BAPI BA/LDT Series Water Leak Detector User Manual

June 4, 2024
BAPI

46091_ins_water_leak
Water Leak Detector (BA/LDT)
Termination and Troubleshooting

Overview & Identification

The Water Leak Detector is designed to sense the presence of water and alert a central monitoring system of the potentially destructive situation. The unit is available in three different models with the Attached Sensor, Remote Sensor, and Rope Sensor is shown in the figures below.

BAPI BA LDT Series Water Leak Detector - fig 1

BAPI BA LDT Series Water Leak Detector - fig 2

Cautions/Warnings
This unit is not intended to be a safety device. In no event shall BAPI or its officers, directors, employees or agents be liable to any company or individual for any indirect, incidental, special, exemplary, punitive or consequential damages including, without limitation, economic or commercial losses, arising out of or resulting from the misuse of this
water detector as a safety device.

Mounting

ATTACHED SENSOR

  1. Set the sensor in a location where a water leak is likely to occur.
  2. Use the 4 screw holes on the feet of the bracket to secure the sensor.
  3. Adjust the depth screw with the wing nut to set the alarm depth for detecting leaks as shown in Fig. 5.
  4. Terminate the unit as described in the Termination section.

BAPI BA LDT Series Water Leak Detector - fig 3

REMOTE SPOT SENSOR

  1. The sensor can be secured to a flat surface using the adhesive mounting strips (Fig. 7) or a screw (Fig. 8). It can also be mounted to a drip pan rim using the provided 7/64” hex set screws as shown in Fig. 6. If using the adhesive mounting strip, clean the surface before adhering.
  2. Adjust the depth screw with the wing nut to set the alarm depth for detecting leaks as shown in Fig. 9.
  3. Mount the BAPI-Box with the transmitter in a visible location within cable length of the Remote Spot Sensor.
  4. Terminate the unit as described in the Termination section.

BAPI BA LDT Series Water Leak Detector - fig 4

ROPE SENSOR

  1. The sensor can be laid on the floor or around pipes as shown in Figs. 10, 11, 12, & 13.
  2. Secure the sensor by using cable clamps.
  3. Mount the BAPI-Box with the transmitter in a visible location within the cable length of the Rope Sensor.
  4. Terminate the unit as described in the Termination section.

BAPI BA LDT Series Water Leak Detector - fig 6

  1. Loosen wing nut.
  2. Set the required depth of the sensor probe screw using a #2 Phillips screwdriver.
  3. Hold the sensor probe screw stationary with the screwdriver.
  4. Turn the wing nut down the probe screw until it engages the plastic.
  5. Tighten the wing nut 1/4 turn into the plastic.

Mounting continued…

BAPI BA LDT Series Water Leak Detector - fig 7

BAPI BA LDT Series Water Leak Detector - fig 9

Rope Sensor Mounting Bracket

The BAPI Rope Sensor Mounting Bracket is specifically designed to hold the rope taut and prevent rope slippage allowing for maximum contact with the monitored surface. Brackets can be easily mounted to flat surfaces utilizing the industrial adhesive backing or the built-in screw holes.
Part Number: BA/LDT-RR-MB

BAPI BA LDT Series Water Leak Detector - fig 11

Combining Sensors
The following combinations of sensors can be used:

  1. Two rope sensors with a combined length of no more than 100ft (30m).
  2. Two spot sensors with a combined length of no more than 75ft (22.8m).
  3. One spot sensor with a maximum length of 25ft (7.6m) and one rope sensor of no more than 50ft (15.2m).

Note: 50ft (15.2m) of two-conductor shielded, twisted pair cables can be used to extend the rope sensor. If you add any cable for extension, the sensitivity pot will need to be adjusted. The 100ft (30.5m) version will need to be fine-tuned based on the application. Ground the shielded cable located at the Water Leak A detector on the GND terminal. Do not ground the shield at the end that is terminated to the rope sensor.

BAPI BA LDT Series Water Leak Detector - fig 12

Wiring and Termination

BAPI BA LDT Series Water Leak Detector - fig 13

Terminal ……..Description
A ………………. Water Leak Sensor (no polarity)
B ………………. Water Leak Sensor (no polarity)
COM2 ……….. Alarm Contact 2
NO2 ………….. Alarm Contact 2
COM1 ……….. Alarm Contact 1
NO1 ………….. Alarm Contact 1
GND ………….. Power Supply Ground
V+ …………….. Power Supply Input, 24VAC/VDC ±10%

Note: This unit does not require a separate isolated power supply. The unit includes circuitry to isolate the power supply used to power the unit.

Sensitivity Adjustment for 10’ and 100’ Remote Rope Sensors

The unit’s leak detection sensitivity is set at the factory. However, for the 10ft (3.0m) and 100ft (30.5m) remote rope sensors, the sensitivity may need to be adjusted in the field.
If you are using a 10ft (3.0m) remote rope and it won’t respond, rotate the sensitivity adjustment potentiometer counterclockwise.
If you are using a 100ft (30.5m) remote rope and it is too sensitive, then rotate the sensitivity adjustment potentiometer clockwise.
Adjust the sensitivity until the unit consistently detects leaks without causing false trips during commissioning.
Note: The Sensitivity Adjustment Potentiometer is set at the factory to the fully counterclockwise (most sensitive) position.

BAPI BA LDT Series Water Leak Detector - fig 14

Set Up and Commissioning

INDICATION/CONTROLS…….. DESCRIPTION
Red LED ………………………………..LED illuminates when water is detected
Green LED …………………………….LED illuminates when normal power is applied
Reset Button ………………………….Resets manual alarm contact (only if water is no longer present)

FIELD CONFIGURABLE DIP SWITCH (SW1) SET UP
Relay Contact on Alarm Switch
Selects whether the alarm contacts on terminals NO1 and COM1 and the alarm contacts on terminals NO2 and COM2 are Normally Open (NO) or Normally Closed (NC)
Open = Normally Closed (NC), Closed = Normally Open (NO)

BAPI BA LDT Series Water Leak Detector - fig 16

Alarm Reset Switch
Selects whether the alarm will be latched ON after a leak detection (Manual) or if it will automatically reset the alarm once the leak is no longer present (Auto).

COMMISSIONING

  1. After the unit is installed and wired, turn on the power. (24VAC/VDC +/- 10%)
  2. Check that the green LED is “ON”. If it is not “ON”, check the power source.
  3. Dampen a cloth or sponge and touch the screws of the Attached Sensor or Remote Spot Sensor. If using a Rope Sensor, wrap the cloth or sponge around the rope. An alarm should occur within 5 seconds.
  4. The red LED should illuminate and the alarm contacts should change state. To check alarm contact status, measure the resistance at the relay contacts or monitor the status from the BAS screen.
  5. Remove the dampened rag or sponge to clear the alarm. If the unit is set up for an Alarm Reset: Manual, the operator must push the reset switch on the detector board or interrupt power to clear the alarm.
    NOTE: If the unit is set to Normally Closed, contact will open with loss of power indicating a leak.

Detectable Liquids

The sensors are designed to detect the presence of water and other conductive fluids. BAPI has performed tests on multiple liquid types to see which are detectable and which are not. Before leaving the installation, always check the sensor with the liquid you are trying to detect as every environment and application may be different.
DETECTABLE : Water, De-ionized water, Distilled Water, Reverse Osmosis (RO) Water
NOT DETECTABLE: Oil, Diesel Fuel, Unleaded Fuel

Maintenance

Check the water sensor probe once a year to be sure there is no dirt or debris collected around the probes. Dirt or debris around the probes may cause nuisance alarms in moist situations. Change the service intervals depending on environmental conditions. In very clean conditions the probe may never need maintenance. The rope sensor may be wiped down with isopropyl alcohol, warm soapy water on a cotton cloth or placed in a dishwasher.

Diagnostics

Possible Problem Possible Solution
Green LED Not On 1. Check for proper power to the unit (see power specs).
Red LED Not 1. Check for proper power to the unit (see power specs).
Working Or Alarm 2. Physically check for water to verify it’s touching both

screws on the Attached Sensor or Remote Spot, or touching the Rope Sensor.
Contact Not| 3. Adjust sensor probe depth on the Attached Sensor or Remote Spot if necessary.
Changing State| 4. For Rope Sensor units, check the sensitivity adjustment as described on page 4.
Unit Will Not Reset| 1. Check for the presence of water or debris on the sensor.
2. Be sure the sensor wires are not shorted.
3. Push the reset button and/or cycle power.
4. For rope sensor units, check the sensitivity adjustment as described on page 4.

Specifications

Power: 24VAC/VDC ±10%, 3.9VA max @ 24VAC, 90mA max @ 24VDC (Reverse Polarity Protected)
Note: This unit does not require a separate isolated power supply.
Rectification: Half Wave
Wiring:
Screw Terminals: 2 to 3 pairs of 12 to 22AWG (BAPI recommends 16 to 22AWG).
Water Detection Sensor: 2 wires (provided) Optional Flex Connector or Liquid Tight Fitting for strain relief
Sensor:
Attached Sensor: Sensor w/ adjustable depth screw from 0.063 to 0.84” (1.60 to 21.34mm)
Remote Sensor: Sensor w/ adjustable depth screw from 0.062 to 0.5” (1.57 to 12.70mm).
(Attached Remote Sensors are designed to be mounted to flat surfaces or on the rims of drip pans.)
Rope Sensor: Plenum-rated sensor cable, detects 1/8” of water. Max Length: 100’ (30.5m)

Alarm Output Relays:
Two SPST (Form A) Relays field selectable for Normally Open or Normally Closed. When configured as Normally Closed, the relay will change state with loss of power. 0.5A relay outputs, 10W max. Relay is not intended to switch a load.
Alarm Reset Action: Field selectable for Auto (Non-Latching) or Manual (Latching)
Auto: Relay automatically resets after water is removed (default)
Manual: Relay stays in alarm until manually reset or power is cycled
Local Indication: 1 Green Power LED, 1 Red Alarm LED
Operating Environment
Remote Sensor: -20 to 185ºF (-20 to 70ºC), 0 to 100%RH, Condensing
Rope Sensor: 32 to 167ºF (0 to 75ºC), 0 to 95%RH, Non-condensing
Detector (BB): -4 to 158ºF (-20 to 70ºC), 0 to 95%RH, Non-condensing
Enclosure Material and Ratings: NEMA 4 (IP66), UV-Resistant Polycarbonate, UL94V-0
Agency: CE 61326-1:2013 EMC (Industrial Electromagnetic Environment), RoHS, UL

Specifications subject to change without notice.
Building Automation Products, Inc.,
750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800
• Fax+1-608-735-4804
• E-mail:[email protected]
• Web:www.bapihvac.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

BAPI User Manuals

Related Manuals