BAPI BA-RCV-BLE-EZ Wireless Receiver and Analog Output Modules Instruction Manual
- June 12, 2024
- BAPI
Table of Contents
- Overview and Identification
- Pairing of the Sensor, Receiver and Analog Output Modules
- Mounting and Locating of Antenna
- Mounting of Receiver and Analog Output Modules
- Termination
- Extending the RS485 Network between the Receiver and the Analog Output
- Receiver Switch Settings
- Resetting a Sensor, Receiver or Analog Output Module
- Wireless System Diagnostics
- Default Status When Wireless Transmission is Interrupted
- Receiver Specifications
- Analog Output Module Specifications
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BAPI BA-RCV-BLE-EZ Wireless Receiver and Analog Output Modules Instruction Manual
Overview and Identification
The Wireless Receiver from BAPI receives the signal from one or more wireless
sensors and supplies the data to Analog Output Modules through an RS485 four-
wire bus. The modules convert the signal to an analog voltage or resistance
for the controller. The receiver can accommodate up to 32 sensors and 127
different modules.
The Resistance Output Module (ROM) converts the temperature data from the
receiver into a 10K-2, 10K-3, 10K-3(11K) or 20K thermistor curve.
The Voltage Output Module (VOM) converts the temperature or humidity data from the receiver into a linear 0 to 5 or 0 to 10 VDC signal. There are eight factory set temperature ranges (°F and °C) and humidity ranges of 0 to 100% or 35 to 70%RH. See the product label for the range and output.
The Setpoint Output Module (SOM) converts the setpoint data from a wireless room sensor into a resistance or a voltage. There are five factory set voltage and resistive ranges, each with an optional override function.
Pairing of the Sensor, Receiver and Analog Output Modules
The installation process requires that each wireless sensor is paired to its
associated receiver and then to its associated output module or modules. The
pairing process is easiest on a test bench with the sensor, receiver and
output modules within arm’s reach of each other. Be sure to place a unique
identification mark on the sensor and its associated output module or modules
after they have been paired to each other so that they can be identified at
the job site.
If more than one variable is transmitted by the sensor (temperature, humidity
and setpoint for instance), each variable requires a separate output module.
Multiple output modules can be paired to the same variable if desired.
PAIRING A SENSOR TO THE RECEIVER
You must pair the sensor to the receiver before pairing the sensor to an
analog output module.
- Select the sensor that you wish to pair to the receiver. Apply power to the sensor. See its manual for detailed instructions.
- Apply power to the receiver. The blue LED on the receiver will light and remain lit.
- Press and hold the “Service Button” on the top of the receiver until the blue LED starts to flash, then press and release the “Service Button” on the sensor (Figs 3 & 4) that you want to pair to the receiver. When the LED on the receiver returns to a solid “On” and the green “Service LED” on the sensor circuit board blinks rapidly three times, the pairing is complete. Repeat this process for all sensors.
PAIRING AN OUTPUT MODULE TO A SENSOR
Once the sensor is paired to the receiver, you can pair output modules to the
sensor’s variable.
- Select the output module for the desired sensor variable and range and connect it to the wireless receiver (Fig 1).
- Press and hold the “Service Button” on the top of the output module until the blue LED begins to flash (about 3 seconds). Then, send a “pairing transmission signal” to that output module by pressing and releasing the “Service Button” on the wireless sensor.
The blue LED on the receiver will flash once indicating that a transmission
was received; then the blue LED on the output module will go solid for about 2
seconds and then turn off. The sensor and output module are now paired to each
other and will remain paired to one another through battery replacement or if
power is removed from wire power
units. The output module’s blue LED will now flash once whenever it receives a
transmission from the sensor.
Note: The wireless sensors are often measuring and transmitting multiple
varibles, such as temperature and humidity,
or temperature, humidity and setpoint. All of these variables are transmitted
when the sensor’s “Service Button” is pressed. However, each Analog Output
Module is configured at the time of order to a specific variable and range so
it will only pair to that variable and not the others.
Mounting and Locating of Antenna
The antenna has a magnetic base for mounting. Although the receiver may be
located inside a metal enclosure, the antenna must be outside the enclosure.
There must be a non-metallic line of sight from all the sensors to the
antenna. Acceptable line of sight includes walls made from wood, sheet rock or
plaster with non-metallic lath. The orientation of the antenna (horizontal or
vertical) will also affect the performance and varies by application.
Mounting the antenna on a metal surface will cut off reception from behind the
surface. Frosted windows may block reception too. A wooden or plastic furring
strip attached to a ceiling beam makes a great mount. The antenna may be hung
from any ceiling fixture using fiber or plastic twine. Do not use wire to
hang, and do not use perforated metal strapping, commonly called plumbers
tape.
Mounting of Receiver and Analog Output Modules
The receiver and output modules can be snaptrack, DIN Rail or surface mounted. Each receiver can accommodate up to 127 modules. Start with the receiver at the far left, then securely attach each output module to the right.
Push in the blue mounting tabs to mount in 2.75″ snaptrack. Push out the
mounting tabs for DIN Rail. Catch the EZ mount hook on the edge of the DIN
rail (Fig 7) and rotate into place. Push out the mounting tabs for surface
mounting using the four supplied screws,
one in each tab.
If your output modules cannot fit in one straight line because of limited
space, then mount a second string of modules above or below. Connect wires
from the right side of the first string of modules to the left side of the
second string of modules. This configuration requires one or more Pluggable
Terminal Block Connector Kits (BA/AOM-CONN) for the extra wire terminations on
the left and right side of the Analog Output Modules.
Each kit includes one set of 4 connectors.
Termination
The Wireless Receiver and Analog Output Modules are pluggable and can be connected in an attached string as shown at right. The power for the bus can be supplied to the receiver or to the last output module on the right side, but not to both places at the same time. Be sure you have enough power for all the devices on the bus.
Extending the RS485 Network between the Receiver and the Analog Output
Modules
The Analog Output Modules may be mounted up to 4,000 feet away from the receiver. The total length of all the shielded, twisted pair cables shown in Fig. 10 is 4,000 feet (1,220 meters). Connect the terminals together as shown in Fig. 10. If the distance from the receiver to the group of Analog Output Modules is greater than 100 feet (30 meters), provide a separate power supply or voltage converter (such as BAPI’s VC350A EZ) for that group of Analog Output Modules.
Note: The configuration in Fig 10 requires one or more Pluggable Terminal Block Kits for the extra wire terminations on the left and right side of the Analog Output Modules. Each kit includes one set of 4 connectors.
Receiver Switch Settings
All sensor settings are controlled and adjusted by the receiver to suit the needs of the installation. These are adjusted via the DIP switches on the top of the receiver. These are the settings for ALL OF THE SENSORS that are paired to that receiver.
Sample Rate/Interval The time between when the sensor wakes up and takes a reading. The available values 30 sec, 1 min, 3 min or 5 min.
Transmit Rate/Interval The time between when the sensor transmits the readings to the receiver. The available values are 1, 5, 10 or 30 minutes.
Delta Temperature The change in temperature between sample intervals that will cause the sensor to override the transmit interval and transmit the changed temperature at the next sample interval. The available values are 1 or 3 °F or °C.
Delta Humidity The change in humidity between sample intervals that will cause the sensor to override the transmit interval and transmit the changed humidity at the next sample interval. The available values are 3 or 5 %RH.
Resetting a Sensor, Receiver or Analog Output Module
Sensors, receivers and output modules remain paired to each other when power
is interrupted or the batteries are removed. To break the bonds between them,
the units need to be reset as described below:
TO RESET A SENSOR: Press and hold the “Service Button” on the sensor for about
30 seconds. During those 30 seconds, the green LED will be off for about 5
seconds, then flash slowly, then begin flashing rapidly. When the rapid
flashing stops, the reset is complete. The sensor can now be paired to a new
receiver. To re-pair to the same receiver, you must reset the receiver. Output
modules that were previously paired to the sensor do not need to be re-paired.
TO RESET AN OUTPUT MODULE: Press and hold the “Service Button” on the top of
the unit for about 30 seconds. During those 30 seconds, the blue LED will be
off for the first 3 seconds and then flash for the remaining time. When the
flashing stops, release the “Service Button” and the reset is complete. The
unit can now be re-paired to a sensor variable.
TO RESET A RECEIVER: Press and hold the “Service Button” on the sensor for
about 20 seconds. During those 20 seconds, the blue LED will flash slowly,
then begin flashing rapidly. When the rapid flashing stops and returns to
solid blue, the reset is complete. The unit can now be re-paired to wireless
sensors. Caution! Resetting the receiver will break the bonds between the
receiver and all sensors. You will have to reset each sensor and then re-pair
each of the sensors to the receiver.
Wireless System Diagnostics
Possible Problems:
The reading from the sensor is incorrect or at its low limit:
Possible Solutions:
– Check for proper wiring and connections from the output modules to the
controller.
– Check to see if the controller’s software is configured properly.
– Press the sensor’s “Service” button (as described in the Analog Output
Module Pairing section on pg 1) and verify that the green LED on the sensor
circuit board flashes. If not, replace the batteries.
– Check for proper power to the receiver and Analog Output Modules.
The LED on the top of the Analog Output Module is blinking rapidly:
– Re-pair the Analog Output Module as described on pg 1, and verify that the blue LED on the output module flashes when a transmission is received.
The sensor reading is coming out – Re-pair the Analog Output Module as described on pg 1, and verify that the blue the wrong output module:
LED on the output module flashes when a transmission is received.
Default Status When Wireless Transmission is Interrupted
If an output module does not receive data from its assigned sensor for 35 minutes, the blue LED on the top of the module will blink rapidly. If this happens, the individual Analog Output Modules will react as follows:
- Resistance Output Modules (BA/ROM) will output the highest resistance in their output range.
- Voltage Output Modules (BA/VOM) calibrated for temperature will set their output to 0 volts.
- Voltage Output Modules (BA/VOM) calibrated for humidity will set their output to their highest voltage (5 or 10 volts).
- Setpoint Output Modules (BA/SOM) will hold their last value indefinitely.
When a transmission is received, the output modules will revert to normal operation in 60 seconds or less.
Receiver Specifications
Supply Power: 15 to 40 VDC or 12 to 24 VAC, halfwave rectified Power
Consumption: 30mA @ 24 VDC, 2.75 VA @ 24 VAC Capacity/Unit: Up to 32 sensors
and 127 different Analog Output Modules Reception Distance: Varies by
application*
Frequency: 2.4 GHz (Bluetooth Low Energy)
Bus Cable Distance: 4,000 ft with shielded, twisted pair cable
Environmental Operation Range: Temp: 32 to 140°F (0 to 60°C) Humidity: 5 to
95% RH non-condensing Enclosure Material & Rating: ABS Plastic, UL94 V-0
Agency: RoHS
Analog Output Module Specifications
ALL MODULES Environmental Operation Range: Temp: 32°F to 140°F (0°C to 60°C)
Humidity: 5% to 95% RH non-condensing
Bus Cable Distance: 4,000 ft (1,220m) w/ shielded, twisted pair cable
Supply Power: (half wave) 15 to 40 VDC, 12 to 24 VAC
Enclosure Material & Rating: ABS Plastic, UL94 V-0 Agency: RoHS
SETPOINT OUTPUT MODULE (SOM)
Power Consumption:
Resistance Models:
20 mA @ 24 VDC, 1.55 VA @ 24 VAC
Voltage Models:
25 mA @ 24 VDC, 1.75 VA @ 24 VAC
Output Current: 2.5 mA @ 4KΩ load
Lost Comm. Timeout:
35 min. (Fast Flash)
Reverts to its last command
Analog Input Bias Voltage:
10 VDC max
(Resistance Output Models only)
Output Resolution:
Resistance Output: 100Ω
Voltage Output: 150µV
VOLTAGE OUTPUT MODULE (VOM)
Power Consumption:
25 mA @ 24 VDC, 1.75 VA @ 24 VAC
Output Current: 2.5 mA @ 4KΩ load
Lost Communication Timeout:
35 min. (Fast Flash)
Temperature output reverts to 0 volts
%RH output reverts to high scale (5V or 10V)
Output Voltage Range:
0 to 5 or 0 to 10 VDC (factory calibrated)
Output Resolution: 150µV
RESISTANCE OUTPUT MODULE (ROM)
Power Consumption:
20 mA @ 24 VDC, 1.55 VA @ 24 VAC
Analog Input Bias Voltage: 10 VDC max
Lost Comm. Timeout: 35 min. (Fast Flash)
Reverts to High Resistance >35KΩ (Low Temp)
Temperature Output Ranges:
10K-2 Unit: 35 to 120ºF (1 to 50ºC)
10K-3 Unit: 32 to 120ºF (0 to 50ºC)
10K-3(11K) Unit: 32 to 120ºF (0 to 50ºC)
20K Unit: 53 to 120ºF (12 to 50ºC)
Output Resolution: 100Ω
Specifications subject to change without notice.
Module Dimensions
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA Tel:+1-608-735-4800 · Fax+1-608-735-4804 · E-mail:sales@bapihvac.com · Web:www.bapihvac.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>