LAPP AUTOMAATIO W-M-TRACE Trace Heating Sensor Instruction Manual

October 30, 2023
LAPP AUTOMAATIO

EPIC® SENSORS
TRACE HEATING SENSOR
TYPE W-M-TRACE, 2xW-M-TRACE
DATA SHEET 23
INSTALLATION INSTRUCTIONS
AND USER MANUAL

Product description and intended use

Sensor types W-M-TRACE and 2xW-M-TRACE (resistance, RTD) are temperature sensors for trace heating applications, constructed with one or two mineral insulated sensors and a terminal box.
Sensors are intended for measuring trace heated pipe surfaces. The 2-sensor version can be used when a separate temperature measurement is wanted for limit/alarm purpose, leaving the other sensor clearly for control circuits.
The sensor elements can be designed long enough to give needed distance between heat source (pipe) and box/enclosure. Standard lengths are 1000 mm or 2000 mm. Sensor element protection tube material can be chosen, and element length can be produced according to customer needs.
Measuring elements are mineral insulated (MI) elements, which are bendable. Elements are RTD elements, standard versions are 4-wire Pt100 sensors. Tailored versions are produced on request.
NOTE!
Also available with ATEX approved, protection type Ex e components.
Please see section Ex data.
When used as part of an installation, subsequent approval of the entity is required.
EPIC® SENSORS temperature sensors are measuring devices intended for professional use. They should be
mounted by professionally capable installer who understands the installations surroundings. The worker should understand mechanical and electrical needs and safety instructions of the object installation. Suitable safety gear for each installation task must be used.

Temperatures, measuring

Allowed measuring temperature range for cable sensor tip is:

  • Standard (non-Ex), sensor type W-M-302 -200…+450, temporarily +550 °C
  • Ex e, cable sensor type WT-MI-302-…-EX -60…+550 °C

Temperatures, ambient

Allowed ambient temperatures for Ex cable sensors; please see section Temperatures, Ex e components.
Allowed ambient temperature range for enclosure is:

  • Standard box -40…+80 °C
  • Ex enclosures please see Ta classes in section Technical data.

Allowed ambient temperature range for terminal connectors is:

  • Standard -55…+85 °C

Temperatures, Ex e components

NOTE! W-M-TRACE assembly can be equipped with Ex e approved components.
When used as part of an installation, subsequent approval of the entity is required.
Sensors:
If Ex e version cable sensors are used, the sensor types are: WT-MI-302-….-.
Allowed measuring temperature range for sensor tip is: -60…+550 °C.
With these Ex e cable sensor types, specific conditions apply according to the ATEX certificates.
For type WT-MI-302-6-…-EX, certificates EESF 18 ATEX 049 Issue 1 and EESF 18 ATEX 051 Issue 1:
The temperature classification of the sensor (550 °C, T1 – T6) is determined by tre ambient temperature of the installation place.
Maximum ambient temperature is 550 °C for the sensor head and 125 °C for the connection terminals of the sensor cable.
Enclosures:

  • for Ex e enclosure please see Technical data for Ta classes.
  • for terminal connectors -55…+85 °C

Please see also section Ex data.

Code key

LAPP AUTOMAATIO W-M-TRACE Trace Heating Sensor - Code
key

Technical data

Materials| AISI 316L, maximum temperature +450 °C, temporarily +550 °C, other materials on request
---|---
Tolerances Pt100 (IEC 60751)| A tolerance ±0.15 + 0.002 x t, operating temperature -100…+450 ‘C
B tolerance ±0.3 + 0.005 x t, operating temperature -196…+600 °C
B 1/3 DIN, tolerance ±1/3 x (0.3 + 0.005 x t), operating temperature -196…+600 °C
B 1/10 DIN, tolerance ±1/10 x (0.3 + 0.005 x t), operating temperature -196…+600 -C
Temperature range Pt100| -60…+450 °C, temporarily +550 °C
Sensing element classification| II 2 GD Ex e T1-T6
Ex tD A21 IP66 T 60 °C T amb (max.) -40…+125/550 ‘C
Length| 1000 or 2000 mm as standard delivery, other lengths on request
Diameter| 3 or 6 mm, other diameters on request
Enclosure dimensions| 160x160x90 mm (WxHxD)
Enclosure material| Glass-reinforced polyester as standard delivery, other materials on request
Enclosure classification| II 2 GD Ex e IIC T6 Gb (Ta = -65…+40°C, +55°C, +60°C or +65°C) Ex e IIC T4 Gb (Ta = -65°C…+90°C)
Ex lb IIC T6 Gb (Ta = -65°C…+40°C, +55°C, +60°C or +65°C) Ex lb IIC T4 Gb (Ta = -65°C…+90°C)
Ex tb IIIC T85°C Db (Ta = -65°C…+40°C, +55°C, +60°C or +65°C) Ex tb IIIC T100°C Db (Ta = -65°C…+90°C)
Box temperature range| -40…+80 °C
Cable glands| Product with 2 sensing elements: 1 x cable gland, M25x1.5, for cable diameters 6-13 mm
Product with 1 sensing element: 2 x cable gland, M25x1.5, for cable diameter 6-13 mm
Approvals| Available with Ex e approved components, subsequent approval of the entity is required.
Quality certificate| ISO 9001:2015 and ISO 14001:2015 issued by DNV
IP rating| IP66 or IP67, other IP rating on request

Materials

These are the standard materials of components for the sensor types W-M-TRACE, 2xW-M-TRACE.

• Sensor element / MI cable sheet AISI 316L
• Enclosure Glass-Reinforced Polyester GRP
• Cable glands Polyamide with CR/Special Elastomer seal
• Contact terminals Polyamide PA66

Other materials can be used on request.

Dimensional drawing

LAPP AUTOMAATIO W-M-TRACE Trace Heating Sensor - Dimensional
drawing

This example drawing above is presenting an application with Ex e approved components. For details about Ex applications, please see section Ex data.

Installation instructions and example

Before any installation, make sure the target process/machinery and site are safe to work!
Installation phases:

  • Install the box/enclosure on wall, considering the length of sensors.
  • During installation, remember the MI element minimum bending radius is 2x ØOD of the element.
  • Do not bend the tip (30 mm) of RTD sensing elements, it might destroy the resistor inside.
  • Bend the sensor elements to align them with the pipe surface.
  • Mount the sensor securely on pipe with pipe clamps or cable ties or similar accessories.
  • Mount the pipe isolation if needed.
  • Make sure there is no excess bending force loading the sensing element.

Image below: this example shows a sensor installed on trace heated process pipe.

LAPP AUTOMAATIO W-M-TRACE Trace Heating Sensor - Dimensional
drawing1

Installation of accessories

Pipe fittings = pipe clamps:
There are stainless steel (1.4401) pipe clamp (hose clamp) components available as accessories.
Installation phases:

  • Select a suitable clamp size according to the pipe diameter.
  • Or select a separate, 1 m long strap part, and cut it in pieces of suitable lengths. Separate clamp parts for the strap can be ordered according to the need. Insert a clamp part to one end of the band.
  • Apply the strap around the pipe, leaving the sensor element under the strap.
  • Tighten the strap by twisting the screw clockwise, to give a secure thermal connection between sensor and pipe surface.

The components available are:

Product number Type Strap length/width Material
915589 Pipe clamp 16-27/12MM 1.4401
1125786 Pipe clamp 25-40/12MM 1.4401
1125787 Pipe clamp 32-50/9MM 1.4401
1026077 Pipe clamp 50-70/12MM 1.4401
1228601 Pipe clamp 70-90/12MM 1.4401
5120444 Pipe clamp 90-110/12MM 1.4401
5120446 Pipe clamp 110-130/12MM 1.4401
5120448 Pipe clamp 130-150/12MM 1.4401
920556 Pipe strap 1METER/12MM 1.4401
920559 Pipe strap clamp    12MM 1.4401

Tightening torques

Use only tightening torques allowed in applicable standards of each thread size and material.

Pt100; connection terminals
In the terminal box / enclosure free wire ends of sensors are available, but they are not connected to terminals, to give the customer freedom of choosing terminals.

Pt100; connection

LAPP AUTOMAATIO W-M-TRACE Trace Heating Sensor -
terminals

Wires are not connected, connected can be realized according to customer specification

Pt100; connection wiring

Image below: These are the connection colors of Pt100 resistor connections, according to standard EN 60751

LAPP AUTOMAATIO W-M-TRACE Trace Heating Sensor - connection
wiring

Other connections on request.

Pt100; measuring current
The highest allowed measuring current for Pt100 measuring resistors depends on resistor type and brand.
Normally the recommended maximum values are:

• Pt100 1 mA
• Pt500 0,5 mA
• Pt1000 0,3 mA.

Do not use higher measuring current. It will lead to false measurement values and might even destroy the resistor.

Type label of standard versions

Each sensor has a type label attached to. It is a moisture and wear proof industrial grade sticker, with black text on white label. This label has printed information of trade name, web page, type code, CE-mark, product number and serial number, including production date. For these sensors manufacturer contact information is printed on a separate label.

Image below: Example of a non-Ex sensor type label.

LAPP AUTOMAATIO W-M-TRACE Trace Heating Sensor - standard
versions

Serial number information

Serial number S/N is always printed on type label in the following form: yymmdd-xxxxxxx-x:

▪ yymmdd production date, e.g. “210131” = 31.1.2021
▪ -xxxxxxx production order, e.g. “1234567”
▪ -x sequential ID number within this production order, e.g. “1”

Ex e data (only for cable sensor components with Ex e approval)
If the trace heating sensor assembly W-M-TRACE is constructed with Ex e components, the cable sensor types are WT-MI-302-…-EX.
These Ex e cable sensor types are available with ATEX and EAC Ex approvals. The approved types are special versions, with type designation ending with -EX. Special data for use in Ex e applications is given in certificates.
Ex certificates and Ex markings of cable sensor components

Type
Certificate number| Issued by| Applicable area| Marking
---|---|---|---
WT-MI-302-6-…-EX
ATEX
EESF 18 ATEX 049X,
EESF 18 ATEX 051X| Eurofins Expert Services
Oy, Finland, Notified BodyNr 0537| Europe| Ex II 2GD Ex e II T1-T6
Ex tD A21 IP66 T+60°C
Tamb: -40…+125°C/+550°C
EAC Ex
№ ЕАЭС RU CFI.AA71.B.00130-19| Lenpromexpertiza OOO,
Russia| Eurasian Customs
Union (Belarus,
Kazakhstan, Russia)| 1 Ex e IIC T6…T1 Gb X
Ex tb IIIC T60°C Db X

For certificate copies and special Ex e product data, please visit:
https://www.epicsensors.com/en/products/temperature-sensors/exe-extb- temperature-sensors/
NOTE! When used as part of an installation, subsequent approval of the entity is required.

Ex e type label of cable sensor components

NOTE!
These Ex e type labels are attached on and they only apply for cable sensor elements, which are used as components.

For ATEX Ex e -approved WT-MI-302-…-EX cable sensor Ex e versions there is more information on the label, according to applicable standards.
Image below: Example of an ATEX Ex e approved cable sensor type label.

LAPP AUTOMAATIO W-M-TRACE Trace Heating Sensor - standard
versions1

For EAC Ex e approved WT-MI-302-…-EX cable sensor versions, exported to Eurasian Customs Union area, there is a special type label.
Image below: Example of an EAC Ex-approved cable sensor type label.

LAPP AUTOMAATIO W-M-TRACE Trace Heating Sensor - standard
versions2

EU Declaration of Conformity

The EU Declaration of Conformity, declaring products‘ conformance to the European Directives, is delivered with products or sent on request.

Manufacturer contact information

Manufacturer HQ main office:

Street address
Postal address| Lapp Automaatio Oy
Martinkyläntie 52
FI-01720 Vantaa, Finland
---|---

Production site and logistics:

Street address
Postal address
Phone (sales)
Email
Https| Lapp Automaatio Oy
Varastokatu 10
FI-05800 Hyvinkää, Finland
+358 20 764 6410
[email protected]
www.epicsensors.com
---|---

Document history

Version / date Author(s) Description
20220822 LAPP/JuPi Telephone number update
20220401 LAPP/JuPi Original version

Although every reasonable effort is made to ensure the accuracy of the content of the operating instructions, Lapp Automaatio Oy is not responsible for the way the publications are used or for possible misinterpretations by end users. The user must ensure that she or he has the latest edition of this publication.
We reserve the right to make changes without prior notice. © Lapp Automaatio Oy

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

LAPP AUTOMAATIO User Manuals

Related Manuals