RFC BS 5EN Suspended Speaker In Compliance User Manual

June 15, 2024
RFC

RFC BS 5EN Suspended Speaker In Compliance

Product Information

Specifications

  • Model: BS 5EN
  • Compliance : EN 54-24 standard

Description

The BS 5EN is a suspended speaker designed for installation in compliance with the EN 54-24 standard. It provides high-qualityaudio output for various applications.

Connection

Before connecting the speaker, please ensure that the power is turned off and follow these steps:

  1. Identify the amplifier outputs that will be connected to the loudspeaker lines.
  2. Ensure that the loudspeaker input voltage matches the amplifier output.
  3. Make sure all connections are made correctly and securely.

Installation

To install the BS 5EN suspended speaker, please follow these steps:

  1. Select a suitable location for installation, considering factors such as sound coverage and acoustic requirements.
  2. Ensure that the speaker lines are protected from damage and positioned in a way that they cannot be stepped on or crushed by objects.
  3. Mount the speaker securely using appropriate mounting hardware.
  4. Connect the loudspeaker lines to the amplifier outputs, ensuring correct polarity.

Notes about Constant Voltage Systems

If you are using a constant voltage system, please take note of the following:

  • Ensure that the loudspeaker input voltage is compatible with the constant voltage system.
  • Follow the manufacturer’s instructions for setting up and configuring the constant voltage system.

FAQ

Q: Can I install the BS 5EN speaker myself?

A : RCF S.P.A. strongly recommends that the product is only installed by professional qualified installers or specialized firms who can ensure correct installation and compliance with regulations.

Q: What factors should be considered when installing a professional audio system?

A : In addition to acoustic considerations, mechanical and electrical factors need to be taken into account. This includes sound pressure, angles of coverage, frequency response, and compliance with electrical system regulations.

Q: Why is it important to respect the loudspeaker phase?

A : Respecting the loudspeaker phase ensures correct sound reproduction, especially when multiple loudspeakers are installed adjacent to each other in the same room.

SAFETY AND OPERATING PRECAUTIONS

IMPORTANT NOTES

Before connecting and using this product, please read this instruction manual carefully and keep it on hand for future reference. This manual is to be considered an integral part of this product and must accompany it when it changes ownership as a reference for correct installation and use as well as for the safety precautions.

RCF S.p.A. will not assume any responsibility for the incorrect installation and /
or use of this product.

  1. All the precautions, in particular the safety ones, must be read with special attention, as they provide important information.
  2. Loudspeaker lines (amplifier outputs) can have a sufficiently high voltage (i.e. 100-70 V) to involve a risk of electrocution: never install or connect this loudspeaker when the line is alive.
  3. Make sure all connections have been made correctly and the loudspeaker input voltage is suitable for the amplifier output.
  4. Protect loudspeaker lines from damage. Make sure they are positioned in a way that they cannot be stepped on or crushed by objects.
  5. Make sure that no objects or liquids can get into this product, as this may cause a short circuit.
  6. Never attempt to carry out any operations, modifications or repairs that are not expressly described in this manual. Contact your authorized service center or qualified personnel should any of the following occur:
    • — The loudspeaker does not function (or works in an anomalous way).
    • — The cable has been damaged.
    • — Objects or liquids have got into the unit.
    • — The loudspeaker has been damaged due to heavy impacts or fire.
  7. Should the loudspeaker emit any strange odors or smoke, remove it from the line after having immediately switched the amplifier off.
  8. Do not connect this product to any equipment or accessories not foreseen. For suspended installation, only use the dedicated anchoring points, and do not try to hang this loudspeaker by using elements that are unsuitable or not specific for this purpose. Also check the suitability of the support surface to which the product is anchored (wall, ceiling, structure, etc.) and the components used for attachment (i.e. wallplugs, screws, brackets not supplied by RCF, etc.), which must guarantee the security of the system/installation over time, also considering, for example, the mechanical vibrations normally generated by transducers.
  9. RCF S.P.A. strongly recommends this product is only installed by professionally qualified installers (or specialized firms) who can ensure a correct installation and certify it according to the regulations in force. The entire audio system must comply with the current standards and regulations regarding electrical systems.
  10. Mechanical and electrical factors need to be considered when installing a professional audio system (in addition to those that are strictly acoustic, such as sound pressure, angles of coverage, frequency response, etc.).
  11. Hearing loss Exposure to high sound levels can cause permanent hearing loss. The acoustic pressure level that leads to hearing loss is different from person to person and depends on the duration of exposure. To prevent potentially dangerous exposure to high levels of acoustic pressure, anyone who is exposed to these levels should use adequate protection devices. When a transducer capable of producing high sound levels is being used, it is necessary to wear earplugs or protective earphones. See the technical specifications in the instruction manual for the maximum sound pressure the loudspeaker is capable of producing.
  12. To ensure correct sound reproduction, the loudspeaker phase is to be respected (loudspeakers are connected respecting the amplifier polarity). This is important when loudspeakers are installed adjacent one another, for instance, in the same room. Make sure loudspeaker lines are not shorted before turning the amplifier on.
  13. To prevent inductive effects from causing hum, noise, and a bad system working, loudspeaker lines should not be laid together with other electric cables (mains), microphone or line level signal cables connected to amplifier inputs.
  14. The loudspeaker cable shall have wires with a suitable section (twisted, if possible, to reduce inductive effects due to surrounding electromagnetic fields) and sufficient electrical insulation. Refer to local regulations, as there may be additional requirements about cable characteristics.
  15. Install this loudspeaker far from any heat source.
  16. Do not use solvents, alcohol, benzene or other volatile substances for cleaning the external parts of this product. Use a dry cloth.

RCF S.P.A. THANKS YOU FOR PURCHASING THIS PRODUCT, WHICH HAS BEEN DESIGNED TO GUARANTEE RELIABILITY AND HIGH PERFORMANCE.

BS 5EN is a 20 W weatherproof suspended speaker in compliance with EN 54-24 standard.

Main features:

  •  ABS cabinet with steel mesh grille.
  • It can be installed both indoors and outdoors (IP 65 protection grade).
  • Equipped with transformer for 100 V (/ 70 V) constant voltage lines.
  • Internal power setting.
  • Ceramic screw terminal for connection.
  • Internal thermal fuse.
  • Color : white.

WARNING : loudspeaker connections should be only made by qualified and experienced personnel having the technical know-how or sufficient specific instructions to ensure that connections are made correctly and to prevent any electrical danger.
To prevent any risk of electric shock, do not connect loudspeakers when the amplifier is switched on. Before turning the system on, check all connections and make sure there are no accidental short circuits. The entire sound system shall be designed and installed in compliance with the current local laws and regulations regarding electrical systems.

Connect the 100 (/ 70) V line through the ceramic terminal block.

RFC-BS-5EN-Suspended-Speaker-In-Compliance-fig1

  1. Select the power rate by connecting only one of the four wires (coming out from the transformer primary winding) to the central screw of the ceramic terminal strip:
    • 20 W, red wire
    • 10 W, blue wire
    • 5 W, yellow wire
    • 2.5 W, white wire
    • The 3 unused wires must be insulated (e.g. with tape).
    • The black wire is common and is always linked to the transformer’s primary winding.
    • If connecting to a 70 V line, the power will be halved (red: 10 W, blue: 5 W, yellow: 2.5 W, white: 1.25 W)
  2. Insert the connecting cable either behind (if installed into the ceiling) and through the mounting plate or through a hole on its cover (if external).
  3. After placing the ceramic terminal strip outside the mounting plate (see the next manual section ‘Installation’), connect the positive wire of the 100 (/ 70 V) line to the loudspeaker + input.
  4. Connect the negative wire of the 100 (/ 70 V) line to the loudspeaker 0 input.RFC-BS-5EN-Suspended-Speaker-In-Compliance-fig2
  5. Connect the earth wire to the screw of the mounting plate and the loudspeaker green wire.

WARNING: Make sure that the loudspeaker is installed in a stable and secure way in order to avoid any conditions that may be dangerous for persons or structures. Ensure the support surface (the wall) has the necessary mechanical characteristics to support the loudspeaker weight. Before installing the loudspeaker, carefully check all components to be used and make sure there is no damage, deformation, corrosion and/or missing or damaged parts that could reduce the safety of the installation. BS 5EN suspended speakers can be installed both indoors and outdoors.

RFC-BS-5EN-Suspended-Speaker-In-Compliance-fig3

  1. Fix the mounting plate to the ceiling with suitable wall plugs (with 4.5 mm screw).
  2. Connect the loudspeaker green wire to the mounting plate earth screw.RFC-BS-5EN-Suspended-Speaker-In-Compliance-fig4RFC-BS-5EN-Suspended-Speaker-In-Compliance-fig5
  3.  Insert the support into the mounting plate, so that it is positioned at its centre. Keep the ceramic terminal strip outside of the mounting plate and tighten the support nut to fix the loudspeaker to the ceiling.
  4. Connect the loudspeaker as described in the previous manual section ‘Connection’. Move the cover to the ceiling (to hide the mounting plate) and fix it by tightening its nut.

NOTES ABOUT CONSTANT VOLTAGE SYSTEMS

RFC-BS-5EN-Suspended-Speaker-In-Compliance-fig7

  • The loudspeaker input voltage (Vd) shall correspond to the amplifier output voltage (Va).
  • The sum of nominal power values (Pd x n) of all loudspeakers connected to the line shall not exceed the amplifier power (Pa).
  • Make sure all loudspeakers are connected in phase to ensure a correct sound reproduction.
  • Always use cables having wires with an adequate cross-section, considering the cable length and the total loudspeaker power.
  • Loudspeaker lines must be kept separated from mains cable, microphone cables or others, in order to avoid inductive phenomena may cause hum or noises.
  • Use loudspeaker cables having twisted wires to reduce the hum caused by inductive effects due to coupling with electromagnetic fields.

SPECIFICATIONS

  • Input voltage: 100 V
  • Power (selectable): 20 W – 10 W – 5 W – 2.5 W (100 V)
  • Input impedance : 20 W – 10 W – 5 W – 2.5 W (100 V)
  • Frequency response (–10 dB): 100 Hz ÷ 20 kHz
  • Sensitivity (±3 dB, 1 kHz): dB (1 W, 1 m), 76 dB (1 W, 4m)
  • Max. sound pressure level : 101 dB (20 W, 1 m), 89 dB (20 W, 4 m)
  • Cabinet material:ABS
  • Grille: steel
  • Color: white
  • Connection: ceramic screw terminals
  • IP protection grade : IP 65
  • Dimensions (without bracket): ø 180 mm, depth: 260 mm

More Information

  • RCF S.p.A. – Via Raffaello Sanzio 13, 42124 Reggio Emilia, ITALY 14
  • 0068-CPR-058/2014
  • EN 54-24:2008

Loudspeaker for voice alarm systems for fire detection and fire alarm systems for buildings

  • BS 5EN
  • Type B
  • DoP: 008_14

Other technical data: see operational manual.

All EN54-24:2008 standard requirements are verified in the RCF S.p.A. manufacturing plant site in Via Raffaello Sanzio 13, 42124 Reggio Emilia, ITALY.

The Declaration of Performance is available on the RCF website (www.rcf.it), in the DOWNLOADS section of the product page.