CYBER SCIENCES CyTime Sequence of Events Recorder SER-32e Digital Input Module User Guide
- October 30, 2023
- CYBER SCIENCES
Table of Contents
IB-eXM-01
May-2023
INSTRUCTION BULLETIN
USER’S GUIDE
CyTime™ Sequence of Events Recorder
SER-32e Digital Input Module
(eXM-DI-08)
CyTime Sequence of Events Recorder SER-32e Digital Input Module
SAFETY PRECAUTIONS
Important safety precautions must be followed before attempting to install,
service, or maintain electrical equipment.
Carefully read and follow the safety precautions outlined below.
NOTE: Electrical equipment should be serviced by qualified personnel. No
responsibility is assumed by Cyber Sciences, Inc. for any consequences arising
out of the use of this material. This document is not intended as an
instruction manual for untrained persons.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
-
Only qualified workers should install this equipment. Such work should be performed only after reading this entire set of instructions.
-
NEVER work alone.
-
Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources of electric power. Assume that all circuits are live until they have been completely de-energized, tested, and tagged. Pay particular attention to the design of the power system.
Consider all sources of power, including the possibility of back feeding. -
Apply appropriate personal protective equipment (PPE) and follow safe electrical practices.
For example, in the USA, see NFPA 70E. -
Turn off all power supplying the equipment in which the device is to be installed before installing and wiring the device.
-
Always use a properly rated voltage sensing device to confirm that power is off.
-
Beware of potential hazards, wear personal protective equipment, and carefully inspect the work area for tools and objects that may have been left inside the equipment.
-
The successful operation of this equipment depends upon proper handling, installation, and operation. Neglecting fundamental installation requirements may lead to personal injury as well as damage to electrical equipment or other property.
Failure to follow these instructions can result in death or serious injury.
NOTICE
FCC (Federal Communications Commission)
This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense. The user
is cautioned that any changes or modifications not expressly approved by Cyber
Sciences, Inc. may void the user’s authority to operate the equipment.
The Class A digital apparatus complies with CISPR 11, Class A, Group 1 (EN
55011) and Canadian ICES-003. (EN 61326-1) L’appareil numérique de classe A
est conforme aux normes CISPR 11, classe A, groupe 1 (EN 55011) et à la norme
Canadiene ICES-003. (EN 61326-1)
INTRODUCTION
Sequence of Events Recorder Overview (SER-32e):
The CyTime TM Sequence of Events Recorder provides precise time-stamped event
reporting for 32 channels to enable root-cause analysis and advanced system
diagnostics.
Configurable event recording: Each input is individually configurable
with digital filter, debounce and contact chatter functions to ensure reliable
operation.
Event log: The CyTime SER records the date and time associated with all state
changes to one (1) millisecond and stores up to 8192 events in non-volatile
memory. Each event record contains the date/time stamp, event type, channel
number and state, time quality, and unique sequence number.
Export events to Comma Separated Variable (CSV): An export button allows
the user to save event data to a CSV fi le for further analysis in Excel® or
other software. EPSS data log groups: Inputs can be assigned to a group for
data logging purposes. If any input in a group changes state, then the states
of all group members are recorded in its EPSS data log. This enables
specialized reporting for mandatory tests of emergency power supply systems
(EPSS) to document compliance with standards for healthcare and other
critical-power facilities.
Operations counters: Operations counters are maintained for all 32
channels (inputs), with date/time of last reset. Each channel can be reset
individually. Ethernet communications: Network data communications to a host
system are supported via 10/100BaseTx Ethernet using Modbus TCP and/or
RESTful web service. The device also features an embedded secure web server to
simplify setup, operation, fi rewire updates and fi le transfers. In
addition, PTP (Precision Time Protocol (IEEE 1588) or NTP(Network Time
Protocol) can be used for time synchronization over Ethernet.
Product Overview (SER-32e)
Note: The Cyber Sciences Digital Input Module is an optional addition to
the CyTime TM SER-32e Sequence of Events Recorder. For more information on the
SER-32e Sequence of Events Recorder, visit www.cyber-sciences.com/our-support
/tech-library SER-32e
User’s Guide SER-32e Reference Guide
Time synchronization (PTP). High-resolution time sync (100 µs) is
supported using PTP (Precision Time Protocol, per IEEE 1588) over the Ethernet
network used for data communications. (Timestamps ± 0.5 Ms) The SER-32e can be
configured as the PTP
master (grandmaster clock for all other SERs and PTP-compatible devices) or a
PTP slave, synchronized to a PTP grandmaster (another SER or third-party
clock).
Time synchronization (other protocols). Hi-res time sync (100 µs) using
‘legacy’ protocols such as IRIG-B (unmodulated) or DCF77 is also supported.
(Timestamps ± 0.5 Ms) NTP or Modbus TCP time-sync are supported, but accuracy
depends on network design and is typically ± 100 ms or more.
Time-sync master. One SER can serve as a time-sync master to other
devices via PTP or an RS-485 subnet. RS-485 serial protocol is either IRIG-B
or DCF77 (per the input time source) or ASCII (selectable). When PTP or NTP is
the time source, an SER can output IRIG-B, DCF77 or 1per10 using an optional
interface (PLX-5V or PLX-24V).
Trigger output. Any input can be configured to close a high-speed output
contact to trigger an associated action, such as a power meter’s capture of
voltage and current waveforms coincident with an event. The trigger occurs in
the same millisecond interval
during which the event is detected, with no filtering applied.
Multiple Modbus masters. The SER supports data access from multiple
Modbus TCP masters (up to 44 simultaneous Modbus connections). This enables
integration of multiple systems and fl edibility in how application software
manages sockets.
Settings stored in non-volatile memory. All settings are stored in non-
volatile fl ash memory in XML fi le format. Configuration is accomplished
using a standard web browser, or by modifying the setup fi le directly (by
advanced users).
Benefits for end users, system integrators and OEMs include:
Time-critical information for root-cause analysis (1 ms)
Time-stamped record of events—up to 8192 events stored in non-volatile memory.
Reliable event recording with “zero blind-time”
Event-recording engine records all events, even those occurring in rapid
succession.
Advanced troubleshooting
High-speed trigger output to capture waveforms by a compatible power meter.
Simple setup using a web browser—no proprietary software
Embedded web server hosts user-friendly pages for setup and monitoring.
No maintenance required
Event data and user setup data is stored in non-volatile fl ash memory.
Easy system integration
Integrate with multiple systems via Ethernet: Modbus TCP, RESTful API and
secure web interface.
Flexible time synchronization choices
PTP, IRIG-B, DCF77, NTP, Modbus TCP or SER inter-device (RS-485).
EPSS generator test-compliance reports enabled
16 data logs: when any group member changes state, all members’ states are
recorded.
Easy replacement
If a unit ever needs to be replaced, settings are transferable via XML setup
fi le.
Regulatory approvals to global standards
UL-Listed (UL/IEC 61010), CSA 22.2, CE, RoHS-compliant.
Product Overview SER-32e (cont.)
Status monitoring examples:
- Breaker status: open/closed/tripped
- Breaker control switch: open/close commands
- Relay trip signal: normal/trip
- Auto-transfer switch (ATS) status: normal/emergency/test
- Control scheme status: auto/manual/test
- UPS status: normal/bypass
- Generator status: stopped/running
- Battery status: normal/alarm
Benefits SER-32e
Key Features SER-32e
The CyTime SER-32e Event Recorder is designed to be mounted on a standard
DIN rail. The table below gives a description of each key feature.
Table 1-1—Key Features
Feature | Description |
---|---|
1 | Embedded Secure Web Server |
diagnostics, and view event log records. Use web browser for firmware updates,
manage security certificates, and upload/download configuration files.
2| High-Speed I/O| 32 digital inputs in four (4) groups of eight (8) inputs.
3| High-Speed Trigger Output| Digital output contact which can be configured
to close momentarily on state change of one or more inputs to trigger an
action, such as a waveform capture (WFC) by a compatible power meter.
4| Time Sync IN/OUT (RS-485)| Time sync OUT (when serving as a time-sync
master to other devices) or time sync IN (when synchronized to another SER
time-sync master) over RS-485 (2-wire plus shield). ASCII / RS-485 output is
selectable.
5| Color Touchscreen| Color resistive touchscreen display (4.3″ TFT, 480 x 272
pixels) for local access to status, events and setup parameters. User
configurable brightness and screen saver.
6| EZC-IRIG-B/DCF77 (IN) or PLX-5V/PLX-24V (OUT)| DB-15-to-screw-terminal
connector: EZ Connector (EZC) to accept IRIG-B or DCF77 time source (IN), or
PLX (PLX-5V or PLX-24V) to output IRIG-B, DCF77 or 1per10 (OUT).
7| Ethernet Interface (10/100BaseTx)| Two Standard Ethernet RJ-45 network
interface, with indicator LEDs for speed (10 or 100 Mbps) and link/ activity.
The SER auto-detects Ethernet wiring polarity and network speed.
8| Expansion Slots| Two expansion slots available for Digital Input and
Digital Relay expansion modules.
9| Power Control Module| Provides over 10 seconds of control power ride-
through to ensure power system events are recorded. Includes replaceable
battery for RTC (Real Time Clock) backup.
Introduction Digital Input Module
The Digital Input Module is an optional accessory for the CyTime™ SER-32e
Sequence of Events Recorder. Each input module provides eight (8) high-speed
digital inputs with millisecond time stamping.
The CyTime™ SER-32e Sequence of Events Recorder provides two (2) option
slots allowing its native 32 high-speed inputs to be expanded to a maximum
of 48 inputs, all with millisecond time stamping to enable root-cause
analysis and advanced system diagnostics.
Configurable event recording: Each input on the SER and its option
modules is individually configurable with digital filter, debounce and contact
chatter functions to ensure reliable operation through the SER’s web
interface.
Event log: The SER records the date and time associated with all state
changes to one (1) millisecond and stores up to 8192 events in non-volatile
memory. Each event record contains the date/time stamp, event type, channel
number and state, time quality, a unique sequence number and delta time
between recorded events.
EPSS data log groups: Inputs and outputs can be assigned to user defined
groups for data logging purposes. If any input or output in a group changes
state, the states of all group members are recorded in its EPSS (Group) data
log. This enables specialized reporting for mandatory tests of emergency
power supply systems (EPSS) to document compliance with standards for
healthcare and other critical-power facilities.
Operations counters: Operations counters are maintained for all input and
output channels, with date/time of last reset. Each channel can be reset
individually.
Key features: The Digital Input Module provides the ability to expand the
native 32 high-speed inputs of the SER-32e to 40 or 48 inputs without the need
for additional space or control power.
Digital Input Module Overview
The Digital Input Module provides 8 high-speed inputs, input status indicators, and an indicator for the presence of control power and module status. Control power for the input module is provided by the SER-32e. Inputs on the Digital Input Module provide the same high-speed performance and features as the inputs native to the SER.
Table 1-2—Ordering Information
Catalog Number | Description |
---|---|
SER-32e | CyTime Event Recorder, 32-input, PTP, secure web, 2x option slots, |
control power ride-thru
eXM-DI-08| 8-input option module, 24 VDC, pluggable screw terminal connector
eXM-RO-08| 8-output option module, 24 VDC, pluggable screw terminal connector
EZC-IRIG-B| EZ connector for SER (input: IRIG-B time source)
EZC-DCF77| EZ connector for SER (input: DCF77 time source)
PLXe-5V| PTP Legacy Interface, Self-Powered (5V DCLS, for unmodulated IRIG-B
output)
PLX-5V| PTP Legacy Interface (5V DCLS, for unmodulated IRIG-B output)
PLX-24V| PTP Legacy Interface (DCF77, 1per10 or 24V IRIG-B output to STR-IDM)
INSTALLATION
Dimensions
The dimensions for the Digital Input Module are illustrated below.
Mounting / Installation
Mounting Considerations
The Digital Input Module is designed to be mounted in one (1) of the two (2)
option slots in the SER-32e. Connections are made to the front of the module
using pluggable connectors.
Installing the Digital Input Module
The Digital Input Module is installed by inserting it into either of the two
(2) option slots on the SER-32e (slot 1 or slot 2). (see figure 1-3)
Installation Procedure
-
Refer to Safety Precautions on page iv for electrical safety guidance, proper PPE and procedures.
-
Remove control power from the SER.
-
Monitor the LED indicators on the Power Control module until they are all OFF.
-
Remove the blank cover from the desired option module slot by pressing the two latches on the top and bottom of the cover and pull out.
We recommend retaining the cover for future use. -
Align the module in the guide rails with the connector on the right side of the module.
-
Insert the module into the option slot by pressing it into the SER until the latches “click” into place.
-
Reapply control power to the SER.
-
Confirm the SER recognizes the option module by viewing the Monitoring Status screen on either the SER display or web page.
WIRING
The Digital Input Module has 8 isolated digital inputs, each sharing a common
return, wired as shown. Control power for the module is provided by the SER
the module is mounted in. Recommended wiring for digital inputs is Belden 8760
(18 AWG, shielded, twisted pair) cable, or equivalent.
Input connections are made via a removable screw terminal plug equipped with
locking screws for mounting. It is recommended the locking screws be secured
to ensure retention of the plug-in connector.
Refer to Safety Precautions on page iv for electrical safety guidance, proper
PPE and procedures before wiring the input module.
Wiring Connections for eXM-DI-08
OPERATION
The inputs on the SER-32e Digital Input Module are reported based on the
option slot in which they are installed. See table below.
Table 4-1—Input Channels
Module(s) Installed | Channels |
---|---|
Slot #1 | Slot#2 |
Yes | No |
No | Yes |
Yes | Yes |
The Digital Input Module status can be viewed on the SER’s touchscreen display
and web interface on the Monitoring > Status screen(s).
The additional 8 (up to 16) inputs on the Digital Input Module are shown at
the bottom of the display screen. The additional inputs (up to 16) are shown
on the right side of the Monitoring Status web page.
Dimensions
Note: If an input module is installed in option slot #2, but not option
slot #1, channels 33 – 40 will reported as disabled.
Note: Refer to SER-32e User’s Guide (IB-SER32e-01) and SER-32e Reference
Guide (IB-SER32e-02) for additional information on SER-32e display screen and
SER-32e web client.
SETUP (WEB SERVER)
Input(s) Setup
Clicking “Inputs” under the Setup tab brings up the Input’s setup page:
Table 5-1— Initial configuration settings
Option | Description | Available values | Default |
---|---|---|---|
Input | Each input can be enabled for event recording. This does not affect | ||
status monitoring—only recording of state changes. | Enabled or Disabled |
Enabled
Input Name| Text string (UTF-8) to describe a given input.| 32 characters max
0| Input nn
Filter| Filter time is the minimum time that an input must remain in its new
state before it is recorded as an event. This helps eliminate false events due
to noise, transients, etc.| 0 to 65535 ms 0| 20ms
Debounce| Debounce time is the period that event processing is suspended for a
given input after an event has been recorded. This prevents recording multiple
events for a single state change.| 0 to 65535 ms 0| 20ms
Chatter| Chatter count is the maximum number of events recorded for a given
input per minute. If the number of events per minute exceeds the setpoint, the
input will be disabled for further event processing until the number of events
per minute drops below the setpoint. This prevents recording an excessive
number of events due to a faulty input. Events are also generated to indicate
the time event processing was suspended / resumed.| 0 to 255 (0 = Disabled)| 0
(disabled)
Off Text and On Text| Customized label to describe an input’s “off” state and
“on” state| UTF-8, 16-char. 0| On / Off
High-speed Trigger Output| Any input can be configured to close the “Trigger
Out” contact on status change. This is typically used to trigger a compatible
power meter to capture current and voltage waveforms coincident with an event
to aid analysis and troubleshooting.| Enabled or Disabled| Disabled
Inverted| Any input can be designated as “inverted” and status reported
opposite of its sensed state| Normal or Inverted| Normal
Group Assignment (for Data Logs)| Each input can be assigned to a data log
group for reporting purposes| None, or Group 01 to Group 16| None
- Only the following special characters are available: ! @ # $ & * ( ) _ – + = { } [ ] ; . ~ ` ’
- Setting this time too low (e.g., < 5 ms) can cause unwanted events to be recorded; setting too high (e.g., > 100 ms) can result in missed events.
PRODUCT SPECIFICATIONS
Electrical
Digital inputs | Number of inputs | 8 |
---|---|---|
Voltage, operating | 24 Vdc (-15% to +10%), Class 2 / LPS | |
Input impedance / current draw (max.) | 10K ohms resistive / 1 mA | |
Must turn ON/OFF voltage | Turn on: 20 Vdc / Turn off: 9 Vdc | |
Turn ON time / turn OFF time (max.) | 0.5 ms | |
Isolation | Each input is isolated to 2.5 KV |
Mechanical
Mounting | Option slot on SER-32e Sequence of Events Recorder |
---|---|
Wire sizes supported | #24 to #12 AWG |
Dimensions (W x H x D) | 1.26” x 3.65” x 1.71” (32mm x 92.7mm x 43.5mm) |
Dimensions (W x H x D) in packaging | 8.0” x 3.0” x 8.0” (203.2mm x 76.2mm x |
203.2mm)
Weight (product alone / product packaged)| 0.375 lbs. (0.17kg) / 0.75 lbs.
(0.34kg)
Environmental
Operating Temperature | -25 to +70°C |
---|---|
Storage Temperature | -40 to +85ºC |
Humidity Rating | 5% to 95% relative humidity (non-condensing) at +40ºC |
Altitude Rating | 0 to 3000 meters (10,000 feet) |
Sustainability / Compliance | RoHS 2 (2011/65/EU), RoHS 3 (2015/863/EU), Pb |
free California Proposition 65, Low Halogen, Conflict Minerals
Regulatory
Safety, USA | UL listed (NRAQ-cULus, UL 61010-1, UL 61010-2-201 |
---|---|
Safety, Canada | CAN/CSA-C22.2 (61010-1-12, 61010-2-201) |
Safety, Europe | CE Mark (EN 61010-1 : 2010, EN 61010-2-201 : 2017) |
Emissions / Immunity | EN 61326-1 (IEC 61326-1 : 2012) |
Radiated emissions | CISPR 11, Class A, Group 1 (EN 55011) / FCC Part 15B, |
Class A
Electrostatic discharge| EN 61000-4-2
Radiated immunity| EN 61000-4-3
Electrical fast transient / burst immunity| EN 61000-4-4
Surge immunity| EN 61000-4-5
Conducted radio frequency immunity| EN 61000-4-6
TROUBLESHOOTING
Symptom | Possible Cause | Suggested Action(s) |
---|
Module status LED
not ON| Connection issue with SER| Remove power from SER. Remove Input module.
Examine the edge connector for damage. Re-insert Input module.
Input(s) not functioning| Wetting voltage or common connection issue or
missing.
Input connector dislodged.| Confirm wetting voltage (24 Vdc) and common
connections.
Ensure Input connector is secured.
Input status for
Inputs 33-40 is reporting as disabled| No Input module installed in option
slot #1| There is no issue using option slot #2 and not using option slot #1.
For
sequential input numbering, move the Input module to option slot #1.
NOTE: you will need to reconfigure the input module when moving it from option
slot #2 to slot #1.
Cyber Sciences, Inc. (CSI)
229 Castlewood Drive, Suite E
Murfreesboro, TN 37129 USA
Tel: +1 615-890-6709
Fax: +1 615-439-1651 Doc. no: IB-eXM-01
May -2023
The service marks, “Precision Timing for Reliable Power.
Simplified.”, CyTime, and the Cyber Sciences stylized logo are trademarks
of Cyber Sciences.
All other trademarks are the property of their respective owners.
© 2023 Cyber Sciences, Inc. All rights reserved.
www.cyber-sciences.com
© 2023 Cyber Sciences, Inc. All rights reserved.
www.cyber-sciences.com
Documents / Resources
|
CYBER SCIENCES CyTime Sequence of Events Recorder SER-32e Digital Input
Module
[pdf] User Guide
CyTime Sequence of Events Recorder SER-32e Digital Input Module, CyTime
Sequence of Events Recorder, SER-32e Digital Input Module, SER-32e, Module,
SER-32e Module, Digital Input Module
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>