sensitron SMART S Series Gas Detectors Instruction Manual
- June 12, 2024
- sensitron
Table of Contents
A Halma Company
SMART S
Quick Guide
SMART S Series Gas Detectors
Short installation manual
MT4962 rev.2 16/03/2023©
Sensitron S.r.l., Viale della Repubblica 48, Cornaredo (MI)
sales@sensitron.it
TEL. +390293548155 FAX. +390293548089
This manual is a short installation guide for gas detectors of SMART S series. The reading of the main manual of the gas detector is recommended. SMART S-SS gas detectors are equipped with a display board, while SMART S-MS not. Both can be equipped with a board fot HART communication.
Identification labels
Each gas detector has two labels:
I ATEX label, with detector marking
II Detector’s label, with serial number, adjustment gas and other
information
Example of ATEX label to be filled
- Enclosure module
- Electronic type
- Sensor head
- Temperature class
- Tmin
- Tmax
- Maximum power
- Entries thread
Example of gas detector label to be filled Link
| Technical manual for detectors of flammable gas with certified performance|
http://www.sensitron.it/MT/P/_MTEX3567_SMART_S_FLAMMABLE_ZONE_1.pdf
---|---|---
| Technical manual for detectors of toxic gas|
http://www.sensitron.it/MT/P/_MTEX3770_SMART_S_TOXIC_ZONE_1.pdf
| Technical manual for IECEx gas detectors|
http://www.sensitron.it/MT/P/_MTEX4720_SMART_S_FLAMMABLE_ZONE_1_IECEx.pdf
| Technical manual for detectors for marine environment|
http://www.sensitron.it/MT/P/_MTEX4899_SMART_S-MS_MED.pdf
|
Technical manual for intrinsically safe detectors|
http://www.sensitron.it/MT/P/_MTEX4985_SMART_S-IS_TOXIC_ZONE_1.pdf
Accessories manual links
|
---|---
Display board| 3 relays board
http://www.sensitron.it/MT/P/_MT3771_DISPLAY_SMART_S.pdf|
http://www.sensitron.it/MT/P/_MT3678_STS3REL.pdf
|
HART module| Calibration keypad-Display LED
http://www.sensitron.it/MT/P/_MT4583_HART.pdf| http://www.sensitron.it/MT/P
/_MT4508_STS-CKD+.pdf
|
Calibration keypad-Display OLED| Calibration keypad -Display LED
http://www.sensitron.it/MT/P/_MT4564_STS-CKD-OLED.pdf|
http://www.sensitron.it/MT/P/_MT894_GAS_TEST_KIT.pdf
|
Remote head kit (5 m)| Remote head kit (25 m)
http://www.sensitron.it/MT/P/_MT3825_ST.R5M.pdf|
http://www.sensitron.it/MT/P/_MT3788_ST.R25M.pdf
Installation site prearrangement
At the mounting and installation phase be sure all safety precautions have been considered. Always consider how important it is the correct positioning of gas detectors to get the optimum response.
- Be careful never to install gas detectors close to air intakes or fans causing strong air currents.
- Be sure the detectors are attached to a firm base to prevent vibration that can damage them, producing unreliable results.
- Although the electronics comply with the electromagnetic compatibility rules, it is advised to keep the detectors at a distance from any radio frequency senders (such as radio links or similar).
- Please be also sure that detectors are placed in a convenient location for future maintenance and calibration requirements.
- All of the gases lighter than air (Methane, Hydrogen, Ammonia) tend to spread upwards; the detector should be placed at 30 cm from the ceiling in order to maximise the effectiveness of the detection.
- All of the gases heavier than air (LPG, Butane, Petrol Vapours) tend to spread downwards; the detector should be placed at 30 cm from the floor.
Installation
CORRECT POSITIONING MODE:
The gas detector is always to be mounted with the sensing element placed
downward. For no reasons at all the enclosure can be drilled. Wall mount the
detectors by employing the existing holes. Exd detectors come complete with
wall fixing brackets.
Detector circuit layout without HART module: Detector circuit layout equipped with HART module:
- Relay 1 is not programmable and it associated to FAULT and external watchdog status.
- Relays 2 and 3 are programmable, as default they are associated to alarm 2 and 3.
- Alla relays as default condition have the contacts normally closed (NC) and they are set as normally energized.
Testing and use
POWER ON
When the detector is powered on, the green LED on the motherboard starts
blinking at slow intermittent. Output current is nearly 2 mA. After 2 minutes
and finished the warmup step, the output current is 4.0mA. Once the warm-up
phase is over, the detector can work correctly, although the optimal
performances will be achieved after two hours. Should the detector be provided
with display, please refer to the additional technical handbook MT3771.
TESTING
Detectors are factory calibrated for the specific gas required by the
customers. Future adjustment of the preset calibration can be carried out by
employing the calibration keypad. Testing should be carried out by using a gas
mixture in the appropriate range, along with our calibration kit.
USE
The detector works autonomously and automatically. Once adequately connected,
no further operations are required. The flashing green LED on the motherboard
indicates the detector’s working condition as detailed in the main manual.
Maintenance
Within the European Union Countries, bump testing and calibration procedures of gas detectors are required by strict regulations and detailed in the IEC EN 60079-29-2. This norm gives guidance on the selection, installation, use and maintenance of gas detectors intended for use in industrial and commercial applications. The standard requires calibration and bump testing as well as recording of the performed checks and it defines that all gas detectors should undergo periodical operational testing according to the manufacturer’s specifications. Test results should be recorded into a suitable book to be shown to the Authority in case of inspection.
Contacts
Viale della Repubblica, 48
20007 Cornaredo (MI) – ITALY
+39 0293548155
sales@sensitron.it
sensitron.it
Sensitron S.r.l.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>