eSolutions eProWallbox Move Charging Station for Electric Vehicle Instructions
- June 12, 2024
- eSolutions
Table of Contents
eSolutions eProWallbox Move Charging Station for Electric Vehicle
Product Information
- Brand: Free2move eSolutions S.p.A
- Model: eProWallbox Move
- Address: Piazzale Lodi, 3 20137 Milan – Italy
Safety Instructions
- This document contains important safety instructions that must be followed during the installation and maintenance of the equipment.
- Ensure that the eProWallbox Move is not connected to the power grid before starting any work on the installation.
- All installation, maintenance, and disassembly work must be carried out only when the device is not connected to the power grid.
- Improperly performed installation, maintenance, or repair work can pose risks to the user.
- Make sure that the eProWallbox Move is used only under proper working conditions.
- The device is equipped with a Residual Current Device (RCD) for protection against indirect contact.
- The RCD has a Type A classification and a maximum rated current of 30 mA.
- The RCD complies with IEC 61008-1, IEC 61009-1, IEC 60947-2, and IEC 62423 standards.
- The RCD has a B classification for sensitivity.
Product Usage Instructions
- Ensure that the eProWallbox Move is not connected to the power grid before starting any installation, maintenance, or disassembly work.
- Follow the provided user manual or installation instructions for detailed guidance on using the eProWallbox Move.
- Store this document in a safe place for easy access during installation and maintenance work.
- Only perform installation, maintenance, and repair work under proper working conditions.
- Refer to the safety instructions in this document for guidelines on safe usage.
SAFETY INSTRUCTIONS This document does not replace the user manual or installer manual. This page contains important safety instructions that must be followed during the installation and maintenance of the equipment. Keep this document in a safe place for easy access at all times during installation and maintenance.
RISK OF ELECTRIC SHOCK AND FIRE
Before starting the installation, make sure that eProWallbox Move is not connected to any electrical network. Any installation, maintenance, or disassembly must be carried out only when the appliance is disconnected from the electrical network. Installation, maintenance or repairs that are not carried out correctly may involve risks for the user. It must be ensured that eProWallbox Move is used only in the presence of the correct operating conditions.
QUALIFIED PERSONNEL
With a permanent connection to the electrical network, the installation
requires the intervention of qualified personnel for the design and
construction of a dedicated, state-of-the-art electrical power system and to
certify the domestic electrical system in compliance with local regulations
and the energy supply contract. The system must comply with IEC 60364-7-722
Low-voltage electrical installations – Part 7-722 Requirements for special
installations or locations, Supplies for electric vehicles. (Requirements for
special plants or sites, Power supplies for electric vehicles). In addition,
the system must comply with local installation standards. Free2move eSolutions
S.p.A. assumes no responsibility for damage caused by improper installation of
the device. Installers are responsible for completing the installation in the
state of the art at a technical level and in compliance with current
regulations. Incorrect installation can cause hazards such as serious injury
or death.
DEDICATED ELECTRIC CIRCUIT FOR POWER SUPPLY
eProWallbox Move shall be supplied by a three-phase 400V, (Line-Line-Line-
Neutral- Protective Earthing) or by a single-phase 230V (Line- Neutral-
Protective Earthing) dedicated circuit with utilization factor (Ku=1) and
contemporaneity factor (Kc=1). The installer must evaluate the cross-section
of the dedicated circuit according to eProWallbox Move nominal current, cable
carrying capacity, type of installation, correction factors, operative
temperature, adjacent cables, and voltage drop.
DEVICE FOR PROTECTION AGAINST INDIRECT CONTACT BY AUTOMATIC DISCONNECTION
OF SUPPLY
- Residual Current Device (RCD) eProWallbox Move shall be protected by a three-phase 400V RCD, or single-phase 230V RCD according to the installation, shall comply with the requirements of an RCD Type A, and shall have a rated residual operating current not exceeding 30 mA. RCD shall comply with one of the following standards: IEC 61008-1, IEC 61009-1, IEC 60947-2, or IEC 62423. RCD shall disconnect all live conductors. Use a Type B RDC if local regulation requires it.
- Insulation Monitoring Device (IMD) For circuits in IT systems that are intended to power eProWallbox Move, for example through an isolation transformer or a battery system, an Insulation Control Device (IMD)compliant with IEC 61557-8 must be provided.
DEVICE FOR PROTECTION AGAINST OVERCURRENT
eProWallbox Move shall be protected by a three-phase 400V or single-phase 230V
overcurrent protective device (Miniature Circuit Breaker – MCB) complying with
IEC 60947-2, IEC 60947-6-2 or IEC 61009-1 or with the relevant parts of IEC
60898 series or IEC 60269 series. Type C curve for domestic or similar use is
suggested as the trip curve. Regarding the nominal current, the installer must
evaluate the choice of an MCB with rated current based on the eProWallbox Move
maximum power allowed. When dimensioning the MCB, the prospective short-
circuit current should be considered. As an indicative value 5kA could be
considered but a precise evaluation must be done before installation. The
maximum interrupting capacity of the MCB must be greater than the evaluated
prospective short-circuit current.
PROTECTION AGAINST TRANSIENT OVERVOLTAGES OF ATMOSPHERIC ORIGIN
To prevent possible damage to the electric vehicle due to overvoltage, it is
strongly recommended that the power supply circuit of the connection point is
protected by SPD. CONSULT THE MANUALS AND PERFORM THE INSTALLATION
OPERATIONS USING THE CLOTHING AND/OR PROTECTIVE EQUIPMENT PROVIDED BY THE
EMPLOYER
Please note the installation should be carried out after reading the dedicated
manual. The installation must be made by a professional following the
Installation manual Guidelines and it is compulsory to perform the described
operations using the clothing and/or protective equipment provided by the
employer. The maximum power that can be distributed by eProWallbox Move is
regulated by the local legislation in force in each country. Please refer to
the FAQs, and User and Installer Manual, for the maximum power, current and
indicative values. The Manual can be downloaded by scanning the QR Code and
clicking on the Library section of the website. To receive the Manual via mail
or in paper form, visit our Customer Support page
https://www.esolutionscharging.com/contact-us/. to find your country’s
Customer Service phone number. Although they are not made of materials that
are harmful to health, the products should not be disposed of along with
household waste but must be collected separately, because they are made of
materials that can be recycled.
CONTACT
Registered office
- FreeZmove Solutions S.p.A
- Piazzale Lodi, 3
- 20137 Milan – Italy
- Customer support:https://www.esolutionscharging.com/contact-us/.