DOMEO 210 FL 3V EU
210 FL 3V EU Counter Flow High Efficiency Heat Recovery
1 DOMED 210 3V FL | 12 Drain connection |
---|---|
2 Connection Supply Air | 13 Cable for power supply |
3 Connection Extract Air | 14 Temperature sensor supply air (T2) |
4 Connection Outdoor Air | 15 Temperature sensor extract air (T3) |
5 Connection Exhaust Air | 16 Electronic board |
6 Filter F7 (Outdoor Air) | 17 Bypass |
7 Extract fan | 18 Supply fan |
8 Temperature sensor Outdoor Air (T1) | 19 Filter G4 (Extract air) |
9 Temperature sensor Exhaust Air (T4) | 20 Wall bracket |
10 Cable for remote Control | 21 Remote control |
11 Counterflow heat exchanger | 22 Drain ducts |
GENERAL INFORMATION
1.1. INTRODUCTION
This manual is intended for the use of the central balanced-fl ow high effi
ciency DOMEO and its peripherals (ductwork, vents, controllers).
It is designed to provide clear and safe guidance for the design, installation
and use of the product.
The products are constantly evolving and so, Soler & Palau reserves the right
to modify this manual without prior notice.
1.2. WARRANTY AND LIABILITY
Warranty
The DOMEO heat recovery system has three years warranty from the date of
purchase. This warranty includes free delivery of necessary spare parts.
The warranty does not cover:
Installation and removal costs.
Defects that, in the opinion of Soler & Palau, are due to improper
installation, handling, neglect or accidental damage.
Those defects that arise as a result from operations or repair performed by a
third party without permission from Soler & Palau.
To return a defective part, the user should contact their installer.
Liability
DOMEO is designed for ventilation systems in individual dwellings.
Soler & Palau is not responsible for damage caused by:
- Improper use.
- Normal wear of components.
- Failure to follow the instructions in this manual concerning safety, use and installation.
- The use of parts not supplied by Soler & Palau.
1.3. SAFETY
General health and safety standards
The heat exchanger DOMEO has been designed to be incorporated into a
ventilation system.
Following installation, there should be no risk to safety, health and the
environment according to EC directives. This also applies to other products
used in the installation.
The following general guidelines are important:
- Follow the safety instructions to prevent injuries and damage to the motorised fans.
- The technical characteristics described in this manual may not be changed.
- The motorised fans must not be modifi ed.
- The motorised fans must be supplied with a single phase AC supply of 230 V / 50 Hz.
- So that the installation complies with EC directives, the DOMEO must be connected to the electricity grid according to current national standards.
- The device must be installed so that under normal operating conditions, there is no risk of contact with moving parts and power.
- The DOMEO meets legal requirements for electrical equipment.
- Before working on the machine, always turn the power off.
- Use appropriate tools.
- Use the machine only for the purpose for which it is intended.
TECHNICAL INFORMATION
2.1. GENERAL INFORMATION
The DOMEO ensures optimum ventilation of a house with a maximum energy
recovery. It draws air from the rooms (bathroom(s), toilet, kitchen and wash
room(s)) and supplies fresh air through the main rooms (living room, bedroom
(s), offi ce, etc ).
The fresh and extract airfl ows are separated and fi ltered. Only heat energy is
transferred to the fresh fi ltered air that is introduced.
Due to the high-effi ciency heat exchanger used in the DOMEO performance can
reach 95%.
Condensation forms during the heat exchange process and is recovered in the
condensate tray, which must be connected to a waste water drain.
The DOMEO is equipped with a double condensate drain system that allows a
propper working in winter (heating) and summer (cooling).
The DOMEO has a 100% heat exchanger bypass system and this allows the
introduction of fresh air at night without it being heated by contact with
warm air accumulated in the house during the day. The system operates
automatically or can be used manually (see section 5-2).
2.2. DESCRIPTION
| Outdoor air (ODA):
It is recommended to install the fresh air intake (wall or roof) at a suffi
cient distance from any area with high pollution (trees, exhaust fumes, road.
etc.)
This duct must be sealed and insulated to prevent condensation.
---|---
| Supply air (SUP):
To avoid thermal losses and optimize the performance of the installation, it
is recommended to use insulated ducts.
| Extract air (ETA):
To avoid thermal losses and optimize the performance of the installation, it
is recommended to use insulated ducts.
| Exhaust air (EHA):
This duct must be sealed and insulated to prevent condensation.
| By-pass:
The DOMEO has a 100% heat exchanger bypass system which allows free cooling by
night. The principle of freecooling uses free energy from the outdoor air to
ventilate and cool buildings when outdoor air temperature is lower than the
exhaust air temperature.
2.3. DIMENSIONAL CHARACTERISTICS
2.3.a Heat recovery unit:
2.3.b Remote control:
INSTALLATION
The DOMEO heat recovery unit is designed for indoor installation. We
recommend a min. temperature of +10ºC in the room where the unit is installed
to guarantee a good effi ciency of the unit.
In areas where temperatures can be below -10ºC in the winter time, it is
necessary to install a pre-heating device.
****In all Passive House applications the pre-heater is mandatory.
Summer condensation
In very humid zones in the summer time there could be condensation on the
supply side when indoor air is cooled therefore we supply an additional drain
connector in order to install if needed (see pictures below).
CHARACTERISTICS AND ELECTRICAL CONNECTIONS
4.1. ELECTRICAL CONNECTION
The unit is supplied with power cable and schuko plug.
Power supply: 230V AC, 50Hz
Max. current: 0,8A
Max. power: 90W
Maximum ambient temperature: 50ºC
Maximum fl ow temperature: 45ºC
-
Power electrical connection and remote control50 m to connect witht the remote control.
-
MODBUS network
Use shielded cable and twisted-pair type PAR-POS 2x2x0,34. -
Free voltage contact connection
Pass the cable through the interior of ferrite type WE 742 727 33 MnZn twice. -
Installation of cable glands
Installation of cable glands
4.2. SPCM-WB COMMUNICATIONS MODULE CONNECTION FOR IOT CONNECTAIR CONNECTION
(OPTIONAL)
Note: The SPCM communication module is not compatible with the use of the
remote controller included with the DOMEO unit.
To connect the SPCM-WB communications module to the unit, please follow the
following instructions:
- First, disconnect the unit from the power.
- Disconnect the remote control from the main board.
- Fix the SPCM-WB in the hole located in the upper left hand corner, above the main board. This is done by inserting a screw into the EPP body of the DOMEO unit through a clip on the module (see drawing 1).
- Once fi xed, connect the SPCM-WB with the cable supplied to the central board in the Modbus terminal block. (see drawing 2).
- Finally, change position of Jumper J1 from open to closed (see drawing 3).
- The installed set will be as per image 4.
This allows the unit to be controlled through the CONNECTAIR platform rather than the remote control, which improves the functionality of the unit.
COMMISSIONING OF THE DOMEO
5.1. FOR INSTALLATION:
The remote control allows:
- Adjust the airfl ows (1st speed, 2nd speed, 3rd speed)
- Timer for adjusting the fi lter maintenance period (6, 9, 12 or 15 months) (factory setting 12 months)
- Adjust the balance of supply / extraction airfl ows
5.1.a Airfl ow adjustment
To adjust the airfl ow turn the potentiometer carefully clock wise with a small
screw driver.
Factory setting: 1st speed = position 3; 2nd speed = position 5; 3rd speed =
position 7 (The curves below are showing the airfl ow according to the position
of the potentiometer)
5.1.b Adjustment of the fi lter maintenance period
It is possible to set maintenance period to 6, 9, 12 or 15 months (12 months
factory setting). The fi lter clogging depends on the pollution of the area
where the unit is installed. We recommend checking the time in which the filter
clogs and adjusting this period.
It is advisable to do this after the second fi lter change as the first filter
life maybe reduced due to construction dust and humidity in the system.
5.1.c Supply/extraction airfl ow adjustment
In the case that in the building is a chimney, gas oven or any apparatus which
needs combustion air and there is no additional supply air opening for this,
it is necessary to adjust the unit in the way that the combustion is not
affected. It is necessary to add a supplementary air supply equal to the
extract airfl ow due to the natural draught of the chimney.
After fi nishing the installation it is recommended to use this feature to
balance the airfl ows!
Example:
- Minimum calculated airfl ow = 90 m 3/h
- Supply airfl ow necessary = 99 m 3/h
Potentiometer position 5 = +10%
****The adjustment is made on the supply airfl ow compared with extraction airfl ow.
REMOTE CONTROL ADJUSTMENTS – USER
Speed adjustment
Pressing the “airfl ow adjustment” buttons you can change the speed and . The
LED will be green illuminated (see pictures below).
Automatic bypass
The DOMEO works with a pre-programmed automatic bypass.
The following conditions have to be fulfi lled to open/close the bypass.
Tint = indoor temperature
Text = outdoor temperature
Activation conditions: [(Tint-Text >1) and (Tint >23) and (Text >13)]
Deactivation conditions: [(Tint-Text ≤0) or (Tint ≤20) or (Text ≤10)] Manual
bypass
Pressing the button “manual bypass” the bypass will open for 1 hour. During
the bypass is activated the button is green illuminated.
To deactivate (close) within the 8 hours the bypass you have to push the
button again (illumination is off).
Standby function
Push and hold the button for 3 seconds, the unit will switch into the standby
mode (see drawing below). To switch the unit on push the button again.
Filter maintenance
When the button is red illuminated, please check the fi lter as a maintenance
is necessary. After the fi lter change press the button during 3 seconds in
order to reset the fi lter alarm.
Stop mode (Flashing red LED):
Press the left key for 3 seconds to activate Stop mode. Press the key again to
start up.
Filters alarm (red LED):
When the fi lters are dirty a red LED appears on the right hand key. The
factory setting is 12 months after commissioning.
If this interval is not ideal for the configuration or use of your installation
(fi lters too dirty or clean).
It is possible to adjust this setting from 6 to 15 months (in 3 monthly steps
– see paragraph 5-1-b).
Once changes have been made push the button 3 seconds to deactivate the
alarm and reset the timer.
SWITCHING ON THE DOMEO
To start your DOMEO unit use the following process:
-
Verify that all system components are correctly installed and connected:
• Fresh air intake duct insulated and connected correctly (Do not use a fresh air intake equipped with insect screen)
• Fresh air and exhaust ducts insulated and connected correctly
• Fresh air and exhaust vents connected
• Flow regulators mounted in the right direction (if installed)
• Air outlet using insulated duct and connected to the outside (Using a roof cowl or outlet without an insect screen)
• Insulated fl exible ducts taut and large radius bends (if installed)
• Check that the unused spigots on plenums are sealed (if installed)
• Condensation drain well connected (siphon)
• Check that all connections are sealed (on the DOMEO, on plenums and vents)
• Check the setting of the power circuit breaker -
Turn on the DOMEO
-
Adjust airfl ows.
ALARM INDEX
Through the LED located in the user control it is possible to supervise the
status of the unit. This LED will show the alarm (check see table) in case of
produce the failure of some critical components of the unit or simply by notifi
cation (replacement fi lters, by-pas manual mode, supply temperature <5°C).
Depending on risk level of the alarm generated, the control will manage the
response required. If it is necessary, the unit will be stopped for safety
reasons.
Priority | Alarm / State | LED | Action |
---|---|---|---|
1 | Extract fan failure | Red LED, 1 blink | Unit stops |
2 | Supply fan failure | Red LED, 2 blinks | Unit stops |
3 | ByPass defect | Red LED, 3 blinks | Unit stops |
4 | Supply air temperature <5°C | Red LED, 4 blinks | Unit stops. Every 2 hours |
the unit starts for 5 minutes to ckeck if conditions allow normal operation
5| ODA sensor failure (fresh air)| Red LED, 5 blinks| Normal operation
6| SUP sensor failure (supply)| Red LED, 6 blinks| Normal operation
7| ETA sensor failure (extract)| Red LED, 7 blinks| Normal operation
8| EHA sensor failure (exhaust)| Red LED, 8 blinks| Normal operation
9| Dirty fi lter failure| Red LED continuous| Normal operation
10| ON bypass manual mode| Green LED continuous| Normal operation
11| Active defrost| Green LED blinking| Defrost management
Blink: A = 0,75s; Interval: B = 3s
PRE-HEATER FOR PASSIVE HOUSE APPLICATION
In order to assure correct function of the unit and to comply with Passive
house specifi cation it is necessary to install a pre-heater on the unit.
We recommend following accessories:
1 pcs. Electric heater MBE-125/12B-R
1 pcs. Temperature probe TG-K
1 pcs. Pressure sensor DPS 2-30
1 pcs. TBI 30
Installation scheme
Technical data electric heater MBE-125/12B-R
Material: | galvanised steel |
---|---|
Power supply: | 230V AC, 50Hz |
Power: | 1200W |
Protection class: | IP43 |
PUTTING OUT OF SERVICE AND RECYCLING
EEC legislation and our consideration of future generations mean that we should always recycle materials where possible; please do not forget to deposit all packaging in the appropriate recycling bins. If your device is also labeled with this symbol, please take it to the nearest Waste Management Plant at the end of its servicable life.
****S &P SISTEMAS DE VENTILACIÓN, S.L.U.
C. Llevant, 4
Polígono Industrial Llevant
08150 Parets del Vallès
Barcelona – España
Tel. +34 93 571 93 00
www.solerpalau.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>