Nexto Logger, Nexto Series
NL717
CE117100 Rev. B
Instruction Manual
Product Description
Nexto Logger is a Datalogger belonging to the Nexto Series product family. It
was developed to expand the Series’ fields of activity and provides high-speed
processing power in a compact design with digital and analog inputs, SDI-12
communication, and LoRa long-distance radio integrated into the same
equipment.
This product was developed with a focus on monitoring and telemetry
applications, in other words, systems that collect remote data, offering
digital and analog inputs, all of them with high precision as required in the
hydrological parameter monitoring market, solar energy generation
applications, and other areas related to science and monitoring of physical
quantities.
In addition to the integrated inputs, it is possible to collect sensor data
via SDI-12 network, the data is stored in the Datalogger’s internal memory and
sent to collection stations via the integrated ethernet network or via the
long range radio frequency infrastructure, LoRa.
Nexto Logger is suitable for data collection in systems that require remote
data collection. Its extended power supply range allows applications in
different areas including powering with alternative energy sources such as
solar power. It can be used in applications such as hydrology, sanitation
(water and effluents), agribusiness, private and public urban infrastructure,
sensor data collection for data analysis, and other scientific applications as
a replacement for traditional analytical methods. In addition, it is an ideal
solution to complement large applications together with the Nexto Series
portfolio, extending the range of applications using the same technology and
engineering environment. This is a great advantage for OEMs and integrators in
these application areas where application scalability is required. Its main features are:
- Compact design
- DIN rail mount
- High-speed 32-bit ARM-based processor
- 10/100 Mpbs Ethernet interface with protocols like OPC UA, EtherNet/IP, MODBUS and MQTT
- LoRa Long Range Radio
- Optoisolated digital inputs
- Analog current inputs
- Real-time clock (RTC)
Ordering Information
2.1. Included Items
The product package has the following items:
- Compact NL717 module
- Connectors
- 2dbi Omnidirectional Antenna
2.2. Product Code
The following code should be used to purchase the product:
Code | Description |
---|---|
NL717 | NL717 – DATALOGGER 8DI 8AI LORA |
Table 1: Product code
Related Products
The following products must be purchased separately when necessary:
Code | Description |
---|---|
MT8500 | MasterTool IEC XE |
NX9202 | RJ45-RJ45 2 m Cable |
NX9205 | RJ45-RJ45 5 m Cable |
NX9210 | RJ45-RJ45 10 m Cable |
AMJG0808 | Simple cable RJ45-RJ45 2 m |
GW700 | GATEWAY LORA, ETH, USB |
Table 2: Related Products
Notes:
MT8500: MasterTool IEC XE is available in four different versions: LITE,
BASIC, PROFESSIONAL and ADVANCED.
For more details, please check MasterTool IEC XE User Manual – MU299609.
NX92xx: Cable for programming the CPUs of the Nexto Series and Ethernet
point-to-point with another device with Ethernet interface communication.
AMJG0808: Cable for programming the CPUs.
Product Features
4.1. General Features
| NL717
---|---
Digital Inputs| 4
Fast Inputs| 4
Max. number of high-speed counters| 1
Max. number of external interruptions| 2
Current Analog Inputs| 8
Ethernet TCP / IP interface| 1
Max. number of tasks| 16
Programming languages| Structured Text (ST)
Ladder Diagram (LD)
Sequential Function Chart (SFC)
Function Block Diagram (FBD)
Continuous Function Chart (CFC)
Online changes| Yes
Watchdog| Yes
Real-time clock (RTC)| Yes
Resolution of 1 ms, max. variance of 95 seconds per year,
retention time of 20 days.
Status and diagnostic indication| LEDs, web pages and CPU’s internal memory
Isolation
Protective earth **** to all
Ethernet to all
Power Supply/Analog Inputs to all
Digital Inputs to all| 1500 Vdc / 1 minute (1000 Vac / 1 minute)
1500 Vdc / 1 minute (1000 Vac / 1 minute)
1500 Vdc / 1 minute (1000 Vac / 1 minute)
1500 Vdc / 1 minute (1000 Vac / 1 minute)
Maximum power dissipation| 15 W
Maximum wire size| 0,5 mm² (20 AWG) with ferrule
1,5 mm² (16 AWG) without ferrule
Minimum wire temperature rating| 75ºC
Wire materia| Copper only
IP level| IP 20
Conformal coating of electronic circuits| Yes
Operating temperature| -20 to 60ºC
Storage temperature| -25 to 75ºC
Operating and storage relative humidity| 5% to 96%, non-condensing
Vibration resistance (IEC 60068-2-6, sinus)| 7 mm from 5 to 8,4 Hz
2 G from 8,4 to 500 Hz
10 sweeps each axis, 1 octave per minute
Shock resistance (IEC 60068-2-27, half-sine)| 15 G for 11 ms, 6 shocks in each
of 3 axis
Product dimensions (W x H x D)| 215,5 x 98,8 x 34,0 mm
Package dimensions (W x H x D)| 270,0 x 102,0 x 40,0 mm
Weight| 370 g
Weight with package| 430 g
Standards and Certifications|
| Yes
Yes
Table 3: General Features
Notes:
For more details, please consult:
www.gov.br/anatel.
This equipment is not entitled to protection against harmful interference and
may not cause interference to properly autho-rized systems.
This product is not suitable for use in domestic environments as it may cause
electromagnetic interference in which case the user is required to take
necessary steps to minimize this interference.
Maximum Number of Tasks: This value represents the maximum total of user
and system tasks. The detailed description of possible user tasks can be found
on Project Profiles section of User Manual.
Conformal coating of eletronic circuits: Conformal coating protects the
electronic components inside the product from moisture, dust and other harsh
elements to electronic circuits.
4.2. Memory
| NL717
---|---
Direct representation input variable memory (%I)| 2 Kbytes
Direct representation output variable memory (%Q)| 2 Kbytes
Direct representation variable memory (%M)| 1 Kbytes
Symbolic variable memory| 2 Mbytes
Maximum amount of memory configurable as retentive or persistent| 7,5 Kbytes
Full Redundant Data Memory
Direct representation input variable memory (%I)
Direct representation output variable memory (%Q)
Direct representation variable memory (%M)
Symbolic variable memory| –
–
–
–
–
Total memory
Program memory (limited to 6 MBytes) +
Source code memory (backup)| 64 Mbytes
User files memory| 8 Mbytes
Table 4: Memory
4.3. Protocols
| NL717| Interface
---|---|---
MODBUS TCP Client| Yes| NET 1
MODBUS TCP Server| Yes| NET 1
MODBUS RTU via TCP Client| Yes| NET 1
MODBUS RTU via TCP Server| Yes| NET 1
OPC DA Server| Yes| NET 1
OPC UA Server| Yes| NET 1
EtherNet/IP Scanner| Yes| NET 1
EtherNet/IP Adapter| Yes| NET 1
MQTT Client| Yes| NET 1
SNTP Client (for clock synchronism)| Yes| NET 1
SDI-12 Master Version 1.4| Yes| SDI-12
Table 5: Protocols
4.4. Ethernet
| Ethernet
---|---
Connector| Shielded female RJ45
Auto crossover| Yes
Maximum cable length| 100 m
Cable type| UTP or ScTP, category 5
Baud rate| 10/100 Mbps
Physical layer| 10/100 BASE-TX
Data link layer| LLC
Network layer| IP
Transport layer| TCP (Transmission Control Protocol)
UDP (User Datagram Protocol)
Diagnostic| LED (Link/activity)
Table 6: Ethernet Interface Features
4.5.LoRa Radio
| LoRa Radio
---|---
Connector| SMA female
Maximum cable length| 10 m (Maximum)
Cable type| PigTail
Baud rate| 290 bps to 50 kbps
Radio type| LoRaWan
Frequency Range| 915-928MHz
Network layer| LoRaWan
Receiver Sensitivity| -140 dBm
Type of Antenna| Omnidirectional for outdoor environments
Output Power| 27 dBm
Gain| 2 dBi
Line-of-Sight Range| 3 to 4km in urban areas and 10 to 12km in rural areas
Table 7: LoRa Radio Features
4.6. SDI-12
| SDI-12
---|---
Connector| 3-pin connector block
Physical interface| SDI-12
Power Supply Output| 12V
Maximum Current| 500 mA
Communication Direction| Single data line in half-duplex
Cable length| 60m (Maximum)
Transmission Rate| 1200 bps
Protocols| SDI-12 Master Version 1.4
Max SDI-12 Sensors| 10
Table 8: SDI-12 Interface Feature
Note:
For the correct operation of the SDI-12, the MainTask must be configured with
a time lower than or equal to 20 ms.
4.7. Power Supply
| Power Supply
---|---
Nominal Input Voltage| 12 / 24 Vdc
Input Voltage| 10 to 30 Vdc
Maximum Input Current (in-rush)| 50A / 300 us
Maximum Input Current| 1500 mA
Table 9: Power Supply Features
4.8. Digital Inputs
| Digital Inputs
---|---
Input Type| Optoisolated point type 1
An isolated group of 8 inputs
Input Voltage| 12 Vdc / 24 Vdc
5 to 30 Vdc for logic level 1
0 to 2 Vdc for logic level 0
Input Impedance| 4,12 kΩ
Maximum Input Current| 7,28 mA @ 30 Vdc
Input State Indication| Yes
Response Time| 0,1 ms
Input Filter| Disabled or 2ms to 255ms – by software
Table 10: Digital Inputs Features
Note:
Input Filter: The filter sampling is performed on MainTask (or Refresh
function), then it’s recommended to use multiple values of the task interval.
4.9. Fast Inputs
| Fast Inputs
---|---
Number of fast inputs| 4 (can be used as high-speed counter, External
interrupt or normal input)
Max. number of high-speed counters| 1
Max. number of external in-terrupts| 2
Connector configuration| 100,101, 102 and 103
Input voltage| 12 Vdc / 24 Vdc
5 to 30 Vdc for logic level 1
0 to 2 Vdc for logic level 0
Input impedance| 4,12 kfi
Maximum input current| 7,28 mA @ 30 Vdc
Configuration mode| 1-input modes:
Normal digital input
External interrupt
2-input modes:
Up/Down (A count, B direction) with zero (uses 100, 101, 102)
Quadrature 2x (uses I00,101)
Quadrature 2x with zero (uses 100,101, 102) Quadrature 4x (uses I00,101)
Quadrature 4x with zero (uses 100,101, 102)
Counting direction control| By software or hardware
Counting input detection edge| Rising edge, active at logic level 1 (except
for quadrature 4x, where it counts on both edges)
Data format| Signed 32-bit integer
Operation limit| From – 2.147.483.648 to 2.147.483.647
Maximum input frequency| 100 kHz
Minimum pulse IA idth @ 24 Vdc| 2µs
Table 11: Fast Inputs Features
4.10. Analog Inputs
| Analog Inputs
---|---
Input Type| Voltage or current input, single ended, individually configured
Data Format| 16 bits in two’s complement, justified to the left
Converter Resolution| 24 bits monotonicity guaranteed, no missing codes
Conversion Time| 400 µs
Input status indication| Yes
Module Protections| Yes, protection against surge voltages and polarity
inversion
Table 12: Analog Inputs Features
| Current Input Mode
---|---
Input ranges| Range| Engineering Scale| Resolution
0 to 20 mA
4 to 20 mA| 0 to 30.000
0 to 30.000| 5,12 µ A
5,12 µ A
Precision| ± 0,3 % of full scale @ 25 ◦ C
± 0,015 % of full scale / ◦ C
Over scale| 3 % of full scale
Maximum input current| 30 mA
Input impedance| 270 Ω
Configurable parameters| Signal type per input Filters Open Channel
Low pass filter time constant| 100 ms, 1 s, 10 s or disabled
Table 13: Analog Input Characteristics – Current
Note:
Input ranges:: When configured as 4 to 20 mA, input signals lower than 4
mA will result in negative values (-7,500 for 0 mA). In MasterTool IEC XE,
there is a parameter called Open Loop Value was included to select the
behavior in this situation.
The default value is Disabled (which provides a linear reading as described
above), having also the option to provide a fixed reading equal to lower and
upper limits (“0” or “30000”).
Compatibility with Other Products
To develop an application for Nexto Series CPUs, it is necessary to check the version of MasterTool IEC XE. The following table shows the minimum version required (where the controllers were introduced) and the respective firmware version at that time:
Controller model | MasterTool IEC XE | Firmware version |
---|---|---|
NL717 | 3.51 | 1.13.9.0 |
Table 14: Compatibility with other products
Additionally, along the development roadmap of MasterTool IEC XE some features
may be included (like special Function Blocks, etc…), which can introduce a
requirement of minimum firmware version. During the download of the
application, MasterTool IEC XE checks the firmware version installed on the
controller and, if it does not meets the minimum requirement, will show a
message requesting to update. The latest firmware version can be downloaded
from Altus website, and it is fully compatible with previous applications.
Istallation
ATTENTION
Products with broken warranty seal are not covered in warranty.
CAUTION
The device is sensitive to static electricity (ESD). Always touch in a
metallic grounded object before handling it.
DANGER
Nexto Series can operate with voltage up to 250 Vac. Special care must be
taken during the installation, which should only be done by qualified
technical personnel. Do not touch on the wiring field when in operation.
6.1. Electrical Installation
DANGER
When executing any installation in an electric panel, certify that the main
energy supply is OFF. Diagram Notes:
- Protective Earth terminal for power supply. Shall be externally connected to ground.
- External power supply connection.
- Typical connection of digital input (sink type). C0 is the common point for the isolated group I00 to I07.
- Protective Earth terminal for communication ports. Shall be externally connected to ground.
- Use Ethernet cables informed onRelated Productssection.
- Typical connection of current analog input (field device with power supplied separately from analog signal).
- Typical connection of current analog input (field device with power supply with the analog signal, 2-wire).
- Typical sensor connection with 12Vdc power supply and SDI-12 communication.
6.2. Physical Dimensions
Dimensions in mm.
Configuration and Usage
The configuration of the Nexto Logger NL717 in a LoRaWAN network is performed
through an application for CPUs developed in the MasterTool IEC XE software in
conjunction with the LoRa “NextoLora” library. Will be described in this topic
the entire routine of creating an application and configuring the NL717 in a
LoRa network, from registering the activation keys to using the library to
send and receive data through the LoRaWAN network.
Registering a device in a LoRaWAN network requires prior configuration of the
device on the server where it will be registered. This configuration will
contain the radio frequency parameters that must be applied as well as the
server access keys. During the creation of a new device (called end node) in
the server, several configurations should be noted for later use when
configuring Nexto Logger in the LoRaWAN network.
Among these configurations are:
- Frequency Plan (or Regional Band): This parameter defines the frequency plan that the device will operate on. The setting of this parameter must be in absolute parity between all elements that involve the LoRaWAN network, such as the server, Gateway and End Device. (e.g. AU915).
- Frequency sub-bands (or FSBs): Some frequency plans also offer the configuration of communication sub-bands. As with frequency plans, sub-bands must be configured accordingly on all network elements (e.g. FSB1).
- Adaptive Data Rate (ADR): Defines the optimization of the choice of radio parameters in the device. When enabled, it allows the server to choose the parameters optimally (e.g. TRUE).
- Unique Device Identifier (or Device EUI): Unique identifier of an End node, can be generated by the server or provided by the device itself. This identifier is a 64-bit key, usually expressed in 8 hex bytes (e.g. [01 02 03 04 05 06 07 08]).
- Class: Defines the mode in which the end node will communicate over the LoRaWAN network. This parameter should be chosen according to the needs of energy use. Class A devices use less energy with some penalties in communication availability. Class C devices are always available on the network, but use more energy
- Activation Modes: Defines the mode in which the end device will be registered to the server. There are two ways of doing the device validation procedure on the server. The first, called Over the air activation (OTAA), activates the device via radio communication. During this process, the device communicates with the server using two identification keys for the server and the application, and then the security and encryption keys are exchanged between the server and the device in a secure manner. This activation process is called JOIN and ensures that the encryption keys are hidden, maintaining the security of the network and the secrecy of the communication content.
The two keys required for the JOIN by OTAA process are:
- Unique application identifier (APP EUI): 8 byte key. (e.g. [01 02 03 04 05 06 07 08]).
- Application Key (APP Key): 16 byte key (e.g. [01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10]).
The second activation mode is called Activation By Personalization (ABP), in this activation mode the security keys are generated by the server and loaded manually on the end device. Since these keys are responsible for encrypting the content of the communication, this activation mode is highly insecure and should not be used in applications that demand high reliability. This activation mode does not perform the JOIN process, since the keys will be written directly to the device. Altogether there are two security keys and one device address.
- Application session key (APP Session KEY): 16 byte key.
- Network session key (NWK Session KEY): 16 byte key.
- Device Address (Dev ADDR): 4 byte key (e.g. [01 02 03 04]).
Once you have the access keys and the other activation configuration
parameters for the device, you can start the device on the network without
difficulty. The first step is to open the MasterTool IEC XE development
software and create a new project.
The procedure for creating a new project can be seen in the following figures.
When opening MasterTool IEC XE access the menu “File” and then “New Project…”
as illustrated in the figure below.Next, select the “MasterTool Standard Project”
template, indicate the project name and path to be saved, and continue by
clicking the “OK” button as illustrated in the figure below.Then choose the target device for the application. In this case,
you should configure the Datalogger NL717 device, found in the “Datalogger
Controllers” category. As illustrated in the figure below.With the new project
created it’s necessary to add the LoRaWAN interface library. To do this,
access the “Library Manager” menu. The figure below illustrates the menu in
question.A new
library management tab will open in the main window of MasterTool IEC XE,
click on the “Add Library” menu to access the menu for adding a new library to
the project. The figure below illustrates the location of the access
button.In the search
bar type “Nexto” and in the results you will find the “LibNextoLora” library
as shown in the figure below.
Double-click on it to add it to the project.Once included in the project it is
possible to check the functional block of use, as well as the associated data
structures.
The block called LORA_MASTER is the only user interface of the library and
provides all the operating states of the device through its state
structures.To configure the LibNextoLora library
blocks, see the following sections.
7.1.Usage of the LibNextoLora library
7.1.1.Configuration
The LibNextoLora library has a main block called LORA_MASTER, this block is
responsible for executing the configuration and usage routines for the LoRa
device. Device related settings are performed via the LORA_CONFIG input of the
LORA_MASTER block, which receives a data structure of type
LORA_RADIO_SET_PARAMETERS. Before executing the LORA_MASTER block via the
ENABLE input, it is necessary to configure and assign its input
parameters.
7.1.1.1.LORA_RADIO_SET_PARAMETERS
With the development environment configured and having the keys and
configuration parameters, it is possible to start the development of the
application that will configure the device in the LoRaWAN network.
The device-related settings are made via the LORA_CONFIG input of the
LORA_MASTER block, which receives a data structure of type
LORA_RADIO_SET_PARAMETERS to be used as input parameters.
The use of this structure is quite simplified and can be seen in the figure
below. Besides the access keys, which should be passed via a pointer to the
array where they are stored, there is a variable type for each given
parameter, in these types are listed the applicable configuration options
available.The types of
configuration variables and their respective available options are:
- REQUEST: Enables a new configuration on the device, if the device does not yet have a valid join.
- FORCE_CONFIG: Forces a new configuration on the device, even if the device already has a valid join.
- REGIONAL_BAND: Defines the frequency band that will be used for LoRa communication. Frequency bands are groupings of frequency channels in which the device will communicate via the LoRa protocol. Each country has its own regulations and pre-definitions for the use of the radio spectrum for communication, so the device must operate in different frequency bands that fit the laws of the region where it will be used. Configuration options:
- According to the region where it is used. In Brazil: AU915.
- DEV_EUI: Unique device identification key. Receives the pointer to the vector containing the saved key.
- MAX_PAYLOAD_LEN: Defines the maximum size of the message that can be sent. Represents the maximum size in bytes that the device can send. Takes the integer value from 1 up to a maximum of 36.
- ACT_CLASS: The activation mode refers to the way the device sends and receives messages. When activated in ClassA the device prioritizes saving power and in ClassC prioritizes the availability of sending and receiving messages. It is recommended to use ClassC in all cases except when there is a need to save power. Configuration options:
- ClassA
- ClassC
- FSB: Frequency sub-band, within the regional bands there are also working frequency sub-divisions, the so-called frequency sub-bands (FSB). This should be chosen in parity with the working subband chosen in the Gateways and the server, by default the NL717 and GW700 devices use FSB2 for working. Configuration options:
- FSB1
- FSB2
- FSB3
- FSB4
- FSB5
- FSB6
- FSB7
- FSB8
-
ADAPTATIVE_DATA_RATE: The Data Rate parameter of LoRa communication indicates the bandwidth at which the message will be sent. The higher the Data Rate, the greater the capacity for sending data, i.e. more data can be sent in a single message. Conversely, the higher the Data Rate, the less effective the communication over long distances, significantly decreasing the communication distance. When the ADAPTATIVE_DATA_RATE mode is activated, the server takes care of choosing the ideal Data Rate for device communication, this adaptation process is time consuming and can cause a lot of communication instability, with few real gains associated with it. It is recommended to disable this function, so the device will communicate at the lowest Data Rate, but having a significant gain in communication distance.
-
ACT_TYPE: Mode in which the device will be joined on the server. The first join mode, OTAA, allows the device to exchange access and encryption keys with the server during the join process. In this way the encryption keys are hidden and secure during the entire process, this is the most secure mode of join. In the second join mode, ABP, the access and encryption keys are pre-generated and loaded on the device before the join process. This mode offers a faster and easier join process but is less secure, since the encryption keys can be misappropriated. Configuration options:
1. OTAA
2. ABP -
ABP_KEYS: Receives a structure of type LORA_ABP_CONFIGURATION that must be filled in if the choice of join mode is of type ABP.
-
LORA_ABP_CONFIGURATION: Different from the others, which list available options, this is a data structure that contains the three keys needed for the join of ABP type.
1. ABP_APP_SESSION_KEY: Receives the pointer of a vector that contains the saved key;
2. ABP_NWK_SESSION_KEY: Receives the pointer of a vector that contains the saved key;
3. ABP_DEV_ADDR: Receives the pointer of a vector that contains the saved key. -
OTAA_KEYS: Receives a structure of type LORA_OTAA_CONFIGURATION that must be filled in if the choice of join mode is of type OTAA.
• LORA_OTAA_CONFIGURATION: Data structure that contains the two keys needed for the join of OTAA type.
1.OTAA_APP_EUI: Receives the pointer of a vector that contains the saved key;
2.OTAA_APP_KEY: Receives the pointer of a vector that contains the saved key.Once the configuration structure LORA_RADIO_SET_PARAMETERS has been properly filled in the LORA_CONFIG input and the ENABLE input of the LORA_MASTER block is set to TRUE, the block will run and start the library configuration and join of the LoRa device on the server with the entered keys, the progress of the process can be observed through the LORA_STATE output of the block.
7.1.2. Current status of the library
The LORA_STATE output informs the user of the current library and device state
via the enumerable LORA_LIB_STATE that identifies what is happening in seven
states. These are:
- DISABLED: It informs that the block is disabled;
- INITIALIZING: It informs that the block is initializing;
- INITIALIZATION_FAIL: It informs that some failure occurred during block initialization;
- INTERNAL_ERROR: It informs that there are internal errors preventing the block from working;
- NOT_JOINED: It informs that the block has joined correctly but the device is not yet activated;
- JOINED_RDY_TO_SEND: It informs that the device is joined and ready to send messages;
- JOINED_SENDING_DATA It informs that the device is joined and performing the LoRa messaging process.
Once initialized, the block will perform a device join verification process,
if the device already contains valid join in-formation, this information will
be used unless a new forced join is requested by the user via the FORCE_CONFIG
variable of the LORA_RADIO_SET_PARAMETERS data structure. The join process is
sometimes time consuming and can take anywhere from seconds to hours in
extreme cases to complete successfully (it depends on the signal quality
between the device and the LoRa Gateway). During the join process the library
will remain in the NOT_JOINED state and will change to JOINED_RDY_TO_SEND once
successfully joined.
Once joined, the device is ready to send LoRa messages. The process is done
via the LORA_SEND input of the block that must be supplied with a structure of
type LORA_SEND_PARAMETERS in this structure are all the necessary information
for sending a message.
7.1.3. Message sending configuration
7.1.3. 1.LORA_RADIO_SEND_PARAMETERS The description of each of the variables in
this data structure is as follows:
- REQUEST: Requests a new message sending;
- LORA_CONFIRMATION: Sets the message confirmation mode;
- LORA_PYLD_LEN: Informs the size of the message that will be sent;
- LORA_PYLD_BUFF: Address of the buffer that contains the message that will be sent.
The state of the block will remain in JOINED_SENDING_DATA while the sending
process is being performed, this process takes about 30 seconds. Once the
sending is complete, the library state returns to JOINED_RDY_TO_SEND informing
that the block is ready for a new sending.
7.1.4. Received messages
Messages received by the LoRa device can be viewed via the PAYLOAD_RECEIVED
output of the block, a data structure of type PYLD_RECEIVED is used to report
the received message data, these are:
- PYLD_COUNTER: Informs the total number of messages received;
- PYLD_LEN: Informs the size of the received message;
- PYLD_BUFF: Buffer that contains the received message.
7.1.5. Block Diagnostics
Via the STATUS output from the LORA_MASTER main block, it is possible to check
all the information regarding the LoRa device, as well as the codes of the
possible errors that might happen.
This output returns a data structure of type LORA_TOTAL_STATUS. This structure
has three outputs (ERROR_CODE, LORA_GET_PARAM and ERROR_STATUS).
A binary variable is associated with the ERROR_STATUS output, which returns
TRUE when an error occurs. The structures associated with the other outputs
are:
- TOTAL_ERROR_LIST: Associated with the ERROR_CODE output, it contains a complete list of possible error causes, plus the error code of the last occurrence;
- LORA_GET_PARAM: Associated with the LORA_GET_PARAM output, it contains the activation information that was read from the LoRa device.
Manuals
For further technical details, configuration, installation and programming,
the table below should be consulted.
The table below is only a guide of some relevant documents that can be useful
during the use, maintenance, and programming of this product.
Code | Description | Language |
---|---|---|
CE114000 | Nexto Series — Technical Characteristics | English |
MU214600 | Nexto Series User Manual | English |
MU299609 | MasterTool IEC XE User Manual | English |
MP399609 | MasterTool IEC XE Programming Manual | English |
MU214606 | MQTT User Manual | English |
NAP165 =I
NAP165_ing| OPC UA Communication with ALTUS Controllers| English
Table 15: Documents Related