COMPTUS A70H-HTP Atmospheric Temperature Sensors
Product Information: A70H-HTP Atmospheric Temperature, Humidity, and
Pressure Sensor
The A70H-HTP is an advanced atmospheric sensor designed to measure
temperature, humidity, and pressure. It is a high sensitivity sensor enclosed
in a single IP65/NEMA4 UV protected casing. The sensor is available with a
radiation shield made of ABS plastic and stainless steel mounting hardware,
providing additional protection. A70H-T & A70H-T-S
The A70H-T is a high sensitivity atmospheric temperature sensor. The sensor is
in a single IP65/NEMA4 UV protected casing. The available radiation shield is
ABS plastic with stainless steel mounting hardware.
Features
- High sensitivity atmospheric sensor
- Measures temperature, humidity, and pressure
- Comes standard as A70H-HTP Sensor
- Available with Solar Radiation Shield (A70H-HTP-S)
- Available with Solar Radiation Shield (A70H-HT-S)
- Comes Standard as A70H-HT Sensor Only
Applications
- Building Automation and Controls
- Environmental Monitoring
Specifications
- Temperature Range: -40°C to +85°C
- Humidity Range: 0-100% R.H.
- Pressure Range: 0-100 kPa
- Humidity Resolution: 0.5% R.H.
- Power Supply: 12-24 VDC
- Range: Humidity – 0-100% R.H.
- Temperature – -40ºC to 60ºC
- Resolution: Humidity – 0.5% R.H.
- Temperature – 0.1ºC
- Accuracy: Humidity – ±3% R.H.
- Temperature – ±0.5ºC
- Electrical: Power Supply – 12-24 VDC
- Output Signal – 4-20 mA; 0-10V, RS485, I²C, SDI-12
- Current Consumption – <20mA
- Operating Temperature: -40ºC to 60ºC
- Ingress Protection: IP65/NEMA4
- Storage Conditions: 10ºC to 60ºC @ 20% to 90% R.H.
- Weight: 120g / 4.2 oz (With Shield, 730g / 1.6 lbs)
- Materials: ABS, Aluminum, Stainless Steel
- Radiaiton Shield Dimensions: 7”D x 12”H
Product Usage Instructions
- Ensure the A70H-HTP Atmospheric Temperature, Humidity, and Pressure Sensor is properly installed in the desired location.
- Connect the power supply (12-24 VDC) to the sensor.
- Make sure the sensor is securely fastened to its mounting hardware.
- If using the Solar Radiation Shield (A70H-HTP-S), attach it to the sensor for additional protection against solar radiation.
- Once the sensor is powered and mounted, it will start measuring atmospheric temperature, humidity, and pressure automatically.
- To retrieve the measured data, refer to the product’s documentation or contact the manufacturer for guidance.
- Regularly maintain and clean the sensor to ensure accurate readings and optimal performance.
INSTALLATION
Install the product in a stable environment, away from artificial heating and
cooling devices and avoiding direct sunlight if possible. Use the supplied
U-bolts to attach the angled mount to a vertical pipe or stan-chion that is
approximately 2” in diameter. The Comptus logo should be angled towards the
ground with the mounting plane for the radiation shield horizontal above the
U-bolts. The angled mount can also be directly attached to a vertical face
with screws or bolts.
Slide the free end of the sensor probe into the large cable gland on the
bottom of the radiation shield until the sensor probe is one third to one half
of the way into the radiation shield. Stop before you get to the hex of the
gland nut that holds the black cable. Tighten down the large cable gland on
the bottom of the radia-tion shield to lock the sensor probe in place.
Remove the cable ties from the coiled black cable and slide the free end (with
wire leads) of the cable through the large round hole in the mounting plane.
Remove the three wing nuts from the radiation shield and feed the black cable
down until you can mount the three studs through the holes on the mounting
plane. Attach in place with the wing nuts from the underside of the mounting
plane.
ELECTRICAL CONNECTIONS
OUTPUT CHARACTERISTICS
- Current (4-20mA)
- Temperature(˚C) = ((I-4)/16 * 100) – 40 where I = output current in mA.
- RS485 Communications Protocol (MODBUS-RTU)
- Communication parameters: Baud rate: 9600;
- Data bits:8; Stop bit:1;
- Parity: none
- Slave address: factory default is FFH (set according to the need, 00H to FFH) The 03H Function Code Example: Read the Atmospheric Temperature Host Scan Order (slave address: 0xFF)
- FF 03 00 00 00 01 91D4
- Slave Response FF 03 02 19AD 5BBD
- Temperature: (19AD)H = (6573)D = (6573/100)-40 = 25.73˚C
- The 10H Function Code Example: Modify the slave address (fixed command, ensure that no other devices are on the bus)
- Host Scan Order (Changed to 33H): 00 10 00 01 00 01 02 00 33 EA04
- Slave Response 00 10 00 01 00 01 51D8
- The 03H Function code Example: Read the Slave Address (fixed command, ensure that no other devices are on the bus)
- Host Scan Order: 00 03 00 01 00 01 D41B
- Slave Response: 00 03 02 00 FF C5C4
Note:
- All underlined is fixed bit;
- The last two bytes is CRC check command
If the transmission distance is over 100m please add a 120-ohm termination resistor on the front and back end of the bus interface respectively.
A70H-HT & A70H-HT-S
The A70H-HT is a high sensitivity atmospheric humidity and temperature sensor. The sensor is in a single IP65/NEMA4 UV protected casing. The available radiation shield is ABS plastic with stainless steel mounting hardware.
FEATURES
- Available with Solar Radiation Shield (A70H-HT-S)
- Comes Standard as A70H-HT Sensor Only
APPLICATIONS
- Building Automation and Controls
- Environmental Monitoring
SPECIFICATIONS
- Range: Humidity – 0-100% R.H.
- Temperature – -40ºC to 60ºC
- Resolution: Humidity – 0.5% R.H.
- Temperature – 0.1ºC
- Accuracy: Humidity – ±3% R.H.
- Temperature – ±0.5ºC
- Electrical: Power Supply – 12-24 VDC
- Output Signal – 4-20 mA; 0-10V, RS485, I²C, SDI-12
- Current Consumption – <20mA
- Operating Temperature: -40ºC to 60ºC
- Ingress Protection: IP65/NEMA4
- Storage Conditions: 10ºC to 60ºC @ 20% to 90% R.H.
- Weight: 120g / 4.2 oz (With Shield, 730g / 1.6 lbs)
- Materials: ABS, Aluminum, Stainless Steel
- Radiaiton Shield Dimensions: 7”D x 12”H
INSTALLATION
Install the product in a stable environment, away from artificial heating and
cooling devices and avoiding direct sunlight if possible. Use the supplied
U-bolts to attach the angled mount to a vertical pipe or stan-chion that is
approximately 2” in diameter. The Comptus logo should be angled towards the
ground with the mounting plane for the radiation shield horizontal above the
U-bolts. The angled mount can also be directly attached to a vertical face
with screws or bolts.
Slide the free end of the sensor probe into the large cable gland on the
bottom of the radiation shield until the sensor probe is one third to one half
of the way into the radiation shield. Stop before you get to the hex of the
gland nut that holds the black cable. Tighten down the large cable gland on
the bottom of the radia-tion shield to lock the sensor probe in place.
Remove the cable ties from the coiled black cable and slide the free end (with
wire leads) of the cable through the large round hole in the mounting plane.
Remove the three wing nuts from the radiation shield and feed the black cable
down until you can mount the three studs through the holes on the mounting
plane. Attach in place with the wing nuts from the underside of the mounting
plane.
ELECTRICAL CONNECTIONS
OUTPUT CHARACTERISTICS
- Current (4-20mA)
- T Temperature(˚C) = ((I-4)/16 * 100) – 40 where I = output current in mA.
- H Humidity(%) = (I-4)/16 * 100% where I = output current in mA.
- RS485 Communications Protocol (MODBUS-RTU)
- If the transmission distance is over 100m please add a 120-ohm termination resistor on the front and back end of the bus interface respectively.
Communication parameters
- Baud rate: 9600;
- Data bits:8; Stop
- bit:1;
- Slave address: factory default is FFH (set according to the need, 00H to FFH) The 03H
- Function Code Example: Read the Atmospheric Temperature & Humidity Host Scan Order (slave address: 0xFF)
- FF 03 00 00 00 02 D1D5
- Slave Response
- FF 03 04 19AD 1BE4 79FA
- Temperature: (19AD)H = (6573)D = (6573/100)-40 = 25.73˚C
- Humidity: (1BE4)H = (7140)D = 7140/100 = 71.40%
- The 10H Function Code Example: Modify the slave address (fixed command, ensure that no other devices are on the bus)
- Host Scan Order (Changed to 33H): 00 10 00 01 00 01 02 00 33 EA04
- Slave Response: 00 10 00 01 00 01 51D8
- The 03H Function code Example: Read the Slave Address (fixed command, ensure that no other devices are on the bus)
- Host Scan Order: 00 03 00 01 00 01 D41B
- Slave Response: 00 03 02 00 FF C5C4
Note:
- All underlined is fixed bit;
- The last two bytes is CRC check command
A70H-HTP & A70H-HTP-S
The A70H-HTP-S is a high sensitivity atmospheric humidity, temperature and barometric pressure sensor with radiation shield. The sensors are in a single IP65/NEMA4 UV protected casing. The available radiation shield is ABS plastic with stainless steel mounting hardware. The mounting bracket is supplied with two 2-1/4” U-bolts for mounting to a mast. The 4-wire sensor cable is 10’ (3m) long. Connections are for V+, V-, data A and data B.
FEATURES
- Available with Solar Radiation Shield (A70H-HTP-S)
- Comes Standard as A70H-HTP Sensor Only
APPLICATIONS
- Building Automation and Controls
- Environmental Monitoring
SPECIFICATIONS
- Range: Humidity – 0-100% R.H.
- Temperature – -40ºC to 60ºC
- Pressure – 10-110kPa (100-1100 mbar)
- Resolution: Humidity – 0.5% R.H.
- Temperature – 0.1ºC
- Pressure – 0.1 mbar
- Accuracy: Humidity – ±3% R.H.
- Temperature – ±0.5ºC
- Pressure – ±1 mbar
- Electrical: Power Supply – 12-24 VDC
- Output Signal – MODBUS RTU – RS485
- Current Consumption – <20mA
- Operating Temperature: -40ºC to 60ºC
- Ingress Protection: IP65/NEMA4
- Storage Conditions: 10ºC to 60ºC @ 20% to 90% R.H.
- Weight: 120g / 4.2 oz (With Shield, 730g / 1.6 lbs)
- Materials: ABS, Aluminum, Stainless Steel
- Radiaiton Shield Dimensions: 7”D x 12”H
INSTALLATION
Install the product in a stable environment, away from artificial heating and
cooling devices and avoiding direct sunlight if possible. Use the supplied
U-bolts to attach the angled mount to a vertical pipe or stan-chion that is
approximately 2” in diameter. The Comptus logo should be angled towards the
ground with the mounting plane for the radiation shield horizontal above the
U-bolts. The angled mount can also be directly attached to a vertical face
with screws or bolts.
Slide the free end of the sensor probe into the large cable gland on the
bottom of the radiation shield until the sensor probe is one third to one half
of the way into the radiation shield. Stop before you get to the hex of the
gland nut that holds the black cable. Tighten down the large cable gland on
the bottom of the radia-tion shield to lock the sensor probe in place.
Remove the cable ties from the coiled black cable and slide the free end (with
wire leads) of the cable through the large round hole in the mounting plane.
Remove the three wing nuts from the radiation shield and feed the black cable
down until you can mount the three studs through the holes on the mounting
plane. Attach in place with the wing nuts from the underside of the mounting
plane
ELECTRICAL CONNECTIONS:
- CABLE: RS485 Output
- RED: V+
- BLACK: V-
- YELLOW: RS485 DA+
- BLUE: RS485 DB-
OUTPUT CHARACTERISTICS
- RS485 Communications Protocol (MODBUS-RTU)
- If the transmission distance is over 100m please add a 120-ohm termination resistor on the front and back end of the bus interface respectively.
- Communication parameters: Baud rate: 9600; Data bits:8; Stop bit:1; Parity: none
- Slave address: factory default is FFH (set according to the need, 00H to FFH)
- The 03H Function Code Example: Read the Atmospheric Temperature, Humidity and Barometric Pressure Host Scan Order (slave address: 0xFF)
- FF 03 00 00 00 03 1015
- Slave Response
- FF 03 06 19AD 1BE4 2715 5A2C
- Temperature: (19AD)H = (6573)D = (6573/100)-40 = 25.73˚C
- Humidity: (1BE4)H = (7140)D = (7140/100) = 71.40%
- Pressure: (2715)H = (10005)D = (10005/100) = 100.05 kpa = 1000.5 mbar
- The 10H Function Code Example: Modify the slave address (fixed command, ensure that no other devices are on the bus)
- Host Scan Order (Changed to 33H): 00 10 00 01 00 01 02 00 33 EA04
- Slave Response 00 10 00 01 00 01 51D8
- The 03H Function code Example: Read the Slave Address (fixed command, ensure that no other devices are on the bus)
- Host Scan Order: 00 03 00 01 00 01 D41B
- Slave Response: 00 03 02 00 FF C5C4
Note:
- All underlined is fixed bit;
- The last two bytes is CRC check command
- Register Map: 40001 Temperature ˚C (value/100 – 40) i.e. 5923/100 – 40 = 19.23˚C
- 40002 Humidity % (value/100) i.e. 6055/100 = 60.55%
- 40003 Barometric pressure mbar (value/10) i.e. 9985/10 = 998.5 mbar
Specifications subject to change without notice Installation Questions and Troubleshooting
- Contact sales@comptus.com
- Call +1 603-726-7500
- 1307 NH Route 175