The Operator Adapter SITEL is an installation accessory designed for I-T-E MAX-FLEXTM disconnects. It allows for the proper installation and operation of the disconnect switches and circuit breakers in Hoffman enclosures.

Product Parts List

Item No. Description Part No. Qty.
1 ADAPTER PLATE FOR FHON 27317001 1
2 PLATE GASKET 89109613 1
3 SCREW, 1/4-20X1/2 PAN HEAD 99401031 4
4 SLIDE ARM 27217001 1
5 SHOULDER COLLAR 27112001 1
6 SCREW, 1/4-20X7/8 HEX HEAD 99401081 1
7 LOCKWASHER, 1/4 SPRING 99401305 1
8 WASHER, FLAT 22101003 2
9 LOCKWASHER, 1/4 INTERNAL TEETH 99401300 2
10 NUT, 1/4-20 HEX 99401406 2
11 DOOR CATCH 23101002 1
12 SCREW, 10-32X3/8 PAN HEAD 99401007 2
13 LOCKWASHER, #10 INTERNAL TEETH 99401307 2
14 NYLON WASHER 26132003 4
15 INSTALLATION INSTRUCTIONS 89114667 1

Product Usage Instructions

Product Installation Steps

Step 1

Install the adapter plate (item 1) and plate gasket (item 2) on the inside of the enclosure, behind the rectangular opening provided. Make sure the gasket side with PSA is attached to the adapter plate. Secure in place with four screws (item 3) and four nylon washers (item 14).

Step 2

Assemble the I-T-E operating handle to the mounting plate installed in step 1. Omit the cap screw and lockwasher that fits into the bottom hole of the I-T-E operating handle.

Step 4

Attach the bottom of the slide arm to the offset arm of the lock release mechanism. Use two flat washers (item 8), two lockwashers (item 9), and two hex nuts (item 10). Do not tighten until parts are adjusted (see step 5B).

Step 5

The handle safety lock release mechanism is adjustable in two places. (A) Check the adjustment of the factory-installed roller bracket. The door latch should hit against the latch stop portion of the roller bracket when the door is closed and latched. Adjust up or down if necessary. The attached mechanism will then provide the necessary up-down motion required to operate the release mechanism in the I-T-E operating handle.

OPERATOR ADAPTER SITEL

  • For floor-mounted enclosures with the disconnect on the right flange.
  • For one- through six-door free-standing enclosures with the disconnect the the right flange.
  • For floor-mounted enclosures with the disconnect on the centerpost.

WARNING

  • The functions, fits and clearances of the installation described hereon are calculated from information supplied by the manufacturers of the equipment to be installed. Be certain to check the function, fits and clearances of all equipment both before and after installation to assure that it operates properly and safely and meets all applicable codes, standards and regulations.
  • In the event the completed installation does not function properly or fails to meet any such codes, standards or regulations, do not attempt to make alterations or operate the equipment. Report such facts immediately to:

Hoffman Customer Service

Parts List

  • Operator Adapter, Catalog Number SITEL, for I-T-E MAX-FLEX™ Disconnects
Item No. Description Part No. Qty.
1 ADAPTER PLATE FOR FHON 27317001 1
2 PLATE GASKET 89109613 1
3 SCREW, 1/4-20X1/2 PAN HEAD 99401031 4
4 SLIDE ARM 27217001 1
5 SHOULDER COLLAR 27112001 1
6 SCREW, 1/4-20X7/8 HEX HEAD 99401081 1
7 LOCKWASHER, 1/4 SPRING 99401305 1
8 WASHER, FLAT 22101003 2
9 LOCKWASHER, 1/4 INTERNAL TEETH 99401300 2
10 NUT, 1/4-20 HEX 99401406 2
11 DOOR CATCH 23101002 1
12 SCREW, 10-32X3/8 PAN HEAD 99401007 2
13 LOCKWASHER, #10 INTERNAL TEETH 99401307 2
14 NYLON WASHER 26132003 4
15 INSTALLATION INSTRUCTIONS 89114667 1

These parts are for the larger I-T-E flange handle (FHOHN), used only with large circuit breakers.

INTRODUCTION

This installation instruction is for I−T−E MAX−FLEX™ mechanisms. These mechanisms are for disconnect switches and circuit breakers mounted in Hoffman two door, floor−mounted and one through six door, free−standing enclosures with the disconnect on the right flange.

INSTALLATION STEPS

Step 1
Install adapter plate (item 1) and plate gasket (item 2) on the inside of the enclosure, behind the rectangular opening provided. Gasket side with PSA should be attached to the adapter plate. Secure in place with four screws (item 3) and four nylon washers (item14).
Step 2
Assemble the I−T−E operating handle to the mounting plate which was installed in the enclosure in step 1. Omit cap screw and lockwasher which fits into bottom hole of I−T−E operating handle.
Step 3
Install the slide arm (item 4) over the interlock lever part of the I−T−E operating handle, as shown. Note that the notch in the slide arm is positioned toward the door opening. Place the smaller diameter end of the shoulder collar (item 5) through the oval slot in the slide arm. Install long cap screw (item 6) with lockwasher (item 7) through shoulder collar into the bottom mounting hole of the I−T−E operating handle and tighten. The slide arm should move up and down smoothly. Install interlock lever extension per I−T−E instructions.
Step 4
Attach the bottom of the slide arm to the offset arm of the lock release mechanism. Use two flat washers (item 8), two lockwashers (item 9), and two hex nuts (item 10). Do not tighten until parts are adjusted (see step 5B).
Step 5
The handle safety lock release mechanism is adjustable in two places.

  • A Check the adjustment of the factory installed roller bracket. The door latch should hit against the latch stop portion of
    the roller bracket when the door is closed and latched. Adjust up or down if necessary. The attached mechanism will then provide the necessary up−down motion required to operate the release mechanism in the I−T−E operating handle.

  • B Adjust the length of the slide arm assembly. With proper adjustment of the slide arm, the safety lock (in I−T−E operating handle) should release just before the master door is fully latched. Lengthen slide arm if safety lock releases too soon. Shorten slide arm if safety lock releases too late.

Step 6
Attach the door catch (item 11), provided by Hoffman, to the tapped spacer on the door using the bottom set of mounting holes. Use two screws (item 12) and lockwashers (item 13). The door catch prevents the door from being opened when the I−T−E operating handle is in the “ON” position.
Step 7
Drill and tap holes in panel per I-T-E instructions. Disconnect can be located anywhere within reach of cable length being used. See I−T−E instructions.
Step 8
Install panel on collar studs in enclosure.
Step 9
Mount disconnect switch or circuit breaker and operating mechanism on panel using I−T−E instructions and parts.

For Two-Door, Floor-Mounted and One- Through Six-Door, Free-Standing Enclosures with Disconnect on Right Flange

HOFFMAN-SITEL-Operator-Adapter-fig-4

INTRODUCTION
This installation instruction is for I−T−E MAX−FLEX™ mechanisms. These mechanisms are for disconnect switches and circuit breakers mounted in Hoffman two door, floor−mounted enclosures with the disconnect on the centerpost.

INSTALLATION STEPS

Step 1
Install adapter plate (item 1) and plate gasket (item 2) on the inside of the enclosure, behind the rectangular opening provided in the centerpost. Gasket side with PSA should be attached to the adapter plate. Secure in place with four screws (item 3) and four nylon washers (item14).
Step 2
Assemble the I−T−E operating handle to the mounting plate which was installed in the enclosure in step 1. Omit cap screw and lockwasher which fits into bottom hole of I−T−E operating handle.
Step 3
Cut 2 1/2” off bottom end of slide arm (item 4) (bottom end has rectangular holes only).
Step 4
Install the slide arm (item 4) over the interlock lever part of the I−T−E operating handle, as shown. Place the smaller diameter end of the shoulder collar (item 5) through the oval slot in the slide arm. Note that the notch in the slide arm is positioned toward the door opening. Place the smaller diameter end of the shoulder collar (item 5) through the oval slot in the slide arm. Install long cap screw (item 6) with lockwasher (item 7) through shoulder collar into the bottom mounting hole of the I−T−E operating handle and tighten. The slide arm should move up and down smoothly. Install interlock lever extension per I−T−E instructions.
Step 5
Attach the bottom of the slide arm to the offset arm of the lock release mechanism. Use two flat washers (item 8), two lockwashers (item 9), and two hex nuts (item 10). Do not tighten until parts are adjusted.
Step 6
Adjust the length of the slide arm assembly. With proper adjustment of the slide arm, the safety lock (in I−T−E operating handle) should release just before the master door is fully latched. Lengthen slide arm if safety lock releases too soon. Shorten slide arm if safety lock releases too late.
Step 7
Attach the door catch (item 11), provided by Hoffman, to the tapped spacer on the door using the bottom set of mounting holes. Use two screws (item 12) and lockwashers (item 13). The door catch prevents the door from being opened when the I−T−E operating handle is in the “ON” position.
Step 8
Drill and tap holes in panel per I-T-E instructions. Disconnect can be located anywhere within reach of cable length being used. See I−T−E instructions.
Step 9
Install panel on collar studs in enclosure.
Step 10
Mount disconnect switch or circuit breaker and operating mechanism on panel using I−T−E instructions and parts.

  • For Two-Door, Floor-Mounted Enclosures with Disconnect on Centerpost

HOFFMAN-SITEL-Operator-Adapter-fig-5

© 2018 Hoffman Enclosures Inc. PH 763 422 2211 • nVent.com/HOFFMAN 89115505

Hoffman Customer Service

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Hoffman User Manuals

Related Manuals