Rheem R801V Endeavor Line Classic Series Gas Furnaces User Manual
- June 12, 2024
- Rheem
Table of Contents
- Rheem R801V Endeavor Line Classic Series Gas Furnaces
- Features and Benefits
- Gas Furnaces
- Physical Data and Specifications—Upflow Models
- Upflow Application
- Dimensional Data: Upflow Model
- For High Altitudes
- OPERATIONAL FEATURES
- GENERAL TERMS OF LIMITED WARRANTY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Rheem R801V Endeavor Line Classic Series Gas Furnaces
R801V
- 80% A.F.U.E.†
- EcoNet® Enabled
- Heating Stages: Single Stage
- Motor Type: Constant CFM
- Input Rates: 50-125 kBTU [14.65-36.63 kW]
- Configuration Options: Upflow/Horizontal
Features and Benefits
- PlusOne® Diagnostics: With the Rheem Contractor & Econet Apps, built-in EcoNet & Bluetooth technology makes monitoring, troubleshooting and repairing the product easier than ever before
- Dip Switch Free Installation Commissioning via Bluetooth Technology: Seamless final install step without DIP switch configuration using the Rheem Contractor App
- PlusOne® Ignition System: Proven Direct Spark Ignition (DSI) for reliability and longevity
- Constant CFM Motor: Truly variable speed technology allows for ultimate humidity control, quieter sound levels and year-round energy savings.
- Quieter Operation1: A fully insulated blower cabinet, solid bottom, and truly variable speed airflow technology make this furnace one of the quieter options available
- EcoNet® Enabled Furnace: The latest in sensor technology and the EcoNet monitoring system provides a new level of protection, control, and energy savings
- Allows on-the-go control and receipt of system alerts by the homeowner via the EcoNet Smart Thermostat and Econet App2
- Based on the manufacturer’s furnace offering, and the product’s heating stages, motor type, and cabinet insulation. Sound levels are also dependent on furnace location and installation.
- Wifi broadband internet connection is required. Download the EcoNet® App from the App Store® or Google Play® to set up your EcoNet Smart Thermostat. Receipt of notifications depend on home WiFi set up. Amazon, Alex and all related logos are trademarks of Amazon.com, Inc. or its affiliates.
Gas Furnaces
Designates Metric Conversions
AVAILABLE MODELS
R801V0503A14UHSCAP
R801V0754A17UHSCAP
R801V0755A21UHSCAP
R801V1005A21UHSCAP
R801V1255A24UHSCAP
R801V0503A14UHNCAP
R801V0754A17UHNCAP
R801V0755A21UHNCAP
R801V1005A21UHNCAP
R801V1255A24UHNCAP
STANDARD EQUIPMENT
Solid state time on/off blower control
Limit controls
Manual shut-off valve
100% safety lockout
Adjustable cool fan off delay
One-hour automatic retry
Power and self-test diagnostics
The flame sense current diagnostics
Twinning (built-in) features
Low-speed continuous fan option
Single speed heating
Two-speed cooling
Transformer
Direct drive motor
PWM-controlled constant torque electrically commutated blower motor
Solid bottom
NOTE: A thermostat is not included as standard equipment.
WARNING
THIS FURNACE IS NOT APPROVED OR RECOMMENDED FOR USE IN MOBILE HOMES.
Physical Data and Specifications—Upflow Models
MODEL NUMBERS R801V 1stg VS-CT UP/HZ SERIES| R801V
0503A14UHCAP| R801V 0754A17UHCAP| R801V 0755A21UHCAP|
R801V 1005A21UHCAP| R801V *1255A24UHCAP**
---|---|---|---|---|---
Input-BTU/Hr [kW]| 50,000 [15]| 75,000 [22]| 75,000 [22]| 100,000 [29]|
125,000 [37]
Heating Capacity BTU/Hr [kW] ®| 40,000 [12]| 60,000 [18]| 60,000 [18]| 80,000
[23]| 100,000 [29]
Heat Ext. Static Pressure [kPa]| .18 [.05]| .20 [.05]| .20 [.05]| .28 [.07]|
.28 [.07]
Blower (D x W) [mm]| 11 x 6 [279 x 152]| 11 x 7
[279 x 178]| 11 x 7 [279 x 178]| 11 x 10 [279 x 254]| 11 x 10 [279 x 254]
Motor H.P. [W] Type| 1/2 [373] VS-CT(ECM)| 3/4 [560] VS-CT(ECM)| 1 [746] VS-
CT(ECM)| 3/4 [560] VS-CT(ECM)| 3/4 [560] VS-CT(ECM)
Min. Circuit Ampacity| 9| 13| 13| 13| 13
Min. Overload Protection Device| 15| 15| 15| 15| 15
Max. Overload Protection Device| 15| 20| 20| 20| 20
Motor Full Load Amps| 5.8| 5.8| 11.1| 8.8| 8.8
Heating CFM [L/s]| 960 [453]| 1450 [684]| 1375 [649]| 1380 [651]| 1900 [897]
MAX Cooling CFM [L/s]| 1240 [585]| 1650 [779]| 1980 [934]| 1980 [934]| 1980
[934]
MIN Cooling CFM [L/s]| 300 [142]| 500 [236]| 500 [236]| 500 [236]| 500 [236]
Fan CFM [L/s]| 600 [283]| 800 [378]| 1000 [472]| 1000 [472]| 1000 [472]
Max. E.S.P. (In. W.C.) [kPa]| 1.0 [0.25]| 1.0 [0.25]| 1.0 [0.25]| 1.0 [0.25]|
1.0 [0.25]
Temperature Rise Range °F [°C]| 25-55 [13.9-30.6]| 25-55 [13.9-30.6]| 25-55
[13.9-30.6]| 35-65 [19.4-36.1]| 35-65 [19.4-36.1]
Approx. Shipping Weight (Lbs.) [kg]| 110 [50]| 125 [57]| 140 [64]| 140 [64]|
150 [68]
AFUE ©| 80.0%| 80.0%| 80.0%| 80.0%| 80.0%
NOTES: All models are 115V, 60HZ, 1 Ph. Gas connection size for all models is 1/2″ [12 mm] N.P.T.
- In accordance with D.O.E. test procedures.
- See Conversion Kit Index Form for high altitude derate.
- S=Standard, N=Low NOx
This furnace does not meet air district requirements of 14 ng/J NOx emissions
limit. This furnace is not eligible for the Clean Air Furnace Rebate
Program:
www.CleanAirFurnaceRebate.com.
This furnace is to be installed for propane firing only in air districts
requiring 14 ng/J NOx emission limits. Operating in natural gas mode is in
violation of these Rules.
Upflow Application
Dimensional Data: Upflow Model
MODEL R801V-| ****
A
| ****
B
| ****
C
| ****
D
| ****
E
| ****
F
| MINIMUM CLEARANCE (IN.) [mm]| SHIP WGTS. (LBS.) [kg]
---|---|---|---|---|---|---|---|---
LEFT SIDE| RIGHT SIDE| BACK| TOP| FRONT|
VENT
050| 14| [356]| 1227/32 [326]| 105/8 [270]| | 111/2 [292]| 17/8 [48]| 0| 4
[102] CV| 0| 1 [25]| 3 [76]| 6 [152] @| 110 [50]
075417| 171/2 [445]| 1611/32 [415]| 123/8 [314]| | 15| [381]| 21/2 [64]| 0|
3| [76] CV| 0| 1 [25]| 3 [76]| 6 [152] @| 125 [57]
075421/100| 21| [533]| 1927/32 [504]| 141/8 [359]| | 181/2 [470]| 21/2 [64]|
0| 0| 0| 1 [25]| 3 [76]| 6 [152] @| 140 [64]
125| 241/2 [622]| 2311/32 [593]| 157/8 [403]| | 22| [559]| 21/2 [64]| 0| 0|
0| 1 [25]| 3 [76]| 6 [152] @| 150 [68]
NOTES
- May require a 3” [76 mm] to 4” [102 mm] or 3” [76 mm] to 5” [127 mm] adapter.
- May be 0” [0 mm] with a type B vent.
- May be 1” [25 mm] with a type B vent.
Furnaces must be vented in accordance with the National Fuel Gas Code, ANSI Z223.1 and in accordance with local codes.
Horizontal Application
WARNING
THIS FURNACE IS NOT APPROVED OR RECOMMENDED FOR INSTALLATION ON ITS BACK, WITH
ACCESS DOORS FACING UPWARDS.
Dimensional Data: Horizontal Model
MODEL R801V-| ****
A
| ****
B
| ****
C
| ****
D
| ****
E
| ****
F
| MINIMUM CLEARANCE (IN.) [mm]| SHIP WGTS. (LBS.) [kg]
---|---|---|---|---|---|---|---|---
SUPPLY AIR SIDE| RETURN AIR SIDE| BACK| TOP|
FRONT| VENT
050| 14| [356]| 1227/32 [326]| 105/8 [270]| C| 111/2 [292]| 17/8 [48]| 4 [102]
@| 4 [102] @| 0| 1 [25]| 3 [76]| 6 [152] @| 110 [50]
075417| 171/2 [445]| 1611/32 [415]| 123/8 [314]| C| 15| [381]| 21/2 [64]| 3|
[76] @| 3| [76] @| 0| 1 [25]| 3 [76]| 6 [152] @| 125 [57]
075421/
100
| 21| [533]| 1927/32 [504]| 141/8 [359]| C| 181/2 [470]| 21/2 [64]| 0| 0| 0| 1
[25]| 3 [76]| 6 [152] @| 140 [64]
125| 241/2 [622]| 2311/32 [593]| 157/8 [403]| C| 22| [559]| 21/2 [64]| 0| 0|
0| 1 [25]| 3 [76]| 6 [152] @| 150 [68]
NOTES
- May require a 3″ [76 mm] to 4″ [102 mm] or 3″ [76 mm] to 5″ [127 mm] adapter.
- May be 0″ [0 mm] with a type B vent.
- May be 1″ [25 mm] with a type B vent.
Furnaces must be vented in accordance with the National Fuel Gas Code, ANSI Z223.1, and in accordance with local codes.
Blower Performance Data
TARGET GAS HEATING AIRFLOWS
| R801V0503A14UHCAP| R801V0754A17UHCAP| R801V0755A21UHCAP|
R801V1005A21UHCAP| *R801V1255A24UHCAP**
Factory High Heating CFM [L/s]| 960.0 [453]| 1450.0 [684]| 1425.0 [673]|
1380.0 [651]| 1900 [897]
High Heat Side Return CFM [L/s]| 960.0 [453]| 1450.0 [684]| 1425.0 [673]|
1380.0 [651]| 1900 [897]
High Heat Approx. ±7°F CFM| 864.0 [408]| 1305.0 [616]| 1282.5 [605]| 1242.0
[586]| 1710 [807]
High Heat Approx. ±12°F CFM| 796.8 [376]| 1203.5 [568]| 1182.75 [558]| 1145.4
[541]| 1577 [744]
BOTTOM RETURN FILTER RACK FOR UPFLOW APPLICATION: RXGF-CB
SIDE RETURN FILTER RACK: RXGF-CD
*FILTER RACK FILTER SIZES INCHES [mm]**
MODEL
| RXGF-CB (UPFLOW/ HORIZONTAL)| RXGF-CD (UPFLOW) SIDE
RETURN
R801V050| 121/4 x 25| 153/4 x 25
[311 x 635]| [400 x 635]
R801V0754A17| 153/4 x 25| 153/4 x 25
[400 x 635]| [400 x 635]
R801V0754A21/| 191/4 x 25| 153/4 x 25
R801V100| [489 x 635]| [400 x 635]
R801V125| 223/4 x 25| 153/4 x 25
[578 x 635]| [400 x 635]
- 4″ FLUE ADAPTER: RXGW-C01
Indoor Coil Casings
MODEL NUMBER
RXBC-D14AI
RXBC-D17AI
RXBC-D21AI
RXBC-D21BI
RXBC-D24AI
| WARNING: IMPORTANT NOTICE
---|---
A SOLID METAL BASE PLATE (SEE TABLE) MUST BE IN PLACE WHEN
THE FURNACE IS INSTALLED WITH SIDE AIR RETURN DUCTS. FAILURE
INSTALL A BASE PLATE COULD CAUSE PRODUCTS OF COMBUSTION
TO BE CIRCULATED INTO THE LIVING SPACE AND CREATE POTENTIALLY
HAZARDOUS CONDITIONS.
FURNACE| SOLID| BASE| BASE
WIDTH IN. [mm]| BOTTOM KIT NO.| PLATE NO.| PLATE
SIZE IN. [mm]
14 [356]| RXGB-D14| AE-61874-01| 115/8 x 239/16 [295 x 598]
171/2 [445]| RXGB-D17| AE-61874-02| 151/8 x 239/16 [384 x 598]
21 [533]| RXGB-D21| AE-61874-03| 185/8 x 239/16 [473 x 598]
241/2 [622]| RXGB-D24| AE-61874-04| 255/8 x 239/16 [651 x 598]
For High Altitudes
- OPTION CODE FOR HIGH ALTITUDE: U.S. None required for high altitudes. HIGH ALTITUDE CONVERSION KITS: U.S. None required for high altitudes. 80+ HIGH ALTITUDE INSTRUCTIONS
- CAUTION: Always follow National Fuel Gas Code (NFGC) guidelines when converting for high altitudes. High altitude option codes are not required for these models. However, the burner orifice size needs to be recalculated and verified at elevations above 2000 ft. See Installation Instructions for more information.
THE ECONET® SMART THERMOSTAT
- BUILT-IN WIFI
- 4.30 LCD TOUCHSCREEN
- LOCAL WEATHER – Current conditions plus 6-day forecast
- 5 OPERATING MODES – Heat, Cool, Auto, Emergency Heat and Fan Only
- 7-DAY PROGRAMMABLE SCHEDULE – Offers comfort without thought
- ONE-TOUCH AWAY – Quickly switch to your energy-saving away preferences
- VACATION SCHEDULING – Allows you to save while you’re away and come home to comfort
- STANDBY SCREEN – Displays indoor temperature and current weather
OPERATIONAL FEATURES
- AUTOMATIC CHANGEOVER – Transitions between heating and cooling automatically to keep the house comfortable
- INTEGRATED WATER CONTROL – Enables easy water heater management
- SMOOTH ARRIVAL – Prompts the system to start ahead of schedule to ensure the home is at the desired temperature at the scheduled time
- HUMIDITY CONTROL – Supports humidifier accessories or over-cool-based dehumidification
- DETAILED OPERATING STATUS – View pertinent equipment status information and run times
- CONTINUOUS FAN – Offers 5 speeds (Low, Medium Low, Medium, Medium High, High)
- SHORT-CYCLE PROTECTION – Avoids damage to equipment from short-run cycles
MONITORING & REMOTE CONTROL FEATURES
- ACTIVE MONITORING – Alerts to problems that need immediate attention
- REMOTE CONTROL – Allows adjusting of comfort and settings from anywhere using a mobile device
- SERVICE ALERTS – Sends routine maintenance reminders
- AIR FILTER MONITORING – Detects when it’s time to replace the air filter
- ALARM HISTORY – Displays time-stamped alarm codes with clear descriptions
GENERAL TERMS OF LIMITED WARRANTY
- Rheem will furnish a replacement for any part of this product that fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.
- For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.
Conditional Parts
- (Registration Required)……………………………. Ten (10) Years
- Heat Exchanger…………………………………Twenty (20) Years
In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.
Rheem Heating, Cooling & Water Heating
- 5600 Old Greenwood Road
- Fort Smith, Arkansas 72908
- www.rheem.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>