CYBER SCIENCES SER-32e PTP CyTime Sequence of Events Recorder Instruction Manual

October 30, 2023
CYBER SCIENCES

CYBER SCIENCES Logo SER-32e PTP CyTime Sequence of Events Recorder
Instruction ManualCYBER SCIENCES SER 32e PTP CyTime Sequence of Events
Recorder

SER-32e PTP CyTime Sequence of Events Recorder

The Cyber Sciences Precision Timing Protocol (PTP) Legacy Interface (PLXe-5V) is a wiring adapter for the CyTime™ Sequence of Events Recorder to output a legacy time protocol to other devices. The adapter fits the “Options” port (DB15 connector) of the SER-32e and facilitates wiring of 5V signals via a screw-type terminal, suitable for power equipment wiring.
The PLXe-5V includes diagnostics LEDs to aid system commissioning and troubleshooting. A link indicator LED flashes (flickers) according to the frequency of the time protocol output (IRIG-B: 100 Hz, DCF77: 1PPS, 1per10: one pulse per 10 seconds). A second LED indicates the presence of control power input from the SER.

SAFETY PRECAUTIONS

Note: The output protocol (IRIG-B, DCF77 or 1per10) depends on the time- sync output setting configured for the CyTime SER-32e Event Recorder.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Only qualified workers should install this equipment. Such work should be performed only after reading this entire set of instructions.
  • NEVER work alone.
  • Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources of electric power. Assume that all circuits are live until they have been completely de-energized, tested, and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of back feeding.
  • Apply appropriate personal protective equipment (PPE) and follow safe electrical practices. For example, in the USA, see NFPA 70E.
  • Turn off all power supplying the equipment in which the device is to be installed before installing and wiring.
  • Always use a properly rated voltage sensing device to confirm that power is off.
  • Beware of potential hazards, wear personal protective equipment, and carefully inspect the work area for tools and objects that may have been left inside the equipment.
  • The successful operation of this equipment depends upon proper handling, installation, and operation. Neglecting fundamental installation requirements may lead to personal injury as well as damage to electrical equipment or other property.

Failure to follow these instructions can result in death or serious injury.

WIRING

The PLXe-5V is provided with control power from the SER-32e and is not compatible with other CyTime® Sequence of Event Recorders (SER-3200 or SER-2408).

CYBER SCIENCES SER 32e PTP CyTime Sequence of Events Recorder -
WIRING

TECHNICAL SPECIFICATIONS

For More Information
CyTime SER-32e User’s Guide (IB-SER-32e-01)
CyTime SER-32e Reference Guide (IB-SER-32e-02)
Tech Note: SER System Architectures (TN-101)
SPECIFICATIONS

Diagnostics LEDs| Link—Flashing for IRIG-B, DCF77 or 1per10 output
Power—Indicates control power
---|---
Output drive| 5V, 10-ohm, +/- 75 mA drive
Isolation| 1000 Vdc min.
Environmental| Operating temperature: -30°C to +80°C ambient
Storage temperature: -40°C to +85°C
Humidity: 5-95% (non-condensing) at 40°C
Mounting| Connects to SER Options Connector (DB-15)
Dimensions (W x H x D)| 2.92 x 1.72 x 0.84 in. (74 x 44 x 21 mm)
Weight| 1.0 oz. (28 g)

Cyber Sciences, Inc. (CSI)
229 Castlewood Drive, Suite E
Murfreesboro, TN 37129 USA
Tel: +1 615-890-6709
Fax: +1 615-439-1651CYBER SCIENCES Logo Precision Timing for Reliable Power. Enabled. SM
Doc. no: IB-PLXe-01 Apr-2023
The service marks, CyTime, and the Cyber Sciences stylized logo are trademarks of Cyber Sciences. All other trademarks are the property of their respective owners.
© 2011-2023 Cyber Sciences, Inc. All rights reserved.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CYBER SCIENCES User Manuals

Related Manuals