renatta RS-N01-2D-LCD Industrial Wall Mounted LCD Temperature and Humidity Transmitter User Manual

June 12, 2024
renatta

renatta RS-N01-2D-LCD Industrial Wall Mounted LCD Temperature and

Humidity Transmitter

renatta-RS-N01-2D-LCD-Industrial-Wall-Mounted-LCD-Temperature-and-Humidity-
Transmitter-product-image

Product Information

The Industrial Wall-mounted LCD Temperature and Humidity Transmitter (Model 485) is a high-quality industrial-grade device designed for accurate temperature and humidity measurement. It features a high-protection grade enclosure with an IP65 rating, making it resistant to rain, snow, and dust. The product utilizes American imported industrial-grade microprocessor chips and high-precision temperature and humidity sensors, ensuring reliable performance and precise measurements. It supports RS485 output signal type with a communication range of up to 2000 meters and follows the standard Modbus protocol, allowing for easy integration and secondary development.

Key Features:

  • High-precision temperature and humidity measurement unit for long-term stability
  • Dedicated 485 circuit with standard ModBus-RTU communication protocol
  • Wide voltage range power supply (10~30V)
  • Easy installation with wall-mount or rail-mount options
  • High anti-dust protection level (IP65)
  • LCD liquid crystal display for clear visibility
  • Parameter setting buttons for easy operation

Main Technical Parameters:

  • DC power supply: 10-30V
  • Maximum power consumption: 0.4W
  • Precision humidity measurement range: -20~+60°C, 0~95%RH (Non-condensing)
  • Precision temperature measurement range: -40~+120°C
  • Transmitter circuit operating temperature and humidity range: 0%RH-100%RH
  • Probe working temperature range: -40~+80°C
  • Modbus-RTU communication protocol
  • Temperature display resolution: 0.1°C
  • Humidity display resolution: 0.1%RH
  • Temperature and humidity refresh time: 8s (1m/s Wind speed)
  • Response time: 25s (1m/s Wind speed)

Product Usage Instructions

Equipment Installation Instructions
Inspection before Equipment Installation
Before installing the equipment, ensure that you have the following:

  • 1 set of temperature and humidity transmitter equipment
  • Certificate of conformity, warranty card, calibration report, etc.
  • 2 expansion plugs and 2 self-tapping screws
  • USB to 485 cable (optional)
  • 485 terminal resistance (provided for multiple devices)

Installation Method – Wall Mount

  1. Remove the slide rail mounting plate from the back of the transmitter.
  2. Using a drill, create two holes on the wall with a diameter of 5mm and a depth of 30mm. The spacing between the holes should be 70mm.
  3. Insert the expansion plugs into the holes.
  4. Fix the slide rail mounting plate to the wall using the self-tapping screws.
  5. Slide the transmitter into the mounted slide rail.

Product description

The product is an industrial wall-mounted high-protection grade enclosure, with a protection grade
of IP65, rain and snow proof and good air permeability. The circuit adopts American imported industrial grade microprocessor chips and imported high- precision temperature and humidity sensors to ensure excellent product reliability, high precision and interchangeability. The output signal type is RS485,
the farthest can communicate 2000 meters, the standard modbus protocol, supports secondary development.

Features

  1. Using high-precision temperature and humidity measurement unit, long-term stability and small drift
  2. Using dedicated 485 circuit, standard ModBus-RTU communication protocol, communication address and baud rate can be set
  3. 10~30V wide voltage range power supply
  4. Easy to install, can be wall-mounted or rail-mounted
  5. High anti-dust protection level (IP65)
  6. LCD liquid crystal display, beautiful and generous
  7. Buttons can set parameters, easy to operate

The main technical parameters

DC power supply (default) DC 10-30V

Maximum power

consumption

| 0.4W
A precision| humidity| ±2%RH(60%RH,25℃)
temperature| ±0.4℃(25℃)


B quasi-accuracy

| humidity| ±3%RH(60%RH,25℃)
temperature| ±0.5℃(25℃)
(default)| -20℃~+60℃,0%RH~95%RH(Non-condensing)
| -40℃~+120℃ default:-40℃~+80℃
Transmitter circuit operating temperature and humidity| 0%RH-100%RH
Probe working temperature| Modbus-RTU letter of agreement
Probe working humidity| 485 Signal
letter of agreement| 0.1℃
output signal| 0.1%RH
Temperature display resolution| 1s
Humidity display resolution| 70mm
Temperature and humidity refresh time| humidity| ≤1%RH/y
temperature| ≤0.1℃/y
Response time| humidity| ≤8s(1m/s Wind speed)
temperature| ≤25s(1m/s Wind speed)
parameter settings| Direct modification through software settings or buttons

Equipment size

System framework

renatta-RS-N01-2D-LCD-Industrial-Wall-Mounted-LCD-Temperature-and-Humidity-
Transmitter-2

Product model

RS- Company code
WS- Temperature and humidity transmission, sensor
N01- 485 communication (Modbus-RTU protocol)
2D-LCD Industrial wall hanging (liquid crystal display)

Equipment installation instructions
Inspection before equipment installation

Equipment List:

  1. 1 set of temperature and humidity transmitter equipment
  2. Certificate of conformity, warranty card, calibration report, etc.
  3. 2 expansion plugs, 2 self-tapping screws
  4. USB to 485 (optional)
  5. 485 terminal resistance (gift for multiple devices)

Installation method
Wall mount

The back of the transmitter is equipped with a slide rail mounting plate. Remove the mounting plate first.There are two expansion plugs and two self- tapping screws in the accessories. First, punch two holes with a diameter of 5mm and a depth of ≥30mm on the wall (the opening spacing is 70mm). After inserting the expansion plug, fix the slide rail mounting plate to the wall with self-tapping screws, and finally slide the transmitter into it.

Slide rail installation
The back of the transmitter is equipped with a slide rail mounting plate. Remove the mounting plate first. The transmitter can be slid directly into the standard 35 rail。

renatta-RS-N01-2D-LCD-Industrial-Wall-Mounted-LCD-Temperature-and-Humidity-
Transmitter-4

Special Note:

  1. There are certain specification requirements for 485 line field wiring. For details, please refer to the data package “485 Equipment Field Wiring Manual”.
  2. When the device is connected to the 485 bus, ensure that the addresses of multiple devices will not be repeated.

Wiring instructions.
Power and 485 signal
Wide-voltage power input can be 10~30V. When wiring the 485 signal line, pay attention to
the two wires A\B not to be reversed, and the addresses of multiple devices on the bus cannot be conflicted.

Specific wiring

| Circuit identification| illustrate
---|---|---
power supply| VCC| V+(10~30V DC)
GND| V-
Communication| 485A| 485-A
485B| 485-B

Panel display description

renatta-RS-N01-2D-LCD-Industrial-Wall-Mounted-LCD-Temperature-and-Humidity-
Transmitter-5

If the device address is less than 100, the decimal address is displayed at the display location of the device address; if the device address is greater than 100, the hexadecimal address is displayed at the display location of the device address.

Configuration software installation and use

Software selection
Open the data package, select “Debugging software” — “485 parameter configuration software”,

Note: When using the configuration software to change the address and baud rate, only one device can be connected.

renatta-RS-N01-2D-LCD-Industrial-Wall-Mounted-LCD-Temperature-and-Humidity-
Transmitter-6

(The device does not provide a communication line by default, the color of the line is for reference only)

Parameter settings

  1. Select the correct COM port (check the COM port in “My Computer — Properties —Device Manager—Port”). The following figure lists the driver names of several different 485 converters.
    renatta-RS-N01-2D-LCD-Industrial-Wall-Mounted-LCD-Temperature-and-Humidity-
Transmitter-7

  2. Connect only one device alone and power it on, click the test baud rate of the software, the software will test the baud rate and address of the current device, the default baud rate is 4800bit/s, and the default address is 0x01.

  3. Modify the address and baud rate according to the needs of use, and at the same time, you can query the current function status of the device.

  4. If the test is unsuccessful, please recheck the equipment wiring and 485 driver installation.

renatta-RS-N01-2D-LCD-Industrial-Wall-Mounted-LCD-Temperature-and-Humidity-
Transmitter-8

letter of agreement

Basic communication parameters

Code 8-bit binary
Data bit 8-bit
Parity bit without
Stop bit 1 person
Error checking CRC (Redundant Cyclic Code)
Baud rate 2400bit/s, 4800bit/s, 9600 bit/s can be set, the factory default is

4800bit/s

Data frame format definition
Using Modbus-RTU communication protocol, the format is as follows:
Initial structure ≥ 4 bytes of time
Address code = 1 byte
Function code = 1 byte
Data area = N bytes
Error check = 16-bit CRC code
Time to end structure ≥ 4 bytes
Address code: the address of the transmitter, which is unique in the communication network (factory default 0x01). Function code: The command function instruction issued by the host, this transmitter only uses function code 0x03 (read register data). Data area: The data area is the specific communication data, pay attention to the high byte of the 16bits data first! CRC code: two-byte check code.
Host query frame structure:

address co de| function co de| Register start ad dress| Register lengt h| Check code l ow bit| High bit of che ck code
---|---|---|---|---|---
1byte| 1byte| 2byte| 2byte| 1byte| 1byte

Slave response frame structure:

address c ode:| function code| Number of valid bytes| Data area| Second data area| Nth data area| Check code
---|---|---|---|---|---|---
1byte| 1byte| 1byte| 2byte| 2byte| 2byte| 2byte

Register address

Register address (Hexadecimal)| Register address (10 hex)| PLC or configuration address (10 hex)| content| operate
---|---|---|---|---
0000 H| 0| 40001| humidity (Expanded by 10 times the actual humidity)| Read only
0001 H| 1| 40002| temperature (Expanded by 10 times the actual temperature)| Read only
07D0H| 2000| 42001| Device address| Read and write
07D1H| 2001| 42002| Device baud rate| Read and write

Communication protocol example and explanation
Example: Read the temperature and humidity value of the device address 0x01 Inquiry frame (hexadecimal):

address code:| function code| initial address| Data length| Check code low b it| High bit of c heck cod e
---|---|---|---|---|---
0x01| 0x03| 0x00 0x00| 0x00 0x02| 0xC4| 0x0B

Response frame (hexadecimal): (for example, the temperature is -10.1℃ and the humidity is 65.8%RH)

address c ode:| function cod e| Returns the n umber of vali| Humidity value| Temperatur e value| Check code low bit| High bit of check c
---|---|---|---|---|---|---
| | d bytes| | | | ode
0x01| 0x03| 0x04| 0x02 0x92| 0xFF 0x9B| 0x5A| 0x3D

Temperature calculation:
When the temperature is lower than 0 ℃, the temperature data is uploaded in the form of complement code. Temperature: FF9B H (hexadecimal) = -101 => temperature = -10.1℃
Humidity calculation:
Humidity: 292 H (hexadecimal) = 658 => Humidity = 65.8%RH

Key operation instructions

  1. short according key ,Enter the password input interface interface, short according , . Password input is possible (default password is 888), Long press again after input key Enter the main interface of settings, the password error prompts ERR.
  2. After entering the setting main menu, short according or Page forward and backward, short according Enter the parameter setting interface。
  3. short according ,  , Modifiable parameters, Short press after parameter modification is completed ,The parameters are automatically saved.
  4. During the setting process, press Can abandon this setting, Press again Back to the main interface。

The specific parameter interface is as follows:

show interface illustrate Key operation

| Set the address of the device
Default value: 1 Range: 1~255| short according Address plus 1, long Press address +10;short according Address minus 1,long
Press Address minus10。short according key, Save the displayed address value as the target address。
| Set the baud rate of the device
Range: 2400/4800/9600 Default value: 4800| press The baud rate can be switched between 2400, 4800, 9600。short according key, Save the displayed baud rate value as the target baud rate.

| Set the temperature calibration value of the device
Range: -100.0~100.0
Default value: 0| short according+1, long Press+10;short according-1, long Press -10。short according key , Save the displayed temperature calibration value as the target temperature calibration value.

| Set the humidity calibration value of the device
Range: -100.0~100.0
Default value: 0| short press+1, long Press+10; short press-1, long Press-10。short press key ,Save the displayed humidity calibration value as the target humidity calibration value.
| Set device password| short press+1 ,long
| Range: 000~999| Press+10; short
| Default: 888| press-1, long
| | Press-10 。short
| | presskey, Save the
| | displayed password as the
| | target password

Common problems and solutions

The device cannot connect to the PLC or computer possible reason:

  1. The computer has multiple COM ports, and the selected port is incorrect
  2. The device address is wrong, or there are devices with duplicate addresses (the factory defaults are all 1).
  3. The baud rate, check method, data bit, stop bit are wrong.
  4. The 485 bus is disconnected, or the A and B wires are reversed
  5. If the number of equipment is too long or the wiring is too long, power supply should be nearby, add 485 booster, and add 120Ω terminal resistance at the same time.
  6. USB to 485 driver is not installed or damaged
  7. The equipment is damaged.

Renatta Control Technology

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>