eSolutions Annex eProWallbox Instruction Manual

June 3, 2024
eSolutions

**eSolutions Annex eProWallbox Instruction Manual

**

INTRODUCTION

The following features on eProWallbox can be configured via Bluetooth.

  • DPM:
    • DPM enabling
    • DPM Pmax
  • DPM 2.0:
    • Electrical Installation
    • Configuration
    • Transformer ratio KI
    • DPM Type selection
  • Load Unbalance
    • Load unbalance enabling
    • Load unbalance current

DPM 2.0 INSTALLATION

During the installation always refer to the meter installation manual included in the package.

  1. Place the Power Meter provided after the main utility meter and before the split power
    e Power Meter diagram

  2. For the three-phase or single-phase electrical connection, refer to the dedicated meter installation manual included in the Power Meter package.

  3. Feed the Modbus communication cables through the wallbox box sheath (C). Suggested cable: STP class 5E, 0.5 mm2 section.

  4. If included connect the Current Transformers as indicated in the meter installation manual, paying attention to drawn through the clamp the line according to the direction indicated on the sensor. The neutral cable must not be drawn through the clamp.

  5. Use the following order for connecting the communication cables from the PowerMeter to the Wallbox. Starting from left on the wallbox RS485 output port CN12
    EM330

EM111

PROCEDURE

The preliminary steps for the next operations are the following:

  1. Download and Install the application nRF Connect on your smartphone. F2meS suggests using an Android operating system

  2. Open nRF Connect and Set a filter (e.g. “ePro”) in order to see only eProWallboxes in the homepage

  3. Select Scan on the top right corner to identify the eProwallbox to be connected via Bluetooth through its Bluetooth name

  4. Once connected to the desired eProwallbox, select Unknown Services to begin with the configuration
    Download and Install the application nRF Connect

  5. The Unknown Services contains all the parameters that can be written and read through Bluetooth
    The Unknown Services contains all the parameters that can be written and
read through Bluetooth

Energy meter Configuration
  1. When powering up the Power Meter for the first time, tap&hold for 1.5 second, the central display button, at the bottom, until the display shows the page where to insert the password, initially set to 0000. You can edit each value using left or right display button and confirm each time by tap&holding the central display button.

  2. For the three-phase Power Meter only, the system mode: 3Pn

  3. To configure the Power Meter, tap&hold the left display button and set:

    • Modbus address: 1
    • BaudRate: 38.4 kbps
    • Parity bit: Even
  4. Set the model of Power Meter installed on nRF Connect app:
    Parameter: DPM_TYPE
    This field allows to select the Power Meter model installed
    UUID : f0f924f8-34ce-4f1d-9791-b1b19ff3ffe4
    TYPE: Uint8, select UINT8 on the app
    VALUE:

    • 00 → FINDER 3ph (212)
    • 01 → FINDER 1ph (210)
    • 02 → GAVAZZI EM330DINAV53HS1X
    • 03 → GAVAZZI EM111DINAV51XS1X
  5. If installed, set the Transformer Ratio KI on nRF Connect app:
    Parameter: TRANSFORMER_RATIO_KI
    This value allows to set the Current Transformer ratio according to the installed sensors. The value on the app is expressed in Hexadecimal
    UUID: 0c8d04fc-247c-4119-ab10-77ad3779310c
    TYPE: Uint32, select UINT32 on the app
    VALUE: Set the Transformer Ratio KI according to the values printed on the sensor.

    • E.g. 100/5 → KI = 20 (Hex value → 14)
    • 150/5 → KI = 30 (Hex value → 1E)
**DPM

**

  1. DPMPMAX
    Parameter: DPM_PMAX
    This field contains the contractual power expressed in Watt
    UUID:
    b4bc4914-1381-4294-acb0-776947becb9d
    TYPE:
    Uint32, select UINT32 on the app
    VALUE:
    min value 0, max value 70000

  2. Identify the UUID of the DPM Pmax parameter

  3. Click on the up arrow next to the Unknow characteristic

  4. Select UINT32

  5. In “New value” field insert the contractual power value, expressed in Watt, from 0 to 70000. Then click SEND

  6. The new value will appear on the main page, expressed in bytes

  7. DPMENABLING
    Parameter: DPM_ENABLED
    This feature enable the DPM functionality
    UUID: 9b5732b1-b557-40f7-ab72-fb00a3696 132
    TYPE:
    Boolean, select BYTE on the app
    VALUE:
    01 enabling, 00 disabling

  8. At the end of the process, to make the changes effective, restart the wallbox

  9. Identify the UUID of the DPM Enabling parameter

  10. Click on the up arrow next to the Unknow characteristic

  11. Select BYTE

  12. . In “New value” field insert: 01 to ENABLE 00 to DISABLE Then click SEND

  13. The new value will appear on the main page

LOAD UNBALANCE
  1. Load unbalance enabling
    Parameter: LOAD_UNBALANCE_ENABLED
    This function enables the load unbalance settings
    UUID: aa29e099-f9dc-40a4-8612-afbb78c612df
    TYPE: boolean, select BYTE on the app
    VALUE:

    • 00 → FALSE, disabled
    • 01 → TRUE, enabled
  2. Load unbalance current
    Parameter: LOAD_UNBALANCE_CURRENT
    This value defines the max allowable phases current unbalance expressed in mA
    UUID: f9217d22-b703-4a2a-a565-38662afc1a9c
    TYPE: Uint32, select UINT32 on the app
    VALUE:

    • 0 → Min value
    • 32000 → Max value, in mA

CUSTOMER SERVICE


Registered office
Free2move eSolutions S.p.A.
Piazzale Lodi, 3
20137 Milan – Italy
www.esolutions.free2move.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

eSolutions User Manuals

Related Manuals