ALTUS HX1120 32 DI 125 Vdc Module with Time Stamping Installation Guide
- June 5, 2024
- ALTUS
Table of Contents
ALTUS HX1120 32 DI 125 Vdc Module with Time Stamping
Legend
Fixing locks
Module Slot locking slider
Label for module identification
Diagnostic LED and switch
Status and diagnostic display
10 pin terminal blocks
Set of terminal blocks
Typical usage of sink digital inputs, C1 is the 0 Vdc common to input group
I00 to I03
Typical usage of source digital inputs, C2 is the +125 Vdc common to input
group I04 to I07
The module power supply is derived from the connection to the backplane rack,
not requiring external connections
The module is grounded through the backplane rack
Features
Minimum / Nominal / Maximum Input Voltage: 91 Vdc / 125 Vdc / 135 Vdc
Current Consumption from Backplane Rack Power Supply: 195 mA
Installation
Digital Input Terminals: 1A to 4A, 6A to 9A, 1B to 4B, 6B to 9B, 1C to 4C, 6C
to 9C and 1D to 4D, 6D to 9D Common Input Terminals: 5A, 10A, 5B, 10B, 5C,
10C, 5D and 10D
The module is grounded through backplane racks.
Main Related Products
HX9402 – 10 pin terminal block
Warning
Products with broken warranty seal are not covered in warranty.
| For further information about programming or installation, see the Product
Datasheet (CE123300) or the Utilization Manual (MU223600) available on Altus
website
---|---
Cautions:
| The device is sensitive to static electricity (ESD). Always touch in a
metallic grounded object before handling it.
---|---
| Hadron Xtorm Series can operate with voltage up to 250 Vac. Special care
must be taken during the installation, which should only be performed by
qualified technical personnel. Do not touch the field wiring when in
operation.
---|---