DIGTUS Professional DN-93603 Keystone Jack Instruction Manual

June 13, 2024
DIGTUS Professional

DIGTUS Professional DN-93603 Keystone Jack

DIMENSION

DIGITUS-Professional-DN-93603-Keystone-Jack-fig-1

ASSEMBLY INSTRUCTION

KEYSTONE MODULE (SHIELDED & UNSHIELDED)

Step 1:

S/FTP: REMOVE THE CABLE JACKET
Strip approximately 40 mm of the cable jacket and separate the wires into 4 pairs.

U/UTP: REMOVE THE CABLE JACKET
Strip approximately 40 mm of the cable jacket, cut off the plastic cross and separate the wires into 4 pairs.DIGITUS-Professional-DN-93603-Keystone-Jack-
fig-2

Step 2: WIRING CONFIGURATION
Insert the wires through the wire manager and lay them into the correct slots, according to the wiring diagram on the wire manager.DIGITUS-Professional-
DN-93603-Keystone-Jack-fig-3

Step 3: TRIM WIRES
Trim the wires flush with the wire manager. It is strongly recommended that the tip of the wires protrude max. 0.15 – 0.20 mm.DIGITUS-Professional-
DN-93603-Keystone-Jack-fig-4

Step 4: WIRE INJECTION
The numbers help you to find the right way to insert the wire manager onto the IDC. Press the wire manager down onto the IDC.DIGITUS-Professional-DN-93603
-Keystone-Jack-fig-5

Step 5: LOCKING
Close the outer cap by pushing down both sides until it clicks.DIGITUS-
Professional-DN-93603-Keystone-Jack-fig-6

Step 6: S/FTP: GROUNDING, STRAIN RELIEF
Connect the drain wire/braid shield to the shielded shell housing and tie up the cable tie and finish.

U/UTP: STRAIN RELIEF
Tie up the cable tie and finish.