DUAL LITE OCR-03L LED Outdoor Emergency Remote Light Fixture Instruction Manual
- June 4, 2024
- DUAL LITE
Table of Contents
DUAL LITE OCR-03L LED Outdoor Emergency Remote Light Fixture
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
- Do not let power supply cords touch hot surfaces.
- Do not mount near gas or electric heaters.
- Equipment should be mounted in locations and at heights where it will not readily be subject to tampering by unauthorized personnel.
- The use of accessory equipment not authorized by the manufacturer may cause an unsafe condition.
- Do not use this equipment for other than its intended purpose.
- Servicing of this equipment should be performed by qualified service personnel.
- Test cycling: the Life Safety Code (NFPA 101) requires testing of emergency lighting units once a month for a minimum of 30 seconds, and once a year for a minimum of 90 minutes.
INSTALLER:
- SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS
- SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT
WARNING: This product contains chemicals known to the State of California to cause cancer, birth defects and/or other reproductive harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise touching this product.
REPLACEMENT HEAD INSTALLATION
Step 3
Remove the cotter pin from the new lamp head. Screw in the new lamp head.
Step 4
Connect the red and black wires. Insert the cotter pin back in the screw head.
FIXTURE INSTALLATION
NOTE: The OCR-03L fixture can be wall mounted or ceiling mounted at a height of 7ft to 10ft. The LED lamps can be adjusted to desired position. The lamp heads can be locked in desired posisiton using the lock nut and screw.
Configuring the number of OCR remotes requires the calculation of total wattage capacity based on the capacity of the fixture powering the remotes.
OCR-03L wattage for calculation:
- OCRSB-03L = 3W
- OCRSW-03L = 3W
- OCRSZ-03L = 3W
- OCRDB-03L = 6W
- OCRDW-03L = 6W
- OCRDZ-03L = 6W
SERVICE/MAINTENANCE
Replacing LED Lamps
The LED lamps inside the unit are not replaceable or field serviceable. Please
see dual-lite.com for further assistance.
Troubleshooting
The emergency circuit does not work
- Check wiring connections
RECYCLING INFORMATION
All steel, aluminum, and thermoplastic parts are recyclable.
NOTICE: Emergency units contain rechargeable batteries which must be
recycled or disposed of properly.
Address:
**** Hubbell Lighting, Inc. Life Safety Products
- www.dual-lite.com Copyright©Hubbell Lighting, Inc., All Rights Reserved
- Specifications are subject to change without notice.
- Printed in the U.S.A.