APC BR1500G-GR Power Saving Back-UPS Pro Operation Manual
- June 12, 2024
- APC
Table of Contents
- APC BR1500G-GR Power Saving Back-UPS Pro
- Inventory
- Important Safety Messages
- Connect the Battery
- PowerChute™ Personal Edition Software
- Connect the Equipment
- Operation
- Unit sensitivity
- Front panel
- Alerts and System Events
- Event Icons
- System Events
- Function Button Quick Reference
- Troubleshooting
- Specifications
- **Warranty
- FAQ’s
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
APC BR1500G-GR Power Saving Back-UPS Pro
Inventory
Important Safety Messages
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during the installation and maintenance of the UPS and batteries.
- This UPS is intended for indoor use only.
- Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
- Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
- The battery typically lasts for three to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor-quality AC power, and frequent short-duration discharges will shorten battery life.
- Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
- Replace the battery at least every 5 years or at the end of its service life, whichever is earlier.
- Replace the battery immediately when the UPS indicates battery replacement is necessary.
- Replace batteries with the same number and type of batteries as originally installed in the equipment.
- Replace the battery immediately when the UPS indicates a battery over-temperature condition, or when there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input and disconnect the batteries. Do not operate the UPS until the batteries have been replaced.
Failure to follow these instructions can result in minor or moderate injury
and equipment damage.
For the recycling battery information, please go to
apc.com/recycle
- CAUTION: Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions.
- CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
- CAUTION: Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic.
- CAUTION: Before replacing batteries, remove conductive jewelry such as chains, wristwatches, and rings. High energy through conductive materials could cause severe burns.
- CAUTION: Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces.
- CAUTION: A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries:
- Disconnect the charging source prior to connecting or disconnecting battery terminals.
- Do not wear any metal objects including watches and rings.
- Do not lay tools or metal parts on top of batteries.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
- Determine if battery is either intentionally or inadvertently grounded. Contact with any part of a grounded battery can result in electric shock and burns by high short-circuit current. The risk of such hazards can be reduced if grounds are removed during installation and maintenance by a skilled person.
- This manual can be downloaded from APC by Schneider Electric Website www.apc.com.
Connect the Battery
Charge the battery for at least 16 hours before use.
PowerChute™ Personal Edition Software
Overview
PowerChute Personal Edition Software allows you to use your computer to
access additional power protection and management features of the Back-UPS.
Using PowerChute, you can:
- Preserve work in progress during a power outage by putting your computer into Hibernate mode. When the power returns, the computer will appear exactly as it did before the power outage.
- Configure the Back-UPS management features, such as power-saving outlets, shutdown parameters, audible alarms, and more.
- Monitor and view the status of the Back-UPS, including the estimated runtime, power consumption, power event history, and more.
Available features will vary by Back-UPS model and operating system. If you choose not to install PowerChute, the Back-UPS will still provide backup power and power protection to connected equipment. However, you will only be able to configure a limited number of features using the display interface.
Compatibility
PowerChute is compatible with Windows operating systems only. For a
detailed list of supported operating systems, go to
www.apc.com, select Software & Firmware. For Mac
operating systems, we recommend using the native shutdown application (within
System Preferences) which recognizes your battery backup and allows you to
configure the shutdown of your system during power outages. To access this
application, connect a USB cable from the Back-UPS DATA PORT (POWERCHUTE PORT)
to a USB port on your computer, and see the documentation provided with your
computer.
Installation
Use the USB cable to connect the Data port on the UPS to the USB and Serial
port on your computer. Download PowerChute™ Personal Edition Software from
www.apc.com/pcpe. Select the appropriate operating
system and follow directions to download and install the software.
Connect the Equipment
Battery Backup and Surge Protected outlets
When the Back-UPS is receiving input power, the Surge Protection only
outlets and the Battery Backup with Surge Protection outlets will supply power
to connected equipment. During a power outage or other utility problems, only
the Battery Backup outlets receive power for a limited time from the Back-UPS.
Connect equipment such as printers, FAX machines, scanners, or other
peripherals that do not need battery backup power to the Surge Protection Only
outlets. These outlets provide full time protection from surges even if the
Back-UPS is switched off.
Master and Controlled outlets
To conserve electricity, when the device connected to Master Outlet goes
into Sleep or Standby mode, or turns off, the Controlled by Master device(s)
will shut down as well, saving electricity. Connect a master device, such as a
desktop computer or audio/visual receiver to the Master outlet. Connect
peripheral devices such as a printer, speakers, or a scanner to the Controlled
by Master outlets.
- USB and Serial Data port: To use PowerChute Personal Edition, connect the supplied USB software cable or serial cable.
- Telephone ports: Connect a telephone cable to the In port, and a modem to the Out port.
- Ground screw: Connect the ground wire from another surge suppression device such as a network or data line surge protector to the ground screw on the Back-UPS.
- Surge Protection outlets, Controlled by Master outlet: These outlets provide surge protection during a power outage. These outlets will disconnect from A/C power during a power outage, or in the event that the Master outlet goes into Sleep mode.
- Surge Protection outlets: These outlets provide full-time surge protection when the unit is turned on or off. Connect a printer, scanner or other devices that do not require battery backup protection.
- AC Power Cable: Connect the Back-UPS to A/C power.
- Battery Backup Outlets with Surge Protection: During a power outage or other utility problems, these outlets provide power from the Back-UPS battery. Connect essential equipment such as desktop computers, computer monitors, modems or other data-sensitive devices to these outlets.
- Battery Backup, Controlled by a Master outlet with Surge Protection: During a power outage or other utility problems, these outlets provide power from the Back-UPS battery. These outlets will disconnect from A/C power during a power outage, or in the event that the Master outlet goes into Sleep mode. Connect essential equipment such as desktop computers, computer monitors, modems or other data-sensitive devices to these outlets.
- Master outlet: Connect the master device to this outlet, in most scenarios, this will be the main computer.
- Gigabit Ethernet surge-protected ports: Use an Ethernet cable to connect a modem to the IN port, and a computer to the OUT port.
- External Battery Pack connector BR1500G-GR model only: Connect an external battery pack to provide additional battery backup runtime.
Operation
Power-Saving Function:
To conserve electricity, configure the Back-UPS to recognize a Master
device, such as a desktop computer or an A/V receiver, and Controlled
peripheral devices, such as a printer, speakers, or a scanner. When the Master
device goes into Sleep or Standby mode or is switched OFF, the Controlled
device(s) will be switched off as well, saving electricity.
Enable the Power-Saving function:
Press and hold MUTE and DISPLAY simultaneously for two seconds. The Back-UPS
will beep to indicate that the feature is enabled. The leaf icon on the
display will illuminate.
Disable the Power-Saving function:
Press and hold MUTE and DISPLAY simultaneously for two seconds. The Back-UPS
will beep to indicate that the feature is disabled. The leaf icon on the
display will go dark.
Setting the threshold:
The amount of power used by a device in Sleep or Standby mode varies between
devices. It may be necessary to adjust the threshold at which the Master
outlet signals the Controlled outlets to shut down.
- Be sure a master device is connected to the Master outlet. Put that device into Sleep or Standby mode, or turn it OFF.
- Press DISPLAY and MUTE simultaneously and hold for six seconds, until the leaf icon flashes three times and the Back-UPS beeps three times.
- The Back-UPS will now recognize the threshold level of the Master device and save it as the new threshold setting.
Power-Saving Display
The display interface can be configured to be continuously illuminated, or
to save energy, it can be configured to go dark after a period of inactivity.
- Full Time Mode: Press and hold DISPLAY for two seconds. The display will illuminate and the Back-UPS will beep to confirm the Full-Time mode.
- Power-Saving Mode: Press and hold DISPLAY for two seconds. The display will go dark and the Back-UPS will beep to confirm the Power-Saving mode. While in Power-Saving Mode, the display will illuminate if a button is pressed, it goes dark after 60 seconds of no activity.
Unit sensitivity
Adjust the sensitivity of the Back-UPS to control when it will switch to battery power; the higher the sensitivity, the more often the Back-UPS will switch to battery power.
- Be sure the Back-UPS is connected to A/C power, but is OFF.
- Press and hold the POWER button for six seconds. The LOAD CAPACITY bar will flash on and off, indicating that the Back-UPS is in programming mode.
- Press POWER again to rotate through the menu options. Stop at selected sensitivity. The Back-UPS will beep to confirm the selection. Front Panel Buttons and Display Interface
Use the three buttons on the front panel of the Back-UPS and the display interface to configure the Back-UPS.
Front panel
- Mute button
- Power On/Off button
- Display button
- Display interface
Alerts and System Events
Audible Alerts
- Four Beeps Every 30 Seconds: Back-UPS is running on battery. You should consider saving any work in progress.
- Continuous Beeping: Low battery condition and battery run-time is very low. Promptly save any work in progress, exit all open applications, and shut down the operating system.
- Continuous tone: Battery Backup outputs are overloaded.
- Chirps for 1 Minute every 5 hours: The battery is not able to pass the automatic diagnostic test and should be replaced.
Event Icons
System Events
The Back-UPS will display these event messages. Contact APC Technical Support.
Function Button Quick Reference
Troubleshooting
Problem | Possible Cause | Corrective Action |
---|---|---|
Back-UPS will not turn on. | The Back-UPS is not connected to A/C | Be |
sure that the Back-UPS is securely connected to
| power.| an A/C outlet.
| The circuit breaker has been tripped.| Disconnect non-essential equipment
from the Back-
| | UPS. Reset the circuit breaker. Re-connect
| | equipment one item at a time. If the circuit breaker is
| | tripped again, disconnect the device that caused the
| | trip.
| The internal battery is not connected.| Connect the battery.
| The A/C input voltage is out of range.| Adjust the transfer voltage and
sensitivity range.
The Back-UPS does not| Be sure that essential equipment is not|
Disconnect equipment from the SURGE ONLY outlet
provide power during an A/C| plugged into a SURGE ONLY outlet.| and re-
connect to a Battery Backup outlet.
power outage.| |
The Back-UPS is operating on| The plug has partially pulled out of the
wall| Be sure that the plug is fully inserted into the wall
battery power, while| outlet, the wall outlet is no longer receiving|
outlet. Be sure that the wall outlet is receiving A/C
connected to A/C power.| A/C power, or the circuit breaker has been|
power by checking it with another device.
| tripped.|
| The Back-UPS is performing an automatic| No action is necessary.
| self test.|
| The A/C input voltage is out of range, the| Adjust the transfer voltage and
sensitivity range.
| frequency is out of range, or the waveform|
| is distorted.|
The Back-UPS does not| Battery Backup outlets may be fully or|
Disconnect non-essential equipment from the
provide the expected amount| improperly loaded.| Battery Backup outlets
and connect the equipment to
of backup time.| | SURGE ONLY outlets.
| The battery was recently discharged due to| Charge the battery cartridge for
16 hours.
| a power outage and has not fully recharged.|
| The battery has reached the end of its| Replace the battery.
| useful life.|
The REPLACE BATTERY| The battery has reached the end of its| Replace the
battery.
indicator is illuminated.| useful life.|
The OVERLOAD indicator is| The equipment connected to the Back-UPS|
Disconnect non-essential equipment from the
illuminated.| is drawing more power than the Back-UPS| Battery Backup
outlets and connect the equipment to
| can provide.| SURGE ONLY outlets.
The SYSTEM EVENT indicator| There is an internal fault detected.|
Determine which internal detected fault message is
is illuminated, all the front| | displayed by matching the number
displayed on the
panel indicators are flashing.| | LCD with the corresponding event
Message (see
| | System Events) and contact APC Technical Support.
Power is not supplied to some| Power to the Controlled outlets has|
Confirm that the correct peripherals are connected to
outlets.| intentionally been turned off.| Controlled outlets. If this
feature is not desired,
| | disable the Power-Saving Master and Controlled
| | outlets.
The Controlled outlets are not| The Master Outlet threshold may be|
Adjust the threshold when the Master outlet signals
supplying power, even though| incorrectly set.| the Controlled outlets
to shut down.
the Master device is not in| |
sleep mode.| |
Specifications
Model | BR1200G-GR | BR1500G-GR |
---|---|---|
VA | 1200 VA | 1500 VA |
Maximum Load | 720 W | 865 W |
Nominal Input Voltage | 230 V | |
Online Input Voltage Range | 176 V- 294 V | |
Automatic Voltage Regulation | 188 V- 216 V +11.2% |
252 V- 282 V -11.2%
Frequency Range| 50/60 Hz ± 1 Hz
On-battery wave shape| Step-approximated sine-wave
Typical Recharge Time| 8 hours
Transfer Time| 10 ms, maximum
Operating Temperature| 0º to 40º C (32º to 104º F)
Storage Temperature| 5º to 45º C (23º to 113º F)
Unit Dimensions| 30.1 × 11.2 × 39 cm (11.9 × 4.4 × 15.3 in)
Unit Weight| 12.8 kg (28.2 lbs)| 13.4 kg (29.5 lbs)
Interface| Serial, USB
On-Battery Runtime| Go to: www.apc.com
Replacement Battery| The battery cartridge typically lasts 3 to 6 years.
Environmental factors impact battery life. High temperatures, poor quality A/C
power, and frequent, short-duration discharges will shorten battery life. To
order a replacement battery cartridge, see Replace Battery.
Humidity| 0 to 95% relative humidity, non-condensing
Pollution Degree| 2
Overvoltage category| II
Applicable power grid distribution system| TN Power system
Applicable standards| IEC 62040-1
International Protection Code| IP20
Replace Battery
Deliver the used battery to a recycling facility. Replace the used battery
with an APC by Schneider Electric-approved battery. Replacement batteries can
be ordered through the APC by Schneider Electric Web site,
www.apc.com. The battery replacement part for Back-UPS
BR1200G-GR and BR1500G-GR is APCRBC124.
APC by Schneider Electric IT Customer Support Worldwide
For country-specific customer support, go to the APC by Schneider Electric
Web site, www.apc.com.
**Warranty
**
The standard warranty is two (2) years from the date of purchase. APC’s standard procedure is to replace the original unit with a factory- reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an APC Technical Support representative. APC will ship the replacement unit once the defective unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to APC. APC pays ground freight transportation costs to ship the replacement unit to the customer.
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
- Review the TROUBLESHOOTING section of the manual to eliminate common problems.
- If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com.
- a. Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models.
- b. Call APC Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
- c. If the unit is under warranty, the repairs are free.
- d. Service procedures and returns may vary internationally. Refer to the APC Web site for country-specific instructions.
- Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty. For UPS, always DISCONNECT THE BATTERY before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The battery may remain in the unit.
- Write the RMA# provided by Customer Support on the outside of the package.
- Return the unit by insured, pre-paid carrier to the address provided by Customer Support.
© 2022 APC by Schneider Electric. APC, the APC logo, Back-UPS, and PowerChute are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are the property of their respective owners.
FAQ’s
What is the capacity or wattage of the APC BR1500G-GR Back-UPS Pro?
The APC BR1500G-GR has a capacity of 1500VA or 865 watts, making it suitable for powering multiple devices during power outages.
How long can the APC BR1500G-GR Back-UPS Pro provide backup power?
The backup runtime of the APC BR1500G-GR depends on the power load connected to it. Typically, it can provide several minutes to an hour of backup power, allowing you to save your work and safely shut down your devices during an outage.
Does the APC BR1500G-GR Back-UPS Pro have surge protection?
Yes, the APC BR1500G-GR features surge protection to safeguard connected devices from voltage spikes and surges, providing additional protection against electrical damage.
How many outlets does the APC BR1500G-GR Back-UPS Pro have?
The APC BR1500G-GR has ten outlets in total, with five outlets providing battery backup and surge protection, and the remaining five outlets offering surge protection only.
Can the APC BR1500G-GR Back-UPS Pro be used with a computer and other devices?
Yes, the APC BR1500G-GR is designed to provide backup power and surge protection for computers, networking equipment, gaming consoles, home entertainment systems, and other sensitive electronic devices.
Is the APC BR1500G-GR Back-UPS Pro compatible with Mac computers?
Yes, the APC BR1500G-GR is compatible with both Windows and Mac operating systems.
Does the APC BR1500G-GR Back-UPS Pro support automatic voltage regulation (AVR)?
Yes, the APC BR1500G-GR includes automatic voltage regulation (AVR) technology, which helps stabilize the incoming voltage and protects connected devices from Undervoltage and overvoltage conditions.
Can the APC BR1500G-GR Back-UPS Pro be monitored or controlled remotely?
Yes, the APC BR1500G-GR offers the capability to connect to a computer via a USB or Ethernet port, allowing for remote monitoring and control using APC's PowerChute software.
Does the APC BR1500G-GR Back-UPS Pro have a replaceable battery?
Yes, the APC BR1500G-GR is equipped with a user-replaceable battery. When the battery reaches the end of its life, it can be easily replaced without needing to replace the entire unit.
Can the APC BR1500G-GR Back-UPS Pro be used in a rack-mount configuration?
No, the APC BR1500G-GR is a tower-style UPS and is not designed for rack-mount installations. However, APC offers rack-mountable UPS models suitable for such setups.
Does the APC BR1500G-GR Back-UPS Pro provide protection against data line surges?
Yes, the APC BR1500G-GR offers data line surge protection for connected Ethernet network and phone lines, safeguarding your equipment from electrical surges that may travel through these connections.
Is the APC BR1500G-GR Back-UPS Pro energy-efficient?
Yes, the APC BR1500G-GR incorporates power-saving features and automatic energy efficiency modes that help reduce energy consumption, saving you money and contributing to a greener environment.
Download This PDF Link:APC BR1500G-GR Power Saving Back-UPS Pro Operation Manual
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>