hager TYMS646T 6X Heating Actuator Instruction Manual
- June 12, 2024
- hager
Table of Contents
**hager TYMS646T 6X Heating Actuator Instruction Manual
**
Assembly instructions
6X heating actuator KNX Secure for 24/230 V valve drives
ETS ≥ 5.6.x
Easytool ≥ 5.3.x
The Regulatory Compliance Mark (RCM) is a trademark owned by the electrical regulator (Regulatory Authorities (RAs)) and Australian Communications Media Authority (ACMA).
ROHS
What In the Box
230 V ~ | max C1/C2/C3/C4/C5/C6 | max C1+C3+C5 / C2+C4+C6 |
---|---|---|
1 t < 200 ms | 2,2 A | 6,6 A |
2 200 ms < t < 4.30 min | 0,6 A | 1,8 A |
3 t > 4.30 min | 45 mA | 135 mA |
24 V ~ | max C1/C2/C3/C4/C5/C6 | max C1+C3+C5 / C2+C4+C6 |
1 t < 200 ms | 2,2 A | 2,2 A |
2 200 ms < t < 4.30 min | 0,9 A | 0,9 A |
3 t > 4.30 min | 500 mA | 500 mA |
| | OK
---|---|---
| |
| | OK
| |
| | Short circuit detection running
| | Short circuit detected
| | Overload detected, load shedding running
| |
| | 50 %
| | 100 %
Name and content of hazardous substances in products
- Part name : Lead
- Elektronic Bord : X 0 0 0
This table is prepared in accordance with the provisions of SJ
0: indicates that said hazardous substance contained in all of the homogeneous materials for this part is below the limit requirement of GB
Safety instructions
Electrical devices may only be installed and assembled by a qualified electrician in accordance with the relevant installation standards, guidelines, regulations, directives, safety and accident prevention regulations of the country.
Failure to comply with these installation instructions may result in damage to the device, fire or other hazards.
These instructions are an integral component of the product and must be retained by the end user.
Design and layout of the device
- Power supply connection (N, L)
- Connection of the thermal valve drives
- Top group: Outputs C1 + C3 + C5
- Bottom group: Outputs C2 + C4 + C6
- Auto/Manu change-over switch ( auto/ )
- Operation button for manual operation with status LED
- Illuminated programming button
- Labelling field
- NX bus connection terminal
Function
Correct use
- Switching of thermoelectric valve drives 24/230 V AC
- Mounting on DIN rail according to IEC 60715 Installation and electrical connection
DANGER!
Electric shock when live parts are touched!
An electric shock can lead to death!
- Isolate all connection cables before working on the device and cover any live parts in the area!
- Install the device on the DIN rail and connect it.
Commissioning
Systemlink: Loading the physical address and application software
For detailed information on commissioning in systemlink or KNX Secure mode, please refer to the product-specific QR code.
Technical data
- KNX Medium …………………………………………TP1-256
- Supply voltage KNX …………………..21…32 Vs SELV
- Supply voltage of the product and the valves
- − 230 V~ +10/-15% 50/60 Hz
- − 240 V~ +/-6% 50/60 Hz
- − 24 V~ +/- 5% 50/60 Hz
- Surge voltage ………………………………………………4 kV
- Protection switch ………………………………………… 16 A
- Operating altitude …………………………….max. 2000 m
- Degree of contamination ……………………………………2
- Heat class ………………………………………………………..2
- Operating temperature ………………………-5° … +45°C
- Current consumption KNX ……………….. typ. 18.5 mA
- Dimension ……………………….4 modules, 4 x 17.5 mm
- Action type …………………………………………………… 2Y
- Voltage and current signalled for EMC testing of
- interference radiation ……….. 230 V~ 1 A / 24V~ 1A
- Power loss ……………………………………….. max. 2.7 W
References