Altronix OLS120 Off-Line Power Supply/Charger Installation Guide
- June 4, 2024
- Altronix
Table of Contents
OLS120 Off-Line Power Supply/Charger
Installation Guide
Overview:
Altronix OLS120 power supply/charger converts 115VAC, 60Hz or 230VAC, and 50Hz input into a 12VDC or 24VDC at 4A of continuous supply current (see specifications). This general-purpose power supply has a wide range of applications for access control and security system accessories that require additional power.
Specifications:
Agency Listings:
- UL Recognized component for Information Technology Equipment (UL 60950-1).
- CE European Conformity.
Input:
- Universal input 115VAC, 60Hz, 0.95A or 230VAC, 50Hz, 0.6A.
Output:
- 12VDC or 24VDC selectable output.
- 4A continuous supply current.
- Filtered and electronically regulated output.
- Short circuit and thermal overload protection.
Battery Backup:
- Built-in charger for sealed lead acid or gel-type batteries.
- Automatic switch over to stand-by battery when AC fails.
- Maximum charge current 0.7A.
Supervision:
- AC fails supervision (form “C” contacts).
- Low battery supervision (form “C” contacts).
Visual Indicators:
- AC input and DC output LED indicators.
Features:
- Power the ON/OFF switch.
- Includes battery leads.
Board Dimensions (L x W x H approx.):
7.25” x 4.5” x 1.75”
(184.1mm x 114.3mm x 44.5mm).
Installation Instructions:
OLS120 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
-
Mount the OLS120 in the desired location/enclosure (mounting hardware included).
-
Slide [Power ON/OFF] switch to the OFF position.
-
Set the OLS120 to the desired DC output voltage via SW1 (Voltage Output Selection Table).
Keep power-limited wiring separate from non-power-limited wiring (115VAC/230VAC 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts.
Shut branch circuit power before installing or servicing equipment.
There are no user-serviceable parts on the unit.
Refer installation and servicing to qualified service personnel. -
Connect AC power to the terminals marked [L & N], and connect ground to the terminal marked [G].
Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting). -
Slide [Power ON/OFF] switch to the ON position.
-
Measure output voltage before connecting devices. This helps avoid potential damage.
-
Slide [Power ON/OFF] switch to the OFF position.
-
Connect devices to be powered to the terminals marked [– DC +].
-
When the use of stand-by batteries is desired, they must be lead acid or gel type.
Connect the battery to the terminals marked [– BAT +] (battery leads included).
Use two (2) 12VDC batteries connected in series for 24VDC operation. -
When batteries are not used, a loss of AC will result in the loss of output voltage.
-
Connect appropriate signaling notification devices to AC Fail & Low battery supervisory relay outputs marked [NC, C, NO].
-
Slide [Power ON/OFF] switch to the ON position.
Voltage Output Selection Table:
Output VDC | Switch Position | Max. Load DC |
---|---|---|
12VDC | SW1 – ON | 4A |
24VDC | SW1 – OFF | 4A |
LED Diagnostics:
Red (DC) | Green (AC) | Power Supply Status |
---|---|---|
ON | ON | Normal operating condition. |
ON | OFF | Loss of AC. The standby battery is supplying power. |
OFF | ON | No DC output. Short circuit or thermal overload condition. |
OFF | OFF | No DC output. Loss of AC. Discharged or no battery present. |
Terminal Identification:
Terminal Legend | Function/Description |
---|---|
L, G, N | Connect 115VAC/230VAC to these terminals: L to Hot, N to Neutral, G |
to ground.
– DC +| 12VDC / 24VDC @ 4A continuous supply current.
AC FAIL
NC, C, NO| Used to notify loss of AC power, e.g. connect to audible device or
alarm panel.
The relay is normally energized when AC power is present.
Contact rating 1A @ 115VAC / 28VDC
Low Battery
NC, C, NO| Used to indicate low battery condition, e.g. connect to the alarm
panel. The relay is normally energized when DC power is present. Contact
rating 1A @ 115VAC / 28VDC.
Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC.
24VDC output threshold set @ approximately 21VDC.
– BAT +| Stand-by battery connections. Maximum charge rate 0.7A.
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA
phone: 718-567-8181
fax: 718-567-9056
website: www.altronix.com
e-mail: info@altronix.com
Lifetime Warranty
IIOLS120 – Rev. 010704