Honeywell LS1000R LightSpot 360 Degree Dual Mount PIR Instruction Manual
- October 30, 2023
- Honeywell
Table of Contents
LS100 0R Lig htSpot 360° Dual Mount PIR
installation and operating instructions
LS1000R LightSpot 360 Degree Dual Mount PIR
Only suitably qualified personnel should install this equipment
- To prevent electrocution, do not work on any appliance live. Turn off mains before commencing work, lock-out tag-out must be followed.
- The current editions of the IEE Wiring Regulations (BS7671) and Buildings Regulations must be followed for installation.
- Ensure all terminal screws are fully tightened and product is securely fixed to its mounting box prior to turning on the mains supply.
PACK CONTENTS
REQUIRED (Warning: Use only VDE Certified Tools)
MOUNTING/ INSTALLATION STEPS
Surface Mount
Flush Mount
REMOVING
MOTION SENSOR DETECTION
LENS MASK
TESTING & OPERATION
Adjustment
- Can be adjusted by flat head screwdriver.
WALK TESTING
MANUAL OVERRIDE OPERATION
SWITCHABLE LOAD
TECHNICAL SPECIFICATIONS
Detection Range:| Up to 6 metres diameter (3m Radius) at mounting height of
2.5m
---|---
Detection Angle:| 360°
Power Supply:| 230Vac 50Hz
Maximum Switchable Load:| Max load current 10A
Incandescent / Halogen Max 2000W
Fluorescent lamp (magnetic) Max 500W
Fluorescent lamp (electronic ballast) Max 400W
Low energy (CFL) Max 120W
LED lamp Max400W
Fan Max 75W
Time On Adjustment:| 5 seconds – 15 minutes
Dusk Level Adjustment:| Day & night or night only operation
Operating temperature:| 0 to 40 degrees
Environment Protection:| For ceiling mount – IP44
For flush mount
– IP44 (at sensor portion only)
– IP20 (ceiling board onwards)
GUARANTEE
The company undertake to replace or repair, at its discretion should it become
defective within a period of 1 year after delivery, solely as a result of
faulty materials and/or workmanship. Understandably, if the product has not
been installed, maintained or used appropriately, or if an attempt has been
made to rectify, dismantle or alter the product in any way, the guarantee will
be invalidated.This guarantee states the company’s entire liability. It does
not extend to cover consequential loss or damage or installation cost arising
from the defective product.This guarantee does not restrict or infringe the
normal statuary rights of the customer.
COMPLIANCE WITH E.U. DIRECTIVES
Apart from meeting the appropriate British standards, products are
manufactured in accordance with BS EN ISO 9002 and comply with the LV
(72/23/EEC) Directive.
**** At the end of their useful life the packaging and product should be
disposed of via a suitable recycling centre.
Do not dispose of with normal household waste. Do not burn.
W6039 REVD 12/2/2023
EU contact for regulatory questions:
PEHA Elektro GmbH & Co.
KG Gartenstraße 49,
58511 Lüdenscheid Germany
Web:www.peha.de
Honeywell
St Marks Court, North Street
Horsham, West Sussex RH12 1BW
Tel: +44 (0)1942 719229
Web:www.buildings.honeywell.com/gb/
en/brands/our-brands/ex-or
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>