the filter as suggested. A clogged filter may result in reduced performance.
- All house exits (windows doors etc) where the dehumidifier is operating, should be shut.
- The room temperature is below the advised operational range.
- There is a kerosene heater or something giving off water vapor in the room.
- The room where the device is placed is bigger than suggested.
- The humidity level is too high.
The unit makes a loud noise when operating
- The air filter is clogged.
- The device is tilted instead of being in an upright position.
- The floor surface is not flat.
Frost build-up on coils
- This is normal. This unit is supplied with an Auto defrost feature.
Drain hose water leakage
- Check the correct installation of the drain hose.
- Check for any blockage or damage to the drain hose.
Understanding Error code indications
EH60-Humidity sensor error- Unplug the unit and plug it back in. If the error
repeats, call for service;
EH61-Tube Temperature sensor of the evaporator error– Unplug the unit and plug
it back in. If the error repeats, call for service;
EH02-Zero-crossing signal detection error; If error repeats, call for service;
EH03-Indoor fan speed malfunction; If error repeats, call for service;
EH0b-Indoor PCB and display board communication error; If error repeats, call
for service;
All the pictures in the manual are for explanatory purposes only. The actual
shape of the unit you purchased may be slightly different, but the operations
and functions are the same.
The company may not be held responsible for any misprinted information. The
design and the specifications of the product for reasons, such as product
improvement, are subject to change without any prior notice.
Please consult with the manufacturer at +30 211 300 3300 or with the Sales
agency for further details. Any future updates to the manual will be uploaded
to the service website, and it is advised to always check for the latest
version.
Scan here to download the latest version of this manual.
www.inventorappliances.com/manuals
Activate your Warranty
Follow the next quick steps to activate your warranty:
STEP 1
Visit our website via the link:
https://www.inventorappliances.com/warranty- card or by scanning the QR code, as follows:
STEP 2
Fill in the obligatory fields as requested in the “Owner’s details” and
“Unit’s details”:
STEP 3
Click SEND button at the end of the submission form:
STEP 4
Wait for the confirmation email you will receive at the email address you have
filled in – please also check your spam folder.
STEP 5
The inventor warranty is now valid!
DEHUMIDIFIER V:1.3.092022
Manufacturer: INVENTOR A.G. S.A.
24th km National Road Athens – Lamia & 2 Thoukididou Str., Ag.Stefanos, 14565
Tel.: +30 211 300 3300,
Fax: +30 211 300 3333 –
www.inventor.ac
References
- Κλιματιστικά Inverter WiFi, Ψυγεία, Αφυγραντήρες, Air Conditioners - Inventor
- Biblioteca media - Inventor
- Αρχεία και Υποστήριξη - Inventor
- Inventor Appliances User Manuals - Inventor appliances
- Inventor
- 10 χρόνια εγγύηση κλιματιστικών Inventor - Inventor
- Inventor
- 2 Year Warranty Card Registration - Inventor appliances
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>