GTE GSME-M4 ADICOS GSME Industrial Fire Detection
- June 11, 2024
- GTE
Table of Contents
GTE GSME-M4 ADICOS GSME Industrial Fire
Product Information
The Industrial Fire Detection GSME-M4 is a device manufacturedby GTE Industrieelektronik GmbH that can be integrated into firealarm systems of common manufacturers. It has a multi-evaluation system with 4 sensors and is EN54 certified. The device is designedfor use in industrial environments and has an IP64 rating, which means it is protected against dust and water spray from any direction. The product comes with an operating manual that includes instructions for mounting and wiring the device.
Product Usage Instructions
Objective: To mount and wire the Industrial Fire Detection GSME-M4.
Mounting
- Choose a mounting location that is suitable for the device’s IP64 rating and that allows for proper detection coverage.
- Use the mounting template provided in the operating manual to mark the location for the mounting holes.
- Drill the holes and insert the wall anchors.
- Align the device with the mounting holes and secure it in place using screws.
Wiring
- Refer to the wiring diagram provided in the operating manual to ensure correct wiring.
- Connect the power supply wires to the device’s power terminals, following the polarity markings.
- Connect the communication wires to the device’s communication terminals, following the wiring diagram.
- Connect the sensor wires to the device’s sensor terminals, following the wiring diagram.
- Secure all wire connections using cable ties or wire connectors.
Note: It is recommended to consult a qualified electrician for proper installation and wiring of the Industrial Fire Detection GSME-M4.
Industrial Fire Detection
GSME-M4
EN
IP64
Operating Manual
Fire Gas Detector GSME®
GTE Industrieelektronik GmbH | Helmholtzstr. 21, 38 40 41747 Viersen | Germany | +49 2162 3703-0 | info@gte.de
Fire Gas Detector GSME – Operating manual Article number: 405-2010-003 Index:
EN54 Release date: 10.01.2023 Translation
Manufacturer: GTE Industrieelektronik GmbH Helmholtzstr. 21, 38-40 41747
Viersen GERMANY
Support hotline: +49 2162 3703-0 E-Mail:
support.adicos@gte.de
© 2023 GTE Industrieelektronik GmbH This document and all figures contained
may not be copied, changed, or distributed without explicit approval by the
manufacturer! Subject to technical changes!
ADICOS® and GSME® are registered trademarks of GTE Industrieelektronik GmbH.
ABSTRACT
Abstract
The Advanced Discovery System (ADICOS®) is used for early detection of fires
in industrial environments. It is comprised of various, separate detector
units. By parameterizing and arranging the detectors appropriately, the system
fulfills a predefined detection goal. The ADICOS system ensures reliable early
detection of embers and smoldering fires even in adverse environments.
GSME fire gas detectors detect at an early stage gases that are characteristic
for developing fires. They detect both open and concealed smoldering fires.
Highly sensitive and at the same time robust, they are ideal for fire gas
detection in industrial environments and already in the incipient stage.
Four parameterizable semiconductor gas sensors monitor and evaluate the
concentration curve of these gases according to multi-criteria technology.
This enables the GSME detectors to distinguish real fires from interference
signals. In industrial environments, this often occurs under harsh conditions,
e.g. due to vehicle exhaust fumes, dust, mist or vapor. With the ADICOS
software, all detector states and concentration curves can be displayed
graphically. Sensitivities as well as alarm thresholds can be parameterized
individually for each detector. The GSME fire gas detectors can be used in
almost any indoor plant area, taking into account the air flow conditions.
In case special interface modules are used, the devices can also be integrated
into fire alarm systems of common manufacturers and transmit their operating
status to the fire alarm control panel.
ADICOS GSME
405-2010-003 EN54
3
Contents
1 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 6 1.1 Objective. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.2 Explanation
of Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 6 1.3 Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 7 1.4 Storing the manual. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 8 2.1 Intended Use . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.2 Standards and
Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Personnel Qualification . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 9 2.4 Modifications . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 9 2.5 Accessories and Spare
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2.6
Handling outgassing adhesives, sealants and lubricants. . . . . . . . 9
3 Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . 10 3.1 Overview. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.1.1
Detector and add-on parts . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 10 3.1.2 Detector components. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 11 3.2 Display Elements . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 12 3.3 Circuit Board
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.4 Cable Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 13 3.5 Sintered metal filter and sensors . . . . . . . . .
. . . . . . . . . . . . . . . . . . 14 3.6 Spray protection . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . 15 4.1 Detection . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 4.1.1
Detection variables and cross-sensitivities . . . . . . . . . . . . . . . . .
15 4.1.2 Configuration and evaluation. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 16 4.2 LED Signals. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . 19 4.3 Signal Relays . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.4 Detector Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 20 4.5 ADICOS M-Bus. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . 20
5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . 21 5.1 Installation Location. . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 5.1.1
Protection aspects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 21 5.1.2 Detection aspects. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .22 5.2 Installation Orientation . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4
405-2010-003 EN54
ADICOS GSME
5.3 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 23 5.4 Wiring . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.4.1 Connecting a GSME detector with the connection cable . . . . . .24 5.4.2
Connecting the connection cable with the ADICOS AAB . . . . . . 25 5.4.3
Wiring variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .26 5.5 Retrofitting of Interface Modules for Fire Panels . .
. . . . . . . . . . . . 29 5.6 Replacing the Configuration Module . . . . . .
. . . . . . . . . . . . . . . . . . 30 6 Commissioning . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 7
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 32 7.1 Software Access . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 7.2 Alarm. . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 32 7.2.1 Resetting the alarm. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .32 7.2.2 Alarm holding time . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 7.2.3 Alarm
delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .33 7.2.4 Pre-alarm. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .33 8 Maintenance. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.1 Condensation and Contamination . . . . . . . . . . . . . . . . . . . . . .
. . . . 34 8.2 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 34 8.3 Function Test of the Signal
Relays . . . . . . . . . . . . . . . . . . . . . . . . . . 35 8.4 Annual
Function Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 35 8.5 Detector Replacement. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 35 8.5.1 Save inventory data . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .35 8.5.2 Prepare new unit
for use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
8.5.3 Replace detector. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .36 8.5.4 Update unit data . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . 37 8.5.5 Optimise alarm
thresholds (optional) . . . . . . . . . . . . . . . . . . . . . . 37 9 Fault .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 38 10 Disposal . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 11
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 39 11.1 ID Plate . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 12
Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 41 12.1 ADICOS Mounting Plate . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 41
ADICOS GSME
405-2010-003 EN54
5
About this mAnuAl
1 About this manual
1.1 Objective
This manual describes the special requirements on installation, wiring,
commissioning and operation of ADICOS detectors of the type “GSME”. After
commissioning, it is used as reference work in the case of faults. It is
intended to be used only by properly qualified personnel (> Chap. 2, For your
Safety).
1.2 Explanation of Symbols
This manual follows a certain structure to make it easy to work with and
understand. The following designations are used throughout.
Operational objectives Operational objectives specify the result to be
achieved by following the subsequent instructions. Operational objectives are
shown in bold print.
Instructions Instructions are the steps to be taken in order to achieve the
previously stated operational objective. Instructions appear like this
Indicates a single instruction
1 First of a series of instructions 2 Second of a series of instructions 3
etc.
Intermediate states When it is possible to describe intermediate states or
events resulting from the instruction steps (e.g. screens, internal function
steps, etc.), they are shown like this: Z Intermediate state
Warnings The following types of notes are used through this manual:
DANGER! This combination of symbol and signal word indicates an immediately
dangerous situation which could lead to death or severe injuries if it is not
avoided.
6
405-2010-003 EN54
ADICOS GSME
About this mAnuAl
WARNING! This combination of symbol and signal word indicates a possibly
dangerous situation which could lead to death or severe injuries if it is not
avoided.
CAUTION! This combination of symbol and signal word indicates a possibly
dangerous situation which could lead to minor injuries if it is not avoided.
NOTICE! This combination of symbol and signal word indicates a possibly
dangerous situation which could lead to property damage if it is not avoided.
Tips and recommendations This type of note provides information that is
directly relevant for the further operation of the device.
1.3 Abbreviations The following abbreviations are used through this manual:
Abbr. Meaning
ADICOS AAB GSME
Advanced Discovery System ADICOS Junction Box Gas Sensor Detector Unit
M4 Multi evaluation with 4 sensors
M-BM ADICOS M-Busmaster
NT ADICOS Power Supply NT V40-A3
FDnet Field Device Network (fire alarm bus of SIEMENS fire alarm systems)
LSNi Local Security Network (fire alarm bus of BOSCH fire alarm systems)
sb slow-blowing (fuse)
TF Test Fire ESD Electro Static Discharge EF Sensitivity Factor
NOX Nitrogen oxides H2 Hydrogen CO Carbon monoxide
HC Hydrocarbons
1.4 Storing the manual
Store this manual near the detectors, in a place where it can easily be
accessed when needed for reference.
ADICOS GSME
405-2010-003 EN54
7
sAfety instructions
Safety Instructions
When properly installed, started up, operated and serviced, ADICOS GSME
devices ensure operational safety at your facility. But it is imperative that
the manual, including all safety notes, be read, understood and followed
completely.
WARNING! Personal injury and property damage! Incorrect installation and
operating errors can cause death, serious injury and damage to industrial
equipment. · Read the entire manual and follow the instructions!
2.1 Intended Use
ADICOS GSME are point-type fire gas detectors for the detection of fire
scenarios in the industrial environment. They are exclusively intended for
operation within ADICOS systems. In this context, the operating parameters
described in Chap. 11, »Technical Data« must be met. Intended use also
includes following the instructions in this manual and complying with all
relevant local regulations. The ADICOS GSME may not be used for any other
purpose. If the device is used in any other way, or if changes are made to the
product, including in the course of installation and maintenance, the warranty
claim is no longer valid.
NOTICE Do not use for potentially explosive atmospheres! ADICOS GSME in their
standard version may not be installed in explosive atmospheres! Special GSME
variants are available for operation within explosive atmospheres.
2.2 Standards and Regulations
The safety and accident prevention regulations applicable for the specific application must be observed during detector installation, commissioning, test and maintenance.
The following standards and directives in their current version are of particular importance when handling fire detector systems:
Regulation VDE 0100 VDE 0800
VDE 0833 VDE 0845
VdS 2095
DIN 14675 DIN EN 54-7
Description
Erection of Power Installations with Rated Voltages below 1000 V
Telecommunications – General Concepts – Requirements and Tests for the Safety
of Facilities and Apparatus
Alarm Systems for Fire
Protection of Telecommunication Systems Against Lightning, Electrostatic
Discharges and Overvoltages From Electric Power Installations – Measures
Against Overvoltages
Guidelines for Automatic Fire Detection and Fire Alarm Systems Planning and
Installation
Fire Detection and Fire Alarm Systems – Design and Operation
Fire Detection and Fire Alarm Systems – Part 7: Smoke Detectors Point
Detectors Using Scattered Light, Transmitted Light or Ionization
8
405-2010-003 EN54
ADICOS GSME
sAfety instructions
2.3 Personnel Qualification Only properly trained and qualified persons may
work on ADICOS equipment. Qualified persons are those who have received
relevant professional training, have the required skills and experience and
who are aware of applicable regulations, enabling them to work on electrical
equipment and detect potential hazards.
WARNING! Personal injury and property damage! Improperly performed work on and
with the device can lead to malfuctions. · Installation, startup,
parameterization and maintenance may be performed
only by authorized and properly trained personnel.
2.4 Modifications
WARNING! Risk of property damage by any form of unauthorized modification! Any
form of unauthorized modification or extension can lead to a failure of the
detector system. The warranty claim expires. · Never make unauthorized
modifications on your own authority.
2.5 Accessories and Spare Parts
WARNING! Property damage due to short circuit or failure of the detector
system The use of parts other than the manufacturer’s original spare parts and
original accessories may result in property damage due to short circuits. ·
Only use original spare parts and original accessories! · Original spare parts
and accessories may only be installed by trained spe-
cialist personnel. · Qualified personnel are persons as described in Chap. 2.3
2.6 Handling outgassing adhesives, sealants and lubricants
NOTICE! Material damage due to the use of siloxanes Silicone-containing
hydrocarbons (siloxanes) damage the surface of the semiconductor gas sensors
of the ADICOS GSME. · Do not use any outgassing adhesives, sealants, or
lubricants
(e.g. silicone) in the surroundings of the detector!
ADICOS GSME
405-2010-003 EN54
9
71
structure 3 Structure 3.1 Overview 3.1.1 Detector and add-on parts
4
3
2 1
No. Description
19
18
17
16
GSME spray protection
15
14
13
12
11
10
GSME-M4
ADICOS connection cable
ADICOS mounting plate (optional)
10
405-2010-003 EN54
ADICOS GSME
3.1.2 Detector components
15
structure
14 13
1 2
3 4 5
9 8
12
11 10
6 7
No. Description Enclosure cover Enclosure screws (4x) Signal LED »Alarm«
Signal LED »Operation« Signal LED »Fault« Sintered metal filter Screw
connection for spray protection Main circuit board Semiconductor gas sensors
Circuit board screws (4x) Configuration module Lower enclosure part Detector
connection M5 mounting thread (on rear side, not shown) (4x) Connector for
detector connection
ADICOS GSME
405-2010-003 EN54
11
structure
3.2 Display Elements
Signal LEDs
vv
For indicating operating conditions, three light pipes are recessed in the
enclosure cover of the detector. They are used to visualize the signal LEDs
located on the detector board.
The top signal LED »Alarm« is red, the center »Operation« is green and the
bottom »Fault« is yellow.
For the function of the signal LEDs, see Chap. 4.2, »LED signals«.
3.3 Circuit Board Connections
Slot “detector connection”
The detector connection slot is a coded, 14-pin connector on the left side of
the detector board.
In the factory configuration, it is connected to the detector connection
(Amphenol bayonet plug-in coupling) in the lower enclosure part.
vv
Slot “configuration module”
The configuration module slot is a coded, 16-pin connector on the right side
next to the detector connection slot and underneath the signal relay on the
detector board.
Depending on the order configuration the slot is equipped with a configuration
module, on which the resistors for the limit value contacts is defined.
vv
Slot “interface module”
The interface module slot is a coded, 10-pin connector above the gas sensors
on the detector board.
Depending on the ordered configuration, it is eqiupped in the factory configuration with an interface module board, which enables integration of the detector in external fire alarm systems.
As an alternative, the pre-alarm module can be inserted here.
(Fig. Interface module)
vv
12
405-2010-003 EN54
ADICOS GSME
structure
Slots “fuses” There are two slots for fuses at the bottom left on the detector
board. These are marked with labels F201 and F203. In the factory
configuration, the fuse slots are equipped with one slow burning 500 mA fuse
each.
vv
3.4 Cable Assignment
Color
red black yellow white brown green pink blue purple gray blue/red gray/pink
Signal
Operating voltage 21.6 … 40 V DC non-polarized
Relay output X6 e Relay output X6 a Relay output X7 a Relay output X7 e Fire
panel interface B-in Fire panel interface A-in Fire panel interface B-out Fire
panel interface A-out M-Bus max. 40 V non-polarized
Potential-free contact
Alarm (NO)1 Alarm (NO)1 Failure (NC)1 Failure (NC)1 Auxiliary assembly
(optionally in factory configuration)
1 with series resistor
ADICOS GSME
405-2010-003 EN54
13
structure
Coupling module option
Color
pink blue purple gray
Signal
Coupling module B-in Coupling module A-in Coupling module B-out Coupling
module A-out
Option auxiliary relay
Color blue purple gray
Auxiliary relay
Normally closed Normally open Common
Siemens FDnet
FDnet-A () FDnet (+) FDnet-B () FDnet (+)
BOSCH LSNi LSN b1 in LSN a in LSN b2 out LSN a out
3.5 Sintered metal filter and sensors
The sintered metal filter (> Chap. 3.1.2) is the central element on the
detector front. It is screwed into the enclosure cover and contains a
continuous element made of sintered metal granules. The fire gases to be
detected can diffuse through the pores of this sintered metal and reach the
gas sensors located behind, while dust and moisture cannot penetrate the
inside of the detector. Thus, the sensors are protected from environmental
influences, but can be reached by fire gases.
3.6 Spray protection
The spray protection (> Chap. 3.1.1) is a mechanical add-on for the ADICOS
GSME. It is bolted onto the sintered metal filter and reduces the risk of
condensation in the sensor area and offers a certain protection from drip and
spray water in the installation environment.
14
405-2010-003 EN54
ADICOS GSME
function
Function
During operation, the ADICOS GSME monitors the signals of its gas sensors and triggers an alarm according to the set limit value combinations. If an ADICOS central unit (ADICOS M-BUSMASTER) is used, the detector transmits additionally all sensor and operating data to be displayed in the ADICOS System Software via M-Bus (> Chap. 4.5). If the detector is connected to a fire alarm panel using an integrated interface module, the alarm display of the detector is controlled by the central fire alarm panel.
4.1 Detection
The ADICOS GSME is equipped with four semiconductor gas sensors that can
provide four differnt detection signals depending on actuation and evaluation.
4.1.1 Detection variables and cross-sensitivities
Phys. sensor Index Detection variable
Cross-sensitivity
Sensor 1
Sensor 2 Sensor 3 Sensor 4
0 Phenolic hydrocarbons (HC) 4 Nitrogen oxides (NOx) 1 Carbon monoxide (CO) 2
Hydrogen (H2)
3 Phenolic hydrocarbons (HC) 5 Nitrogen oxides (NOx)
Hydrogen, alcohols Ozone, phenols Hydrogen, alcohols -/Ozone, amines Ozone, ammonia
The specified cross-sensitivities represent an exemplary selection. Cross- sensitivities must also be expected in the case of high concentrations of other gases.
ADICOS GSME
405-2010-003 EN54
15
function
4.1.2 Configuration and evaluation
The ADICOS GSME is characterized by its particular intelligence and
flexibility during signal detection and evaluation. The detector electronics
does not only investigate the concentrations of individual fire gases, but
considers the relations of the detection concentrations as well. These
relations are configured through limit value combinations. Every detector
features two sets with five limit value combinations each.
In the factory configuration, every detector is equipped with a basic
configuration of meaningful alarm parameters. At first, both parameters have
identical default values. For this reason, one set of limit value combinations
is described only in the following sections. The second parameter set is of
particular importance, e.g., when a pre-alarm module is used (> Chap. 7.2.4).
Basic configurations »Standard«, »Extended 1«, »Extended 2« and »Robust« are
currently available. Depending on the application, an individual basic
configuration is possible upon request. The following table shows the
suitability of the basic configurations for typical detection objectives.
Typical detection objective Smoldering wood fire (TF2) Smoldering cotton fire
(TF3) Flaming PU fire (TF4) Flaming n-heptane fire (TF5) Smoldering lignite
fire Smoldering bituminous coal fire Smoldering wood chip fire
1. Ignition phase 2. Propagation phase 3. Full ember Smoldering
plastic/rubber 1. Phase: Steam 2. Phase: Pyrolysis 3. Phase: Ember
Standard
Basic configuration
Extended 1 Extended 2
Robust
Suitable (*tested per EN 54-7)
Suitable
Suitable with low sensitivity
Suitable within compact, non-vented enclosures (e.g., silos)
16
405-2010-003 EN54
ADICOS GSME
function
4.1.2.1 Basic configuration “Standard”
In the “Standard” basic configuration, the following limit values are set as
default during factory configuration.
Index
Detection variable
1
Limit value combination
2
3
4
5
2
H2
9
HC
5
10
0
5
0
25
3
1
CO
40
20
20
15
5
10
NOX
10
*The limit values approx. correspond to the concentrations in ppm for hydrogen and carbon monoxide. However, as the particles to be detected are often present as aerosols, the limit values should rather be considered as characteristics without dimensions. In addition, the function for automatic zero-point adjustment leads to a discrepancy between parameter and actual concentration.
Zero-point adjustment
To prevent incorrect displaying due to sensor aging, the “Standard” basic
configuration features sliding zero-point adjustment of the sensor signals.
However, the longtime constant of this zero-point adjustment of 6 hours also
hides slowly increasing signal backgrounds.
Smoldering fires that develop over a timeframe of days, cannot be detected in the “Standard” basic configuration!
4.1.2.2 Basic configuration “Extended 1”
In the “Extended 1” basic configuration, the following limit values are set as
default during factory configuration.
Index
Detection variable
1
Limit value combinations
2
3
4
5
3
HC
5
10
3
5
0
HC
5
3
1
CO
40
20
15
15
10
NOX
ADICOS GSME
405-2010-003 EN54
17
function
4.1.2.3 Basic configuration “Extended 2”
In the “Extended 2” basic configuration, the following limit values are set as
default during factory configuration.
Index
Detection variable
1
Limit value combinations
2
3
4
5
2
H2
9
HC
50
20
0
3
25
10
1
CO
20
80
20
30
10
NOX
4.1.2.4 Basic configuration “Robust”
In the “Robust” basic configuration, the following limit values are set as
default during factory configuration.
Index
Detection variable
1
Limit value combinations
2
3
4
5
2
H2
9
HC
90
90
50
50
10
20
1
CO
40
20
50
20
10
NOX
The “Robust” basic configuration is exclusively suited for operation within closed, non-vented enclosures (e.g. silos or bunkers)! The free volume within the enclosure should not exceed 10 m³!
4.1.2.5 Basic configuration “Individual”
If an application environment requires limit value combinations deviating from
the “Standard”, “Extended” and “Robust” basic configurations, a set of
individual limit value combinations can be programmed as factory configuration
upon request. In such cases, the basic configuration is referred to as
“Individual”.
18
405-2010-003 EN54
ADICOS GSME
function
4.1.2.6 Customized configuration changes
Using the ADICOS System Software, all limit values of the ADICOS GSME can be
change independently from the delivered basic configuration. If the limit
values of the basic configuration are replaced with freely selected limit
values, an individual detector configuration is chosen.
CAUTION! Ineffectiveness due to incorrect parameterization Faulty limit value
combinations can lead to complete ineffectiveness of the detector! · The
detector parameters may only be changed by experienced specialist
personnel!
4.2 LED Signals
The current operating condition of the detector is indicated by three signal
LEDs on the front of the detector. The following table explains the
illumination states.
LED
State
Function
green flashing
Initialization /not ready for operation yet
on
Normal operation
off yellow on
Detector system off/detector, fuse, or cable defective Detector fault
off with fire panel module:
Normal operation
red
off
Normal operation
on
Alarm to central fire alarm panel
flashing
Detector alarm, however, without central fire alarm panel alarm
with pre-alarm module:
red
off
Normal operation
on flashing
Alarm Pre-alarm
without fire panel module:
red
off
Normal operation
on
Alarm
ADICOS GSME
405-2010-003 EN54
19
function
4.3 Signal Relays
The ADICOS GSME is equipped with two signal relays that signal the “Alarm” and
“Fault” states. The “Alarm” signal relay is realized as normally open contact,
the “Fault” signal relay as normally closed contact. The signal lines of the
signal relays are integrated into the ADICOS connection cable (> Chap. 3.4).
4.4 Detector Heating
In the factory configuration, the ADICOS GSME is equipped with an integrated
heating unit. It heats the detector enclosure and prevents condensation of
ambient humidity. Depending on the ordered configuration, it is already
activated with the basic configuration of the detector at the factory. During
operation, detector heating can be switched on and off via the ADICOS System
Software. The power consumption of detector heating is up to 10 VA.
In the case of undervoltage, detector heating is switched off automatically.
Once the undervoltage is corrected, heating becomes only active again after a
detector reset.
Beyond that, the heating function is limited through enclosure temperature
monitoring. If the pre-set maximum temperature (default: 40 °C) is exceeded,
the heating unit switches off automatically, until the enclosure temperature
is lowered again. In the case of a very high ambient temperature and high air
humidity, it may thus be necessary to adjust the set limit temperature for the
heating function accordingly.
4.5 ADICOS M-Bus
The ADICOS M-Bus is a proprietary two-wire data line, which is used to
transfer all detector parameters as well as operating and detection data. With
the help of the ADICOS System Software this data is displayed and archived.
Furthermore the parameters of each connected detector can be adjusted.
The M-Bus lines are integrated into the ADICOS connection cable (> Chap.
3.4).
20
405-2010-003 EN54
ADICOS GSME
instAllAtion
Installation
WARNING! Danger of malfunction and failure of the detector system Improper
installation of ADICOS detectors can lead to faults and failures of the
detector system. · Installation work may only be performed by specialist
personnel! (> Chap.
2.3, Personnel qualification)
5.1 Installation Location
DANGER! Explosion danger in potentially explosive atmospheres ADICOS GSME in
their standard version may not be installed in explosive atmospheres! · Only
use approved GSME variants for operation within explosive atmo-
spheres!
NOTICE! Correct alignment Arrangement and alignment of ADICOS detectors are
highly important for a reliable detection. Unfavorable placement can lead to
complete ineffectiveness of the detector! · Only experienced specialist
planners may define detector position and
alignment!
5.1.1 Protection aspects
The following aspects must be considered when selecting the installation
location to ensure fault-free operation of the ADICOS GSME detector.
Temperature The ambient temperatures at the planned installation location must
not exceed and/or undercut the specified temperature range (> Chap. 11) of
the ADICOS GSME detector even in the worst-case scenario. Special attention
must be paid to the waste heat of heating-up system components in the
surroundings. Intensive solar irradiation should be avoided as well.
Condensation and contamination The ADICOS GSME detector is basically suited
for operation in dust-loaded environments (not in explosive atmospheres). In
the case of condensation or permanent contact with damp or oil-containing
dusts, the sintered metal filter can be clogged. This reduces the detectivity
of the detector and can lead to ineffectiveness. In the case of condensation,
detector heating and spray protection must be used. Beyond that, the sintered
metal filter must be regularly checked for incrustation.
NOTICE! Danger of sensitivity loss and failure of the detector system In dust
environments with simultaneous high humidity, the functionality of the
sintered metal filter may be impaired. · In case of high dust exposure in
combination with high air humidity, contact
the manufacturer for consultation!
ADICOS GSME
405-2010-003 EN54
21
instAllAtion
Moisture
If drip or spray water is to be expected in the planned installation
environment, direct contact with the sintered metal filter must be prevented.
This also applies in the case of regular building cleaning with water. Spray
protection must be used in the case of moisture!
Vibration
Strong vibrations can damage the electronics of the ADICOS GSME detector. If
strong vibration sources can be found in the surroundings of the planned
installation location, the detector must be positioned such that it is
protected from vibrations.
Sensor toxins
Silicone-containing hydrocarbons (siloxanes) can oxidize and thus damage the
surface of the semiconductor gas sensors of the ADICOS GSME detector. No
outgassing adhesives, sealants and lubricants (e.g., silicone) may be used in
the surroundings of the detector.
Electromagnetic radiation Electromagnetic radiation can impact the electronics
of the ADICOS GSME detector. Do not mount the detector in the immediate
surroundings of power current equipment. Use shielded cables only.
5.1.2 Detection aspects
The following aspects must be considered when selecting the installation
location to ensure reliable and sensitive operation of the ADICOS GSME
detector.
Building geometry and air flow The way fire gases propagate depends on
numerous factors and is far less intuitive as generally assumed. It is thus
difficult inside industrial systems with complex building geometry, possibly
with ventilation systems and machines generating waste heat. There it is a
particular challenge to ensure that the gas emissions from a smoldering fire
reach the detector’s sensors in sufficient concentration.
Thus, all influencing factors of the air flow within the building must be
considered when defining the installation locations for ADICOS GSME detectors.
It may be necessary to perform a fire test at the location of the expected
fire source to identify these factors.
False variables Different false variables can negatively impact the detector
function and lead to false alarms and sensor aging. No exhaust gases e.g. from
conveyor vehicles or fermentation gases from biological or thermal
decomposition must be present at the planned installation location.
22
405-2010-003 EN54
ADICOS GSME
instAllAtion
5.2 Installation Orientation
NOTICE! Property damage due to incorrect installation A sintered metal filter
clogged with dust deposits reduces the detectivity of the detector and can
lead to ineffectiveness! Water accumulation on the filter can damage the
detector. · Mount the detector with the sintered metal filter pointing
downward! · Use heating if humidity is present!
5.3 Mounting
The ADICOS GSME detector features four M5 threaded holes for mounting. They
can be found on the rear of the enclosure.
Mounting the GSME
1 Bolt the ADICOS mounting plate (> Chap. 12.1) using M5 countersunk screws
(included in the scope of delivery of the mounting plate) on the rear of the
detector enclosure
For ceiling mounting:
2 Drill four mounting holes arranged in a square at a distance of 130 mm
3 Press dowels into the mounting holes 4 Attach mounting plate including
detector using suitable
screws
For any other mounting location (e.g., gallows construction):
2 Bolt mounting plate including detector to the gallows construction using
suitable M6 screws, nuts and lock washer
ADICOS GSME
405-2010-003 EN54
23
instAllAtion
5.4 Wiring
NOTICE! Faults and failures of the detector system by improper wiring!
Incorrect wiring of ADICOS detectors can lead to faults and failures of the
detector system. · Wiring may only be performed by specialist personnel! (>
Chap. 2.3, Per-
sonnel qualification) · De-energize the entire detector system for any wiring!
· Use ADICOS connection cables only for connecting detectors as well as
ADICOS junction boxes!
5.4.1 Connecting a GSME detector with the connection cable
1 Push the bayonet plug-in coupling of the ADICOS connection cable against the
detector connection
2 Carefully turn the entire bayonet plug-in coupling to find the correct
orientation of the anti-rotation protection
3 Turn the bayonet ring of the coupling forcefully to attach cable
24
405-2010-003 EN54
ADICOS GSME
instAllAtion
5.4.2 Connecting the connection cable with the ADICOS AAB Depending on the
system and detector configuration, the specific wiring of the ADICOS
connection cable and the ADICOS branching and connection box (ADICOS AAB)
varies. The following procedure applies for all wiring variants.
A
A
Wiring the ADICOS AAB 1 Open the enclosure cover of the ADICOS AAB 2 Open the
lower cable gland of the ADICOS AAB 3 Route the ADICOS connection cable
through the lower cable gland into the ADICOS AAB 4 Connect the wires to the
connection terminals of the ADICOS AAB according to the wiring
diagram 5 Close the cable gland of the ADICOS AAB 6 Close the enclosure cover
of the ADICOS AAB
Further information on the installation of the ADICOS junction box can be
found in ADICOS instructions no. 430-2410-001!
ADICOS GSME
405-2010-003 EN54
25
instAllAtion
5.4.3 Wiring variants
Specific wiring of the detectors with the ADICOS branching and connection
boxes varies depending on the system configuration. The following wiring
diagrams outline the most frequent system configurations and/or wiring
variants.
ADICOS M-Bus and external power supply
ADICOS M-BUSMASTER
+ (24V) – (24V)
M-Bus M-Bus
ADICOS ext. power supply
NT V40-A3
0 V +40 V
+24 V 0V
M-Bus A M-Bus B
B1 A1 B2 A2 X6e X7e X6a X7a
+24 V 0 V
X7 (Stoer) X6aus (Al) X6ein (Al) LOOP B LOOP A M-Bus A M-Bus B
0 V +24 V
PE PE
ADICOS-AAB
+24 V 0 V
X7 (Stoer) X6aus (Al) X6ein (Al) LOOP B LOOP A M-Bus A M-Bus B
next ADICOS-AAB
red black yellow green white brown pink blue violet grey blue/red grey/pink
ADICOS connection cable / detector
26
405-2010-003 EN54
ADICOS GSME
Limit value detection lines “Fault” and “Alarm”
Non-ADICOS fire alarm panel
Fault Alarm Alarm
+24 V 0 V
X7 (Stoer) X6aus (Al) X6ein (Al) LOOP B LOOP A M-Bus A M-Bus B
0 V +24 V
PE PE
ADICOS-AAB
+24 V 0 V
X7 (Stoer) X6aus (Al) X6ein (Al) LOOP B LOOP A M-Bus A M-Bus B
instAllAtion
next ADICOS-AAB
At the end of the line: 3k3
Terminating resistor wire break detection
+24 V 0V
M-Bus A M-Bus B
B1 A1 B2 A2 X6e X7e X6a X7a
red black yellow green white brown pink blue violet grey blue/red grey/pink
ADICOS connection cable / detector
External fire alarm LOOP with LSN / FDnet (internal interface module)
FDnet/LSNi
fire alarm panel
LOOP B LOOP A
+24 V 0 V
X7 (Stoer) X6aus (Al) X6ein (Al) LOOP B LOOP A M-Bus A M-Bus B
0 V +24 V
PE PE
ADICOS-AAB
+24 V 0 V
X7 (Stoer) X6aus (Al) X6ein (Al) LOOP B LOOP A M-Bus A M-Bus B
next ADICOS-AAB
+24 V 0V
M-Bus A M-Bus B
B1 A1 B2 A2 X6e X7e X6a X7a
red black yellow green white brown pink blue violet grey blue/red grey/pink
ADICOS GSME
ADICOS connection cable / detector
405-2010-003 EN54
*Detector with integrated FDnet- or LSNi-Module
27
instAllAtion
External fire alarm LOOP with other bus (external coupling module)
Non-ADICOS
fire alarm bus
LOOP B LOOP A
External connection module
Fault ,Fault Alarm Alarm
LOOP B LOOP A
LOOP B LOOP A
+24 V 0 V
X7 (Stoer) X6aus (Al) X6ein (Al) LOOP B LOOP A M-Bus A M-Bus B
0 V +24 V
PE PE
ADICOS-AAB
+24 V 0 V
X7 (Stoer) X6aus (Al) X6ein (Al) LOOP B LOOP A M-Bus A M-Bus B
next ADICOS-AAB
+24 V 0V
M-Bus A M-Bus B
B1 A1 B2 A2 X6e X7e X6a X7a
red black yellow green white brown pink blue violet grey blue/red grey/pink
ADICOS connection cable / detector
Primary cable shielding
Primary cable
+24 V 0 V X7 (Stoer) X6aus (Al) X6ein (Al) LOOP B LOOP A M-Bus A M-Bus B
0 V +24 V
PE PE
ADICOS-AAB
+24 V 0 V X7 (Stoer) X6aus (Al) X6ein (Al) LOOP B LOOP A M-Bus A M-Bus B
Primary cable
+24 V 0V M-Bus A M-Bus B B1 A1 B2 A2 X6e X7e X6a X7a
28
405-2010-003 EN54
ADICOS GSME
instAllAtion
5.5 Retrofitting of Interface Modules for Fire Panels
NOTICE! Property damage due to electrical voltage! Detector electronics and
interface modules are sensitive assemblies, which can be damaged on contact
due to electrostatic discharge. · De-energize the entire detector system for
any wiring and secure against
unintentional reactivation! · Apply ESD measures when working on the detector
electronics! · Do not touch electronic components!
The electronics of the ADICOS GSME features a slot for interface modules.
Depending on the ordered configuration, the detector electronics is populated
with the necessary module in the factory configuration. However, interface
module retrofits are required on site in special cases. In addition to the
electrical installation, it must be observed that a configuration change of
the detector using the ADICOS System Software is usually also required to use
the module functionalities.
Retrofitting the interface module
1 Using the SL/PH2 screwdriver, loosen the enclosure screws in the detector
cover The screws remain in the cover.
2 Carefully remove the enclosure cover with the detector electronics The plug
connector for detector connection remains connected.
3 Insert the interface module into the module slot on the detector board
4 Close the detector enclosure, required torque 1.5 Nm
ADICOS GSME
405-2010-003 EN54
29
instAllAtion
5.6 Replacing the Configuration Module
NOTICE! Property damage due to electrical voltage Electrical voltages can
cause damage to property. · De-energize the detector for any wiring and secure
against unintentional
reactivation! · Apply ESD measures when working on the detector electronics! ·
Do not touch electronic components!
The configuration module is a compact electronics module, which is populated
in the factory configuration in the configuration module slot of the detector.
It is used to define the resistances of the ralay contacts of the detector.
Configuration modules must be replaced on site in special cases.
Replacing the configuration module
1 Using the SL/PH2 screwdriver, loosen the enclosure screws in the detector
cover The screws remain in the cover.
2 Carefully remove the enclosure cover with the detector electronics The plug
connector for detector connection remains connected.
3 Carefully pull off the old configuration module 4 Insert the new
configuration module in the correct
orientation into the configuration module slot on the detector board 5 Close
the detector enclosure, required torque 1.5 Nm
30
405-2010-003 EN54
ADICOS GSME
commissioning
Commissioning
DANGER! Property damage due to electrical voltage! ADICOS systems work with
electrical current, which can cause equipment damage and fire if not installed
properly. · Before switching on the system, verify that all detectors are
properly
mounted and wired. · Startup may be performed only by properly trained
personnel.
WARNING! Risk of faults and failures of the detector system The degree of
protection of ADICOS detectors specified in the technical data is only
guaranteed when the enclosure cover is completely closed. Otherwise a false
alarm can be triggered or the detector can fail. · Before startup, check that
all of the detector enclosure covers are com-
pletely closed, ohterwiese the ADICOS system will not work properly.
The ADICOS detectors do not have to be started up individually. When the
ADICOS power supply unit is switched on, all of the detectors start
automatically.
The ADICOS detector indicates a malfunction until the startup process is
completed.
Supply voltage to the device to start up the ADICOS GSME.
Start up the ADICOS system as described in the manual for the M-Busmaster
interface unit used.
Z The approx. 5-minute start-up process starts automatically.
Z The green signal LED »Operation« flashes.
Z The yellow signal LED »Fault« illuminates continuously. The detector remains
in fault, until the end of the start-up process.
Z The detector electronics is initiated and all sensors are subsequently
heated to operating temperature.
Z Once the start-up process is completed, the signal LED »Operation«
illuminates green continuously and the yellow signal LED »Fault« goes off.
ADICOS GSME
405-2010-003 EN54
31
operAtion
Operation
During operation, the detector monitors the fire gas concentrations captured by the sensors per its basic configuration and triggers an alarm, when the set alarm limit values are exceeded. The query interval of the sensors amounts to 30 seconds.
7.1 Software Access
If a M-Bus interface is used, detailed detector information can be called up via the ADICOS M-Bus. For this purpose, a service PC with the ADICOS System Software connected to the ADICOS M-BUSMASTER is required.
TYPEANR
AdvancSEeRdIALDis°CGc0o0-v20e00r02y0T01Sa…y45s0Y0t/Re1m4I2P01I 7S 642x 0,5A
GS4M08E–2M0G40010-2000101 COM
GTE
/ VA V DC Industrieelektronik
GmbH
Using the communication number (COM or K.N.) printed on the type plate and the front of the detector, a single view of the detector can be called up in the software. Within this single view, the concentration profiles of the gas sensors can be called up as chart, for example. The alarm thresholds of the detector can be adjusted here as well.
COM-Nummer
Detailed information regarding the use of the ADICOS System Software as well as the specific approach to changing the detector settings is available upon request.
7.2 Alarm
If the gas concentrations detected by the detector sensors exceed the set
alarm thresholds, the detector triggers an alarm. The internal alarm relay is
activated and the red signal LED is illuminated (without fire panel module).
This status is also transmitted via the M-Bus.
If an alarm delay (see Chap. 7.2.3) has been set, the alarm is not triggered
until the alarm conditions have been met for longer than the set duration.
Fire Detection System Operation
If the detector is connected to a central fire alarm panel, the alarm is
transmitted to the central fire alarm panel via the interface module. The fire
panel switches the detector in alarm state and the alarm relay as well as the
red signal LED of the detector are switched on. If the fire panel does not
switch the ADICOS GSME into alarm state, the red signal LED flashes.
7.2.1 Resetting the alarm
The ADICOS GSME remains in alarm state, as long as the alarm condition is met.
The state is newly determined in every query cycle (30 seconds interval). As
soon as the alarm condition is not met, the alarm state is automatically
reset. Signal LED »Alarm« is only reset after a respective delay, if an alarm
holding time (> Chap. 7.2.2) is set.
32
405-2010-003 EN54
ADICOS GSME
operAtion
If the alarm LED is controlled via central fire alarm panel, the alarm state
can be reset via the alarm reset contact of the fire panel. Beyond that, an
alarm can only be reset via a detector reset, which is expressly discouraged.
7.2.2 Alarm holding time
The alarm holding time is an optional parameter that can be adjusted via the
ADICOS System Software. If set, the signal LED »Alarm« is only reset after a
respective delay after the alarm condition is not met anymore. By default, the
alarm holding time amounts to approx. 7.5 minutes.
7.2.3 Alarm delay
The alarm delay is an optional parameter that can be adjusted via the ADICOS
System Software. If set, the alarm state is only triggered, if the alarm
condition is met over the set minimum timeframe (in minutes).
NOTICE! Faulty parametrizing! Incorrect parameterization of the alarm delay
function can lead to ineffectiveness of the detector! · The detector
parameters may only be changed by experienced specialist
personnel! · In case of doubt, contact the manufacturer!
7.2.4 Pre-alarm
If the ADICOS GSME is equipped with a pre-alarm module and respectively
configured, set 2 of the limit value combinations (> Chap. 4.1) is
automatically evaluated as trigger criterion for the pre-alarm. If the limit
values from set 2 are exceeded, the pre-alarm module relay switches and the
red signal LED »Alarm« flashes.
ADICOS GSME
405-2010-003 EN54
33
mAintenAnce
8 Maintenance
The following maintenance measures must be performed in the specified cycle.
Measure
daily
Cycle quarterly
yearly
Check for fault message via fire panl and/or software (> Chap. 9, Fault)
Visual inspection for condensation on the detector enclosure (> Chap. 8.1, Condensation and contamination)
Visual inspection for damage on detector, attachment and connection cable
Visual inspection for pollution of the sintered metal filter (> Chap. 8.1, Condensation and contamination)
Function test of the “Alarm” and “Fault” signal relays (> Chap. 8.3, Function test of the signal relays)
Measurement of the supply voltage in the connection boxes (Permissible voltage range 21,6 … 40 V)
Function test with ADICOS GTL-3 GSME tester (> Chap. 8.4, Annual function test)
- Within the first three months after commissioning
8.1 Condensation and Contamination
Condensation on the detector enclosure, in particular in the area of the sintered metal filter, can lead to reduced sensitivity of the ADICOS GSME detector. If damp dusts form deposits on the detector, the sintered metal filter can become polluted, which leads to reduced detectivity or even ineffectiveness of the detector.
For this reason, condensation must be avoided under any circumstances. In the case of condensation, switch on detector heating and use spray protection! In addition, the sintered metal filter must be checked for pollution within the scope of quarterly maintenance as well as regularly within the first three months after commissioning.
8.2 Cleaning
In the normal case, the ADICOS GSME also works with heavy contamination. Dry
dust can be removed using a vacuum cleaner as needed.
NOTICE! Clogging of the sintered metal filter! The sintered metal filter can
clog when coming in contact with water and dirt. · Clean the sintered metal
filter dry only!
34
405-2010-003 EN54
ADICOS GSME
mAintenAnce
8.3 Function Test of the Signal Relays
The “Alarm” and “Fault” signal relays must be checked for function quarterly.
For this purpose, they can be switched for test purposes via the ADICOS System
Software.
NOTICE! Switching through the relays! The function test of the signal relays
triggers an alarm resp. fault state in the connected central fire alarm panel.
· Switch the fire panel into inspection mode prior to the function test!
8.4 Annual Function Test
WARNING! Malfunction of the detector! To ensure correct function of the
detector, a test with the ADICOS GTL-3 tester is required. · Perform at least
one test triggering per year with the GTL-3! · Observe ADICOS instructions no.
430-2410-102!
NOTICE! The function test of the detector triggers an alarm state in the
connected central fire alarm panel. · Switch the fire panel into inspection
mode prior to the function test!
8.5 Detector Replacement
The maximum service life of the sensors of the ADICOS GSME detector is limited
to eight years. Depending on the ambient conditions, the sensitivity of the
sensor can also decrease earlier and make a detector replacement necessary.
Replace ADICOS GSME detectors no later than eight years after commissioning!
The same information apply to detector replacement like for their initial
installation (> Chap. 5, Installation). Proceed as follows to replace the
detector:
8.5.1 Save inventory data Save the inventory data if any of these cases apply:
The ADICOS System Software is used permanently for monitoring measurement
data. The alarm thresholds of the old units do not correspond to the alarm
thresholds of the new
units and should be available for data transfer.
To save the inventory data of a detector, an installed ADICOS System Software
is required.
ADICOS GSME
405-2010-003 EN54
35
mAintenAnce
Create a backup file
1 Open ADICOS System Software 2 Call up “Service functions” 3 Select “Test” 4
Save table
Z The backup file with all relevant unit data is now located under:
C:GSMEMelder_Liste_komplett.csv
8.5.2 Prepare new unit for use If the ADICOS System Software is used
permanently for monitoring measurement data, it is necessary to prepare the
new device for use at a specific position. A specific position is identified
by a line number, for example.
The prerequisite for a 1-to-1 exchange of the new unit and the old unit is an
identical M-Bus address.
Adopt the M-Bus address of the old unit for the new unit before commissioning
it on the M-Bus.
If the alarm thresholds before and after the detector replacement are to be
identical, adopt the alarm thresholds of the old unit for the new unit.
The M-Bus address and the alarm thresholds of the replacement device are
stored in the backup file (see 8.5.1 Save inventory data).
8.5.3 Replace detector If the ADICOS System Software is used permanently for
monitoring measurement data, it is necessary to store the serial number of the
new device correctly.
For this purpose, adopt the M-Bus address of the old unit for the new unit on
the M-Bus before commissioning (see 8.5.2 Prepare new unit for use).
If interface modules for a fire alarm bus are transferred from old to new
units, make sure that the electronics of the units are protected from external
damage when opening the new units. When closing the unit, tighten all screw
connections with a torque of 1.5 Nm to ensure dust-tightness.
36
405-2010-003 EN54
ADICOS GSME
mAintenAnce
8.5.4 Update unit data If the ADICOS System Software is used permanently for
monitoring measurement data, an update of the device data at the ADICOS System
Software is mandatory.
An update of the device data on the ADICOS System Software has no effect on
the functionality of the new device.
Call up the unit for updating
1 Open ADICOS System Software 2 Call up “Service Funktoinen” 3 Select the
button “Unit input”. (De-
vice input) button 4 Select the old unit in the “Aktive
Geräte” table by double-clicking on it
Z ,,GSME-Dateneingabe” window is open
5 Read in the serial number of the new device by pressing the “Von Melder
lesen” button. Then confirm with “OK”
8.5.5 Optimise alarm thresholds (optional)
Even if you exactly transfer the alarm thresholds from an old device to a new
device, the performance of the new device may differ from the previous
performance of the legacy device.
Possible reasons for different performance with identical alarm thresholds
are:
marginally varying cross-sensitivities Contamination of the sintered metal
filter of old units whose influence on the measure-
ment result cannot be compensated.
Optimise alarm thresholds or set new alarm thresholds using the following
methods: Long-term recording
Long-term recordings are used to record the usual fire gas concentrations at
the site of operation. Fire test Fire tests are used to determine the
expected fire gas concentration in the event of an alarm.
ADICOS GSME
405-2010-003 EN54
37
fAult
9 Fault
A fault of the ADICOS GSME is indicated by illumination of the yellow signal
LED »Fault« as well as by deactivation of the »Fault« signal relay.
The following fault states and/or causes are recognized by the detector:
Fault Undervoltage/ power outage
Checksum ROM / EEPROM Heating temperature
Description
Measure
Operating voltage drops below Check supply voltage;
20 V (including temporarily)
Check wiring;
Use stronger or additional
power supply;
Self-resetting
The checksum is incorrect after 1. Update checksum
a new start or reset.
2. Detector replacement with
aid of System Software
One or several heating tempera- Observe;
tures do not reach the target val- Detector replace-
ue.
ment, if necessary;
Test fault Sensor fault Start-up sequence
A test fault was triggered using Cancel test fault using the ADICOS System
Software. ADICOS System Software
The conductance of at least one Detector replacement sensor is exceeded resp.
undercut.
The detector always remains in Self-resetting fault, until the end of the
startup process.
Use the ADICOS System Software for a detailed analysis of the fault states!
The ADICOS GSME does not offer automatic contamination detection for the sintered metal filter.
10 Disposal
Return the device to the manufacturer when it reaches the end of its
serviceable life. The manufacturer will ensure that the components are
disposed of properly, in an environmentally friendly manner.
38
405-2010-003 EN54
ADICOS GSME
11 Technical Data
General
Model: Item No.:
Enclosure dimensions:
mm
Weight:
kg
Degree of protection:
Enclosure:
Electrical properties
Voltage range:
Maximum power consumption (without heating):
Maximum power consumption (with heating):
Internal fuse:
V VA
VA
mA sb
Environmental conditions
Ambient Temperature:
°C
Relative humidity
%
Detection data
Sensor combination:
Response time:
s
Detection scenarios:
Other
Bending radius
mm
connection cable
technicAl DAtA
GSME-M4 408-2001-201 120 x 100 x 100 (Length x Width x Depth) (Length: bayonet
connector included, Depth: spray protection incl.) 0.7 IP 64 Aluminum die
casting, powder coated
DC 21.6 … 40 4 14 2 x 500
20 … + 50 95 (non-condensing)
CO — H2 — HC — NOx > 30 Smoldering fires per EN 54-7 Smoldering coal fires
91,5
ADICOS GSME
405-2010-003 EN54
39
technicAl DAtA 11.1 ID Plate
Model: Device model
ART-Nr: Article number (variable)
COM-Nr: Communication number (variable)
CE marking
SERIAL: Serial number YR: (variable)
TEMP: VDC/VA:
Ambient
IP:
temperature
Voltage range /
I
0
:
maximum pow-
er consumption
(heating incl.)
Year of production (variable)
Degree of protection
Internal fusing (Short-circuit current)
40
405-2010-003 EN54
ADICOS GSME
12 Appendix 12.1 ADICOS Mounting Plate
150 130
A
AppenDix
A 63
150 130
85 6.4
A-A
ADICOS GSME
405-2010-003 EN54
41
notes
42
405-2010-003 EN54
ADICOS GSME
notes
ADICOS GSME
405-2010-003 EN54
43
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>