BAPI BA/LDT Series Water Leak Detector User Manual
- June 4, 2024
- BAPI
Table of Contents
46091_ins_water_leak
Water Leak Detector (BA/LDT)
Termination and Troubleshooting
Overview & Identification
The Water Leak Detector is designed to sense the presence of water and alert a central monitoring system of the potentially destructive situation. The unit is available in three different models with the Attached Sensor, Remote Sensor, and Rope Sensor is shown in the figures below.
Cautions/Warnings
This unit is not intended to be a safety device. In no event shall BAPI or its
officers, directors, employees or agents be liable to any company or
individual for any indirect, incidental, special, exemplary, punitive or
consequential damages including, without limitation, economic or commercial
losses, arising out of or resulting from the misuse of this
water detector as a safety device.
Mounting
ATTACHED SENSOR
- Set the sensor in a location where a water leak is likely to occur.
- Use the 4 screw holes on the feet of the bracket to secure the sensor.
- Adjust the depth screw with the wing nut to set the alarm depth for detecting leaks as shown in Fig. 5.
- Terminate the unit as described in the Termination section.
REMOTE SPOT SENSOR
- The sensor can be secured to a flat surface using the adhesive mounting strips (Fig. 7) or a screw (Fig. 8). It can also be mounted to a drip pan rim using the provided 7/64” hex set screws as shown in Fig. 6. If using the adhesive mounting strip, clean the surface before adhering.
- Adjust the depth screw with the wing nut to set the alarm depth for detecting leaks as shown in Fig. 9.
- Mount the BAPI-Box with the transmitter in a visible location within cable length of the Remote Spot Sensor.
- Terminate the unit as described in the Termination section.
ROPE SENSOR
- The sensor can be laid on the floor or around pipes as shown in Figs. 10, 11, 12, & 13.
- Secure the sensor by using cable clamps.
- Mount the BAPI-Box with the transmitter in a visible location within the cable length of the Rope Sensor.
- Terminate the unit as described in the Termination section.
- Loosen wing nut.
- Set the required depth of the sensor probe screw using a #2 Phillips screwdriver.
- Hold the sensor probe screw stationary with the screwdriver.
- Turn the wing nut down the probe screw until it engages the plastic.
- Tighten the wing nut 1/4 turn into the plastic.
Mounting continued…
Rope Sensor Mounting Bracket
The BAPI Rope Sensor Mounting Bracket is specifically designed to hold the
rope taut and prevent rope slippage allowing for maximum contact with the
monitored surface. Brackets can be easily mounted to flat surfaces utilizing
the industrial adhesive backing or the built-in screw holes.
Part Number: BA/LDT-RR-MB
Combining Sensors
The following combinations of sensors can be used:
- Two rope sensors with a combined length of no more than 100ft (30m).
- Two spot sensors with a combined length of no more than 75ft (22.8m).
- One spot sensor with a maximum length of 25ft (7.6m) and one rope sensor of no more than 50ft (15.2m).
Note: 50ft (15.2m) of two-conductor shielded, twisted pair cables can be used to extend the rope sensor. If you add any cable for extension, the sensitivity pot will need to be adjusted. The 100ft (30.5m) version will need to be fine-tuned based on the application. Ground the shielded cable located at the Water Leak A detector on the GND terminal. Do not ground the shield at the end that is terminated to the rope sensor.
Wiring and Termination
Terminal ……..Description
A ………………. Water Leak Sensor (no polarity)
B ………………. Water Leak Sensor (no polarity)
COM2 ……….. Alarm Contact 2
NO2 ………….. Alarm Contact 2
COM1 ……….. Alarm Contact 1
NO1 ………….. Alarm Contact 1
GND ………….. Power Supply Ground
V+ …………….. Power Supply Input, 24VAC/VDC ±10%
Note: This unit does not require a separate isolated power supply. The unit includes circuitry to isolate the power supply used to power the unit.
Sensitivity Adjustment for 10’ and 100’ Remote Rope Sensors
The unit’s leak detection sensitivity is set at the factory. However, for the
10ft (3.0m) and 100ft (30.5m) remote rope sensors, the sensitivity may need to
be adjusted in the field.
If you are using a 10ft (3.0m) remote rope and it won’t respond, rotate the
sensitivity adjustment potentiometer counterclockwise.
If you are using a 100ft (30.5m) remote rope and it is too sensitive, then
rotate the sensitivity adjustment potentiometer clockwise.
Adjust the sensitivity until the unit consistently detects leaks without
causing false trips during commissioning.
Note: The Sensitivity Adjustment Potentiometer is set at the factory to
the fully counterclockwise (most sensitive) position.
Set Up and Commissioning
INDICATION/CONTROLS…….. DESCRIPTION
Red LED ………………………………..LED illuminates when water is detected
Green LED …………………………….LED illuminates when normal power is applied
Reset Button ………………………….Resets manual alarm contact (only if water is no
longer present)
FIELD CONFIGURABLE DIP SWITCH (SW1) SET UP
Relay Contact on Alarm Switch
Selects whether the alarm contacts on terminals NO1 and COM1 and the alarm
contacts on terminals NO2 and COM2 are Normally Open (NO) or Normally Closed
(NC)
Open = Normally Closed (NC), Closed = Normally Open (NO)
Alarm Reset Switch
Selects whether the alarm will be latched ON after a leak detection (Manual)
or if it will automatically reset the alarm once the leak is no longer present
(Auto).
COMMISSIONING
- After the unit is installed and wired, turn on the power. (24VAC/VDC +/- 10%)
- Check that the green LED is “ON”. If it is not “ON”, check the power source.
- Dampen a cloth or sponge and touch the screws of the Attached Sensor or Remote Spot Sensor. If using a Rope Sensor, wrap the cloth or sponge around the rope. An alarm should occur within 5 seconds.
- The red LED should illuminate and the alarm contacts should change state. To check alarm contact status, measure the resistance at the relay contacts or monitor the status from the BAS screen.
- Remove the dampened rag or sponge to clear the alarm. If the unit is set up for an Alarm Reset: Manual, the operator must push the reset switch on the detector board or interrupt power to clear the alarm.
NOTE: If the unit is set to Normally Closed, contact will open with loss of power indicating a leak.
Detectable Liquids
The sensors are designed to detect the presence of water and other conductive
fluids. BAPI has performed tests on multiple liquid types to see which are
detectable and which are not. Before leaving the installation, always check
the sensor with the liquid you are trying to detect as every environment and
application may be different.
DETECTABLE : Water, De-ionized water, Distilled Water, Reverse Osmosis
(RO) Water
NOT DETECTABLE: Oil, Diesel Fuel, Unleaded Fuel
Maintenance
Check the water sensor probe once a year to be sure there is no dirt or debris collected around the probes. Dirt or debris around the probes may cause nuisance alarms in moist situations. Change the service intervals depending on environmental conditions. In very clean conditions the probe may never need maintenance. The rope sensor may be wiped down with isopropyl alcohol, warm soapy water on a cotton cloth or placed in a dishwasher.
Diagnostics
Possible Problem | Possible Solution |
---|---|
Green LED Not On | 1. Check for proper power to the unit (see power specs). |
Red LED Not | 1. Check for proper power to the unit (see power specs). |
Working Or Alarm | 2. Physically check for water to verify it’s touching both |
screws on the Attached Sensor or Remote Spot, or touching the Rope Sensor.
Contact Not| 3. Adjust sensor probe depth on the Attached Sensor or Remote
Spot if necessary.
Changing State| 4. For Rope Sensor units, check the sensitivity adjustment as
described on page 4.
Unit Will Not Reset| 1. Check for the presence of water or debris on the
sensor.
2. Be sure the sensor wires are not shorted.
3. Push the reset button and/or cycle power.
4. For rope sensor units, check the sensitivity adjustment as described on
page 4.
Specifications
Power: 24VAC/VDC ±10%, 3.9VA max @ 24VAC, 90mA max @ 24VDC (Reverse
Polarity Protected)
Note: This unit does not require a separate isolated power supply.
Rectification: Half Wave
Wiring:
Screw Terminals: 2 to 3 pairs of 12 to 22AWG (BAPI recommends 16 to
22AWG).
Water Detection Sensor: 2 wires (provided) Optional Flex Connector or
Liquid Tight Fitting for strain relief
Sensor:
Attached Sensor: Sensor w/ adjustable depth screw from 0.063 to 0.84”
(1.60 to 21.34mm)
Remote Sensor: Sensor w/ adjustable depth screw from 0.062 to 0.5” (1.57
to 12.70mm).
(Attached Remote Sensors are designed to be mounted to flat surfaces or on the
rims of drip pans.)
Rope Sensor: Plenum-rated sensor cable, detects 1/8” of water. Max
Length: 100’ (30.5m)
Alarm Output Relays:
Two SPST (Form A) Relays field selectable for Normally Open or Normally
Closed. When configured as Normally Closed, the relay will change state with
loss of power. 0.5A relay outputs, 10W max. Relay is not intended to switch a
load.
Alarm Reset Action: Field selectable for Auto (Non-Latching) or Manual
(Latching)
Auto: Relay automatically resets after water is removed (default)
Manual: Relay stays in alarm until manually reset or power is cycled
Local Indication: 1 Green Power LED, 1 Red Alarm LED
Operating Environment
Remote Sensor: -20 to 185ºF (-20 to 70ºC), 0 to 100%RH, Condensing
Rope Sensor: 32 to 167ºF (0 to 75ºC), 0 to 95%RH, Non-condensing
Detector (BB): -4 to 158ºF (-20 to 70ºC), 0 to 95%RH, Non-condensing
Enclosure Material and Ratings: NEMA 4 (IP66), UV-Resistant
Polycarbonate, UL94V-0
Agency: CE 61326-1:2013 EMC (Industrial Electromagnetic Environment),
RoHS, UL
Specifications subject to change without notice.