NTI TFTN Series Natural GAS to Propane Gas Conversion Instructions
- June 12, 2024
- NTI
Table of Contents
NTI TFTN Series Natural GAS to Propane Gas Conversion Instructions
WARNING
This conversion kit shall be a qualified installed by service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information an explosion or production of carbon monoxide may result causing property damage, personal responsible for the proper installation of this kit. THE INSTALLATION IS NOT PROPER AND COMPLETE UNTIL THE OPERATION OF THE CONVERTED APPLIANCE IS CHECKED AS SPECIFIED IN THE MANUFACTURER’S INSTRUCTIONS SUPPLIED WITH THE KIT, WHICH NECESSITATES THE USE OF A CALIBRATED CO2/O2 AND CO COMBUSTION ANALYZER.
General Safety Information
NTI boilers are factory set to operate with Natural Gas. BEFORE OPERATING WITH PROPANE the boiler must be converted to Propane using this kit. Use the procedures outlined in these instructions to fully complete the Natural Gas to LP conversion for models 085, 110, 150, and 199.
Kit Contents:
- Natural to LP Conversion Instructions nr. 1
- LP Conversion Label nr. 1
- LP-Mixer w. Diaphragm (Table 1) nr. 1
- Gasket for gas pipe nr. 2
If the kit contents do not match those specified for your boiler model (see Table 1), DO NOT proceed with installing the Conversion Kit, and DO NOT operate the boiler – contact NTI for assistance.
Table 1 – LP Mixer and Gas Diaphragm
Model | Polidoro code (MIXER data plate) | LP diaphragm Ø in (mm) |
---|---|---|
085 and 110 | 350_0944_03 | 6.4 mm |
150 | 350_0921_03 | |
199 | 350_0922_03 | 6.9 mm |
WARNING
These instructions CANNOT be used to convert NTI appliance models not referenced in these instructions. Contact NTI for the Natural Gas to LP conversion kit and instructions for other models.
Failure to apply these instructions properly may result in dangerous explosion leading to property damage, personal injury or death.
ATTENTION:
LIQUEFIED PETROLEUM (LP) PROPANE propane gas is heavier than air; therefore,
it is imperative that your boiler is not installed in a pit or similar
location that will permit heavier than air gas to collect.
Local Codes may require appliances fueled with LP gas be provided with an approved means of removing unburned gases from the room. Check your local codes for this requirement.
WARNING.
Breathing Hazard – Carbon Monoxide Gas
- Do not operate heater if flood damaged.
- Install vent system in accordance with local codes and manufacturers installation instructions.
- Do not obstruct heater air intake or exhaust. Support all vent piping per manufacturers installation instructions.
- Do not place chemical vapor emitting products near unit.
- According to NFPA 720, carbon monoxide detectors should be installed outside each sleeping area.
- Never operate the heater unless it is vented to the outdoors.
- Analyze the entire vent system to make sure that condensate will not become trapped in a section of vent pipe and therefore reduce the open cross sectional area of the vent.
Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.
Propane Conversion Procedure
Install LP-Mixer with LP-Diaphragm
a. Check that the code of the air / gas mixer and the diameter of the gas
diaphragm are those indicated for the model of boiler to be converted – see
Table 1.
b. Turn the 120VAC power supply OFF to the boiler.
c. Turn the gas supply OFF.
d. Remove the front cover from the unit
e. Remove the silencer.
Figure 1 – Remove the Silence
f. Unscrew the two nuts and remove the gas pipe.
Figure 2 – Remove the Gas Pipe
g. Remove the three bolts securing the NG-mixer to the blower and remove the NG-Mixer.
Figure 3 – Remove the NG-mixer
NOTICE: 150 NG-mixers are equipped with an NG Diaphragm located on the mixer gas line inlet (see Figure 4 for general diaphragm location).
NOTICE: Save the NG-mixer (and NG Diaphragm for 150) in-case the boiler needs to be converted back to Natural Gas at a later date.
h. Secure the LP-Mixer (with LP Diaphragm) to the blower in the same position as the removed NG-Mixer, reusing the bolts from the previous step.
NOTICE: Verify the O-ring seal between the mixer and blower is correctly positioned and in good condition before assembling.
Figure 4 – Insert the LP-diaphragm
i. Reassemble the gas pipe to the gas valve and mixer.
ATTENTION!! Use the new rubber gaskets provided with the kit.
j. Install the silencer
Propane Conversion Procedure
Perform preliminary adjustment on gas valve throttle screw 4.
a. 085 and 110: Adjust throttle screw 4 counter-clockwise 0.5 turns.
b. 150 and 199: Adjust throttle screw 4 counter-clockwise 2 turns.
c. Turn the gas supply on and test for gas leaks in all piping.
d. Perform gas line pressure test and combustion calibration in
accordance with Parts 2 and 3.
NOTICE: 199 Model ONLY
When converted to LP, the 199 model must have the Max Power (parameter 24.1.1) adjusted from 87% to 89%, and the Min Power (parameter 24.1.3) adjusted from 4% to 6%.
Parameters are adjusted from Tech Menu – Complete Menu.
Figure 5 – Gas valve
Gas valve and burner setup
WARNING
Failure to perform the Gas Valve and Burner Setup correctly may result in
incorrect operation, component failure, property damage, serious injury or
death
Operating Sequence
Prior to commencing the Gas Valve and
Burner Setup, perform the following operating sequence check:
a. Turn the supply of gas to boiler off.
b. Set the thermostat to the highest setting.
c. Ensure the combustion fan prepurges for a short time prior to
activating the igniter.
d. Ensure the combustion fan postpurges for at least 5 seconds prior to
reactivating the igniter.
e. Set the thermostat to the lowest setting and continue with the Gas
Valve and Burner Setup procedure outlined below.
Gas Line pressure
The boiler gas valve is equipped with a Line Pressure Test Port; see screw 1,
Figure 5.
Use the following procedure to measure the gas line pressure to the boiler to ensure it falls within the range given in Table 2:
a. Turn the supply of gas to boiler off.
b. Loosen screw 1 (Torx 10 – Line Pressure Test Port). This port is
directly connected to the gas line feeding the boiler. See screw 1, Figure5.
c. Connect a gas pressure gauge to the line pressure test port using
applicable tubing. Ensure both ends of the tubing make a tight connection.
d. Turn the gas supply to the boiler on and check for gas leaks.
e. Observe the line pressure under static conditions and compare it to
Table 2. The pressure will be greatest under static conditions.
f. Observe the line pressure with the boiler running, while checking/
adjusting the CO2 at maximum and Compare it to Table 2. The pressure will
g. Adjust the gas line pressure to ensure the parameters in Table 2 are
attained under all conditions. If possible, adjust the line pressure to the
“Nominal/Desired” value listed in Table 2 while the unit is operating at the
maximum power. Continue observing gas line pressure until completing of
necessary Checking/ Adjusting of the CO2 (see Part 3), in case adjustments
need to be made.
h. Complete pressure testing. Remove the tubing from the test port and
then return the bleed screw of the Line Pressure Test Port to the closed
position. Check for gas leaks.
| Line Pressure (inches w.c.)
---|---
Nominal| Min.| Max.
Natural| 7| 3.5| 10.5
Propane| 11| 8| 13
Table 2 – Line Pressure Parameters
DANGER
Failure to close the bleed screw of the Line Pressure Test Port will cause
a severe leakage of gas, causing property damage, serious injury or death.
NOTICE
The line pressure is a function of the gas supply and affected solely by
field provided parameters such as line size and regulator settings. Under no
circumstances con the boiler gas valve influence or be used to adjust the gas
line pressure.
Checking/Adjusting the CO2 at Max and Min Power
WARNING
Adjustments to the Gas valve may technician, while using a calibrated
combustion analyzer capable of measuring CO2 and CO. Adjustments may only be
performed if the gas line pressure is maintained above minimum levels
throughout the duration of the test. See Table 3. Failure to follow these
instructions may result in serious injury or death.
WARNING
FAILURE TO PERFORM THE FLUE GAS ANALYSIS AND ADJUSTMENT AS DETAILED IN THIS
SECTION MAY RESULT IN ERRATIC AND UNRELIABLE BURNER OPERATION, LEADING TO
REDUCED EFFICIENCY, INCREASED FUEL CONSUMPTION, REDUCED COMPONENT LIFE, HEAT
EXCHANGER COMBUSTION DEPOSITS, AND GENERAL UNSAFE OPERATION. FAILURE TO FOLLOW
THESE INSTRUCTIONS MAY RESULT IN SERIOUS INJURY OR DEATH.
Preparing the measuring equipment
Remove the Combustion Test Port plug, as illustrated (Figure 6), and insert a
calibrated combustion analyzer.
NOTICE
Make sure the analyzer is set to the appropriate fuel
Figure 6 – Combustion Test Port
WARNING
It is required to use a calibrated combustion analyzer to verify the
combustion chart (Table 3). Failure to do so could result in serious personal
injury or death.
WARNING
It is very important that the
combustion system be set within the recommended CO2/ CO measurements listed
in Table 3. Visually looking at the burner does not determine combustion
quality. Failure to measure combustion with a calibrated combustion analyzer
and set the throttle within the recommended CO2/CO measurements could result
in property damage, severe personal injury, or death.
Checking/Adjusting the CO2 at Max Power
Set the thermostat at the highest possible setting to create a demand for heat.
Select Max Power from the Test Mode – Burner Test screen, then wait for the
Burner Power gauge to reach 100%.
Wait 1 minute for the boiler to stabilize before carrying out the combustion analyses. Read the CO2 value (%) and compare it with the values given in the table below:
Gas | CO2 (%) | CO (ppm) |
---|---|---|
Max Power (100%) | Min Power (10%) | |
NG | 8.7 – 10.0 | 8.5 – 9.8 |
LP | 9.7 – 11.0 | 9.5 – 10.8 |
ATTENTION:
The CO2 at Min Power must be set lower than the CO2 at Max Power by 0.2 – 1.0%
(e.g. if, using LP, the CO2 at Max Power = 10.3%, the CO2 at Min Power must be
between 9.5 – 10.1%).
ATTENTION!! Values must be obtained with the front cover installed. If the CO2 values given in Table 3, adjust the gas valve following the instructions below. Otherwise move directly to the next operation.
Adjusting the Gas Valve at Max Power
Adjust the gas valve by turning setting screw 4 clockwise to increase the CO2 level; counterclockwise to reduce the CO2 level (1 turn adjusts the CO2 level by approximately 0.3%). Wait 1 minute after each change in setting for the CO2 value to stabilize. If the measured value corresponds to the value given in Table 3, Max Power adjustment is complete. Otherwise, continue with the procedure
Figure 7 – Max Power CO2 Adjustment
ATTENTION!!
Test Function will automatically deactivate after 30 minutes. Test Function
can be turned off manually by pressing the RESET button.
Checking/Adjusting the CO2 at Min Power
Select Min Power from the Test Mode – Burner Test screen, then wait for the
Burner Power gauge to reach 10%.
Wait 1 minute for the boiler to stabilize before carrying out the combustion analyses
If the CO2 (%) reading at Min Power is not 0.2 – 1.0% lower than the CO2 (%) reading at Max Power, adjust the gas valve following the instructions below. Otherwise move directly to the next operation.
Adjusting the Gas Valve at Min Power
Remove cap and adjust screw 2 by turning counter-clockwise to reduce the CO2
level; clockwise increase it.
Figure 8 – Min Power CO2 Adjustment
Wait 1 minute after each adjustment for the CO2 value to stabilize.
WARNING! Min Power adjustment is very sensitive.
If the value measured corresponds to the value given in Table 3, Min Power
adjustment is complete. Otherwise continue with the procedure.
Attention!!
If Screw 2 has been adjusted, it is necessary to repeat the ‘Ajusting the CO2
at Max Power’ procedure.
Ending Adjustment
- Exit Test Mode by pressing the ‘Press to Stop Test’ button (located in the lowerleft corner of the Burner Test screen).
- Turn down the thermostat and / or stop the DHW draw.
- Reinstall the Combustion Test Port plug (see Figure 6).
- Check for and repair any gas leaks.
- Reinstall the front cover.
WARNING
Carbon Monoxide – Never leave the unit operating while producing Carbon
Monoxide (CO) concentrations in excess of the values indicated in Table 3.
Failure to follow this warning may result in serious injury or death.
WARNING
Breathing Hazard – Carbon Monoxide Gas
- Do not operate heater if flood damaged.
- Install vent system in accordance with local codes and manufacturers installation instructions.
- Do not obstruct heater air intake or exhaust. Support all vent piping per manufacturers installation instructions.
- Do not place chemical vapor emitting products near unit.
- According to NFPA 720, carbon monoxide detectors should be installed outside each sleeping area.
- Never operate the heater unless it is vented to the outdoors.
- Analyze the entire vent system to make sure that condensate will not become trapped in a section of vent pipe and therefore reduce the open cross sectional area of the vent.
Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.
Model | Min Power | Max Power |
---|---|---|
Burner Power | MBH | Burner Power |
TFTN085 | 10 % | 8.5 |
TFTN110 | 11.0 | HO |
TFTN150 | 15.0 | 150 |
TFTN199 | 19.9 | 199 |
- Canada: Altitudes between 2000-4500 ft, de-rate by 10%. Consult local authorities for de-rating for altitudes above 4500ft.
- USA: De-rate capacity by 4% for every 1000 ft above sea level, if altitude is above 2000 ft.
Update rating plate
As the certified installer of the Natural Gas to LP Conversion Kit, you must indicate on the boiler that it has been converted for use with Propane (LP) Gas:
a. Update Rating Plate Decal
– Locate the rating plate decal on the side of the appliance. Using a regular
ink pen, check the box next to “Field converted to Propane Gas” and fill in
the date. Press hard enough to permanently mark the decal. See Figure 9.
FACTORY SET FOR NATURAL GAS
Field converted to Propane Gas
October 22,2018
ADJUSTER A L’USINE POUR GAZ NATURAL
Convertie au propane sur place
Gas Pressure [Pression du Gaz] | Natural [Naturel] | Propane |
---|---|---|
Maximum Inlet Gas Pressure [Pression maximale d’entrée du gaz] | 10.5″ wc | |
[2.6 kPa] | 13″ wc [3.2 kPa] | |
Minimum Inlet Gas Pressure [Pression minimum d’entrée du gaz] | 3,5″ wc [1 | |
kPa] | 8″ wc [2 kPa] | |
Manifold Pressure [Pression d’admission] | 0″ wc [0 kPa] | 0″ wc [0 kPa] |
Figure 9 – Update the Rating Plate Decal
b. Conversion Decal – Fill out the required information on the Conversion Decal (included in this adjacent to the rating plate decal, in a location where it can be easily seen. See Figure 10.
THIS CONTROL WAS CONVERTED FOR USE WITH PROPANE GAS
This appliance has been converted for use with Propane Gas, in accordance with
the
instructions provided with the Natural to Propane Conversion Kit
by __ , which accepts responsibility that
the conversion was performed properly.
Reference rating plate for Propane Input and Gas Pressure
420060882600
Figure 10 – Conversion Decal
Visit us online
NTI Boilers Inc.
30 Stonegate Drive Saint John,
NB E2H 0A4 Canada
Technical Assistance: 1-800-688-2575
Website: www.ntiboilers.com
Fax: 1-506-432-1135
Visit us online
86662 Rev. 22.7.13
Documents / Resources
| NTI
TFTN Series Natural GAS to Propane Gas
Conversion
[pdf] Instructions
TFTN085, TFTN110, TFTN150, TFTN199, TFTN Series Natural GAS to Propane Gas
Conversion, TFTN Series, TFTN Series GAS to Propane Gas Conversion, Natural
GAS to Propane Gas Conversion, GAS to Propane Gas Conversion, GAS to Propane
Gas, GAS Conversion, Conversion
---|---
| NTI
TFTN
Series
[pdf] Instructions
TFTN500, TFTN600, TFTN725, TFTN850, TFTN500 TFTN Series NATURAL GAS TO PROPANE
GAS, TFTN500, TFTN Series NATURAL GAS TO PROPANE GAS, Series NATURAL GAS TO
PROPANE GAS, NATURAL GAS TO PROPANE GAS, GAS TO PROPANE GAS, TO PROPANE GAS,
PROPANE GAS, GAS
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>