GTE ADICOS AAB-L Junction Box Instruction Manual
- June 12, 2024
- GTE
Table of Contents
**GTE ADICOS AAB-L Junction Box Instruction Manual
**
Abstract
The Advanced Discovery System (ADICOS®) is used for early detection of fires
in industrial environments.
It is comprised of various, separate detector units. By parameterizing and
arranging the detectors appropriately, the system fulfills a predefined
detection goal.
The ADICOS system ensures reliable early detection of embers and smoldering
fires even in adverse environments.
ADICOS AAB-L serve as wiring aids for ADICOS detectors.
They are are large, high-quality surface-mounted junction boxes with
internally pre-connected double-pole terminals, which enable the electrical
connection of ADICOS detectors of all models to the special fire alarm system
in a very simple way.
Thanks to their robust mechanical design, the branch boxes are protected
against the ingress of dust and moisture and can be installed and used in
harsh industrial environments in the vicinity of the ADICOS detectors.
Features
- High quality distribution box made of stainless steel
- Spacious design
- Simple assembly thanks to offset fastening straps
- Maximum moisture and dust resistance
- Optimum wiring conditions thanks to large connection space, wiring channel inside the housing, high-quality and internally pre-wired double-level terminals
- Connection of supply voltage, M-Bus, external fire alarm LOOP as well as alarm and fault contact
- Power supply terminals for external power supply unit
- Up to eight cable glands (4 x M20 pre-mounted, further 4 x M25 enclosed)
About this Manual
Objective
This manual describes the proper assembly, wiring, commissioning, and
operation of ADICOS junction boxes AAB-L.
Once the device has been successfully started up, this document serves as a
reference in the event of malfunctions.
It is intended to be used only by properly qualified personnel (see Chap. 2
Safety Instructions).
Operational objectives
Operational objectives specify the result to be achieved by following the
subsequent instructions.
Operational objectives are shown in bold print.
Instructions
Instructions are the steps to be taken in order to achieve the previously
stated operational objective.
Instructions appear like this
► Indicates a single instruction
- First of a series of instructions
- Second of a series of instructions
- etc.
Intermediate states
When it is possible to describe intermediate states or events resulting from
the instruction steps (e.g. screens, internal function steps, etc.), they are
shown like this:
Intermediate state
Explanation of Symbols
This manual follows a certain structure to make it easy to work with and
understand.
The following designations are used throughout.
Warnings
The following types of notes are used through this manual:
| DANGER:
This combination of symbol and signal word indicates an immediately dangerous
situation which could lead to death or severe injuries if it is not avoided.
---|---
| WARNING:
This combination of symbol and signal word indicates a possibly dangerous
situation which could lead to death or severe injuries if it is not avoided.
| Tips and recommendations
This type of note provides information that is directly relevant for the
further operation of the device.
Abbreviations
This manual uses the following abbreviations:
Abbreviation | Meaning |
---|---|
ADICOS | Advanced Discovery System |
AAB-L | ADICOS Junction box – Large version |
M-BM | ADICOS M-BUSMASTER |
NT | ADICOS Power Supply NT V40-A3 |
FDnet | Field Device Network (fire alarm bus of SIEMENS fire alarm systems) |
LSNi | Local Security Network (fire alarm bus of BOSCH fire alarm systems) |
BMA | Fire Detection System (Brandmeldeanlage) |
Storing the Manual
Store this manual easily reachable and in direct vicinity of the system to
enable use as needed.
Safety Instructions
When properly installed, started up, operated and serviced, ADICOS junction
boxes AAB-X22/ X2 ensure operational safety at your facility.
But it is imperative that the manual, including all safety notes, be read,
understood and followed completely.
| WARNING:
Personal injury and property damage!
Incorrect installation and operating errors can cause death, serious injury
and damage to industrial equipment.
- Read the entire manual and follow the instructions!
---|---
Intended Use
ADICOS AAB-L are junction boxes for the electrical connection of ADICOS
detectors with the fire alarm cable of ADICOS systems.
They additionally enable feeding-in an external voltage supply using the
ADICOS power supply NT V40-A3.
In this context, the operating parameters described in Chap. 10, »Technical
data« must be met.
Compliance with this manual as well as all applicable country-specific
provisions is also part of the intended use.
Standards and Regulations
The current safety and accident prevention regulations relevant to the
specific application must be complied with when installing, starting up,
servicing and inspecting the AAB-L.
The following standards and directives are of particular importance when
handling fire alarm systems in potentially explosive areas:
Regulation | Description |
---|---|
VDE 0100 | Erection of power installations with rated voltages below 1000 V |
VDE 0800 | Telecommunications – General concepts – Requirements and tests for |
the safety of facilities and apparatus
VDE 0833| Alarm Systems for Fire
VDE 0845| Protection of telecommunication systems against lighting,
electrostatic discharges and over voltages from electric power installations;
measures against over voltages
VdS 2095| Guidelines for automatic fire detection and fire alarm systems –
planning and installation
DIN 14675| Fire detection and fire alarm systems – design and operation
Personnel Qualification
Any work on ADICOS AAB-L may only be performed by qualified personnel.
Persons, who can perform work on electrical systems and recognize possible
dangers based on their professional education, knowledge, and experience as
well as knowledge of the applicable provisions, are considered qualified
personnel.
| WARNING:
Personal injury and property damage!
Improperly performed work on and with the device can lead to malfunctions.
- Installation, startup, parameterization and maintenance may be performed only by authorized and properly trained personnel.
---|---
Modifications
| WARNING:
Property damage or detector failure by any form of unauthorized
modification!
Any form of unauthorized modification or extension can lead to a failure of
the detector system.
The warranty claim expires.
- Never make unauthorized modifications on your own authority.
---|---
Accessories and Spare Parts
| WARNING:
Property damage due to short circuit or failure of the detector system
The use of parts other than the manufacturer’s original spare parts and
original accessories may result in property damage due to short circuits.
- Only use original spare parts and original accessories!
- Original spare parts and accessories may only be installed by trained specialist personnel.
- Qualified personnel are persons as described in Chap. 2.3
---|---
Cable glands and blanking glands can be purchased from the manufacturer in M20 and M25 threads.
Scope of Delivery
The following components are included in the scope of delivery of the
AAB-L:
Number | Description |
---|---|
1 | ADICOS AAB-L with 4 cable glands M20 and 4 dummy cable glands M25 |
4 | Cable glands M25 |
4 | Blind glands M20 |
Structure
Overview
No. | Description |
---|---|
1 | Enclosure cover with ground cable (not shown) |
2 | Enclosure screws (4x) |
3 | Wiring duct cover |
4 | Enclosure base |
5 | M20 cable glands with locknuts (4x) |
6 | Mounting brackets (4x) |
7 | M25 blind glands with locknuts (4x) |
8 | Wiring duct with breakout ribs |
9 | Preconnected double deck terminals |
Connections
Column | Line | Label | Assignment |
---|---|---|---|
1– 3 | A + D | +24V | Power supply (+) |
1– 3 | B + C | 0V | Power supply (–) |
4–5 | A + D | **LOOP A | |
** → | External Fire Detection System LOOP A in SIEMENS FDnet + BOSCH LSNi a in | ||
4–5 | B + C | **LOOP B | |
** → | External Fire Detection System LOOP B in SIEMENS FDnet-A (–) BOSCH LSNi |
b1 in
6–7| A + D| LOOP A
←| External Fire Detection System LOOP A out SIEMENS FDnet + BOSCH LSNi a
out
6–7| B + C| LOOP B
←| External Fire Detection System LOOP B out SIEMENS FDnet-B (–) BOSCH LSNi
b2 out
8| A + D| X6e| Input limit value contact Alarm NO
8| B + C| X6a| Output limit value contact Alarm NO
9| A + D| X7e| Input limit value contact Fault NC
9| B + C| X7a| Output limit value contact Fault NC
10– 12| A + D| M-BUS A| ADICOS M-Bus
10– 12| B + C| M-BUS B| ADICOS M-Bus
13– 15| A + D| SHIELD| Cable shielding / PE of external power
supply
13– 15| B + C| |
Installation
Selecting the Mounting Location
The following aspects must be considered when selecting the installation
location:
- the installation floor must be sufficiently firm and as vibration-free as possible.
- the installation environment must meet the climate conditions specified in the technical data.
- install the AAB-L near to the connected detector and well accessibly.
Mounting
Mounting the AAB-L
- Depending on the underground, drill mounting holes for sufficiently dimensioned screws and/or wall plugs (4x) (see drilling plan)
- Press in the plugs
- Insert sufficiently dimensioned mounting screws through mounting brackets in the enclosure base (4x)
- Place precisely the enclosure base with the screws onto the mounting holes with wall plugs
- Tighten the screws (4x)
Wiring
| WARNING:
Malfunctioning and failures of the detector system!
Incorrect installation of the ADICOS AAB-L can cause malfunctioning, leading
to failure of the fire detection system.
- Wiring may only be performed by specialist personnel! (–› Chap. 2.3, Personnel Qualification)
- Use ADICOS connection cables for detector wiring only!
- Only use suitable fire alarm cables for the ADICOS primary line and BMALOOP!
---|---
The wiring plan of the AAB-L varies depending on system configuration and
topology.
The following procedure applies for all wiring variants.
Wiring ADICOS AAB-L
-
Open enclosure cover
-
Open cable glands
-
Route cables through the cable glands into the enclosure
-
Strip wire ends 8 … 10 mm strip insulation
-
Connect the cores to the terminals according to the wiring diagram.
To do this, press the stripped wire end firmly into the connection holes of the terminals -
Close cable glands
-
Close enclosure cover
In the case of wiring variants with more than four cables:
Installing additional cable glands
- Open enclosure cover
- Loosen M25 blind cable glands and lock nuts
- Mount supplied M25 cable glands with locknuts in holes (tightening torque 12.0 Nm)
ADICOS M-BM and external power supply red black
Fire Detector Loop with FDnet/LSNi (internal fire panel interface)
| Tips and recommendations
For integration in BOSCH or SIEMENS fire alarm systems, ADICOS detectors must
be equipped with an interface module by the manufacturer!
---|---
Other fire detector bus systems (external interface)
| Tips and recommendations
For integration in other Non-ADICOS fire alarm systems suitable external
interface modules are required.
---|---
Primary cable shielding
Commissioning
Wiring according to chapter 5.3.
| WARNING!
Equipment damage!
ADICOS systems work with electrical current, which can cause equipment damage
if not installed properly.
- Before switching on the system, verify that all components are properly mounted and wired.
- Commissioning may be performed only by properly trained personnel.
(See Chap. 2.3 Personnel Qualification)
---|---
| Tips and recommendations
The ADICOS AAB-L is a passive component. Separate commissioning is not
required.
Operation
| Tips and recommendations
The ADICOS-AAB-L is a passive component.
Its operating state depends on the superordinate central unit.
---|---
Maintenance
In general the ADICOS AAB-L does not require special maintenance.
Disposal
Return the product to the manufacturer after the end of the useful life.
The manufacturer ensures environmental friendly disposal of all components.
Technical Data
General information
Model| | AAB-L
Article No.| | 430-2002-039
Dimensions (W x H x D)| mm| 200 x 200 x 120
Weight| kg| 2.75
Degree of protection| | IP66
Enclosure| | Stainless steel junction box
Installation| | Surface-mounted
Cable gland tightening torque| Nm| 12.0
Electrical properties
Cable diameter M20 glands| mm| 7 … 13
Cable diameter M25 glands| mm| 9 … 17
Max. cable cross-section| mm²| 4
Nominal cross-section| mm²| 2.5
Environmental conditions
Permissible environment temperature| °C| -10 … +50
Relative humidity| %| ≤ 95 (non-condensing)
Installation environment| | vibration-free
ID Plate
Model| Device model| SERIAL| Serial number (variable)| YR| Year of production
(variable)
---|---|---|---|---|---
ART-Nr| Article number (variable)| TEMP| Ambient temperature| IP| Degree of
protection
COM
Nr.| Communication number (variable)| VDC/VA| Voltage range / maximum power
consumption| Is| Internal fusing (Short-circuit current)
CE marking|
CUSTOMER SUPPORT
Junction Box AAB-L
Article number: 430-2410-004-EN-12
Release date: 10.03.2023
Manufacturer:
GTE Industrieelektronik GmbH
Helmholtzstr. 21, 38-40
41747 Viersen
GERMANY
Support hotline: +49 2162 3703-0
E-Mail: support.adicos@gte.de