Knightsbridge BF1430EM 6000K 291mm Emergency LED Bulkhead Instruction Manual
- June 4, 2024
- Knightsbridge
Table of Contents
Knightsbridge BF1430EM 6000K 291mm Emergency LED Bulkhead
GENERAL INSTRUCTIONS
These instructions should be read carefully and retained after installation by the end user for future reference and maintenance. These instructions should be used to aid installation of the following products: BF1430EM / BF2440EM
SAFETY
- This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician
- Please isolate mains prior to installation or maintenance
- Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of the circuit cable, fuse, or circuit breaker
- Please note the IP (Ingress Protection) rating of this luminaire when deciding the location for installation
- This product is Class II double insulated
- This product is IP44 rated
INSTALLATION
Note – If this luminaire is being used in conjunction with an external PIR or sensor, please confirm with the manufacturer of the sensors that they are compatible with LED luminaires.
- Provide power to the required point of installation (refer to BS7671 for correct cabling methods). Suitable IP rated junction boxes should be used where required
- Remove the diffuser by turning the three diffuser clips 90° (see Fig. 1)
- Remove the three fixing screws securing the LED plate
- Remove the LED plate and disconnect from the driver (via the DC socket) and emergency inverter .
- Drill the fixing holes in the rear of the fitting. Mark the location of the fixing holes and drill ensuring not to nge with any gas/water pipes or electrical cables .
- Feed the mains cable through the rubber grommet to retain IP rating, and secure the baseplate to the surface.
- Ensuring correct polarity is observed, carefully wire as shown in Fig. 2
- Ensure the battery is connected via the plug and socket to the emergency inverter
- Refasten the LED plate screws.
- Reattach the diffuser by rotating clockwise.
- Switch on and check f r correct operation, ensuring the green indicator LED is illuminated.
- We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying out an emergency duration test.
- If the batteries have b en left in a discharged state for an extended period, we recommend that one or more charge and discharge ycles are completed which should help to restore the battery capacity
WARNING
This luminaire must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing. Irreparable damage will occur if this instruction is not followed
GENERAL
This product contains an LED light source which can be replaced by the end
user and a control gear which can be replaced by a professional.
Clean the external surfaces with a damp cloth using a mild solution of
detergent and warm water only, do not use aggressive cleaning products or
solvents which may damage the product. Do not use any source of high-pressure
washers to maintain or clean this luminaire. This product is non-dimmable.This
product should be dismantled for disposal when it reaches the end of its life.
Please see website for dismantling instructions. This product should be
recycled in the correct manner when it reaches the end of its life. Check
local authorities for where facilities exist. The batteries in this luminaire
are Nickel Cadmium and must be disposed of correctly. Please contact the local
authorities for the disposal of this toxic waste.
WARRANTY
This product has a warranty of 3 years (excluding the battery) from date of purchase. Failure to install this product in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the batch code will invalidate the warranty. If this product should fail within its warranty period, it should be returned to the place of purchase for a free of charge replacement. ML Accessories does not accept responsibility for any installation costs associated with the replacement product. Your statutory rights are not affected. ML Accessories reserve the right to alter product specification without prior notice.
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266
- Daily check – check LED charge indicator is illuminated
- Monthly functional test – simulate a mains supply failure for approx. 30 seconds by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
- Annual 3-hour duration test – simulate a mains supply failure for 3-hour continuous test by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
- If the luminaire fails any of the above tests, please contact a qualified electrician. See below/overleaf for test record sheet
INTERNATIONAL CONTACT DETAILS
ML Accessories Limited LU5 4LT www.mlaccessories.co.uk
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>