Panasonic CS-LU9ZKA Air Conditioner Instruction Manual
- October 30, 2023
- Panasonic
Table of Contents
- Panasonic CS-LU9ZKA Air Conditioner
- Product Information: Air Conditioner Model No. CS-LU9ZKA/CS-LU12ZKA
- Product Usage Instructions
- Operating Instructions
- Accessories
- Safety Precautions
- 8 must be followed to remove the refrigerant.
- Cleaning the Air Conditioner
- Troubleshooting
- Information
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Panasonic CS-LU9ZKA Air Conditioner
Product Information: Air Conditioner Model No. CS-LU9ZKA/CS-LU12ZKA
The Panasonic Air Conditioner Model No. CS-LU9ZKA/CS-LU12ZKA is a split air conditioning system that includes an indoor unit (CS-LU9ZKA or CS-LU12ZKA) and an outdoor unit (CU-LU9ZKA or CU-LU12ZKA). It comes with a built-in Network Adaptor that allows the user to control the air conditioner unit operation from anywhere using a remote control. The unit has four operating modes: POWERFUL, ECO, AUTO, and DRY. The air conditioner also has a SLEEP mode, ON TIMER, and an OFF function. The temperature can be adjusted using the TEMP UP and TEMP DOWN buttons, and the fan speed can be set to QUIET mode. The indoor unit has an air inlet and outlet, and the outdoor unit has an air outlet.
Product Usage Instructions
Before operating the air conditioner, please read the operating instructions thoroughly and keep them for future reference.
- Remove the remote control packed with the indoor unit and insert AAA or R03 batteries.
- To turn on/off the air conditioner, press the POWER button. To change the operating mode, press the MODE button and select POWERFUL, ECO, AUTO or DRY mode.
- Use the TEMP UP and TEMP DOWN buttons to set the desired temperature. The fan speed can be set to QUIET mode by pressing the FAN SPEED button.
- The SLEEP mode can be activated by pressing the SLEEP button. The ON TIMER function can be set by pressing the ON TIMER button, and the OFF function can be set by pressing the OFF button.
- The air swing function can be turned on/off by pressing the AIR SWING button.
- The remote control should be used within 8 meters from the remote control receiver on the indoor unit.
For safety precautions, please ensure that the air inlet and outlet of the indoor and outdoor units are not blocked. Please consult an authorized dealer or specialist for cleaning, repair, installation, removal, disassembly, and reinstallation of the unit. Improper installation and handling may cause leakage, electric shock, or fire. Also, confirm with authorized dealer or specialist on usage of any specified refrigerant type.
Operating Instructions
Air Conditioner
Model No. Indoor Unit CS-LU9ZKA CS-LU12ZKA
Outdoor Unit CU-LU9ZKA CU-LU12ZKA
2-19
:
Operating Instructions Air Conditioner
20-37
Before operating the unit, please read these operating instructions thoroughly and keep them for future reference.
Before installation, the installer should: Read the Installation Instructions, then request the customer keep them for future reference.
Remove the remote control packed with the indoor unit. If the equipment is transferred to a new user or delivered
to a recycling plant, be sure also to hand over the manual.
English
ACXF55-35690
A new built-in Network Adaptor that allows you to control your air conditioner unit operation from anywhere.
Use the remote control within 8 m from the remote control receiver on the indoor unit.
B
POWERFUL/ ECO
OFF/ON
MODE
SLEEP
ON TIMER
OFF
TEMP
FAN SPEED/ QUIET
AIR SWING
A
SET
CANCEL
20
AIR CONDITIONER
Quick Guide
Inserting the batteries A Clock setting
1
OPEN
2
3
1 Pull out the back cover of remote control.
2 Insert AAA or R03 batteries.
3 Close the cover.
1 Press , then press to set the time.
· Press for approximately 5 seconds to show the time as 12-hour (am/ pm) or
24-hour. 2 Press to confirm.
Thank you for purchasing Panasonic Air Conditioner.
Table of Contents
Safety Precautions ……..22-29 How to Use ……………….30-31 To Learn More… ……………..32
Cleaning the Air Conditioner ………………..33 Troubleshooting …………34-36 Information
…………………….37
Accessories
· Remote control · AAA or R03 batteries × 2 · Remote control holder · Screws
for remote control
holder × 2
The illustrations in this manual are for explanation purposes only and may
differ from the actual unit. They are subject to change without notice.
English
B Basic operation
1 Press
to start/
stop the operation.
2 Press
to select
the desired mode.
POWER
· When the unit is ON, disappears from the remote control display.
AUTO
COOL DRY
3 Press TEMP UP, TEMP DOWN to select the desired temperature.
Up
Down
Selection range: 16.0 °C ~ 30.0 °C / 60 °F ~ 86 °F. · Press for approximately
10 seconds to show the temperature as °C or °F.
21
Safety Precautions
To prevent personal injury, injury to others or property damage, please comply with the following: Incorrect operation due to failure to follow instructions below may cause harm or damage, the seriousness of which is classified as below: This appliances is not intended for accessibility by the general public.
WARNING
This sign warns of death or serious injury.
CAUTION
This sign warns of injury or damage to property.
The instructions to be followed are classified by the following symbols:
This symbol denotes an action that is PROHIBITED.
These symbols denote actions COMPULSORY.
Indoor unit
Power supply Air inlet
Air outlet
Remote control
Air inlet
Outdoor unit
Air outlet
WARNING
Indoor unit and outdoor unit
This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
Please consult an authorised dealer or specialist to clean the internal parts,
repair, install, remove, disassemble and reinstall the unit. Improper
installation and handling will cause leakage, electric shock or fire.
Confirm with authorised dealer or specialist on usage of any specified
refrigerant type. Using refrigerant type other than the specified may cause
product damage, burst and injury etc.
Do not use means to accelerate the defrosting process or to clean, other than
those recommended by manufacturer. Any unfit method or using incompatible
material may cause product damage, burst and serious injury.
Do not install the unit in a potentially explosive or flammable atmosphere.
Failure to do so could result in fire.
Do not insert your fingers or other objects into the air conditioner indoor or
outdoor unit, rotating parts may cause injury.
Do not touch the outdoor unit during lightning, it may cause electric shock.
Do not expose yourself directly to cold air for a long period to avoid excess
cooling.
Do not sit or step on the unit, you may fall down accidentally.
Remote control
Do not allow infants and small children to play with the remote control to
prevent them from accidentally swallowing the batteries.
22
Power supply
Do not use a modified cord, joint cord, extension cord or unspecified cord to prevent overheating and fire.
To prevent overheating, fire or electric shock: · Do not share the same power
outlet with other
equipment. · Do not operate with wet hands. · Do not over bend the power
supply cord. · Do not operate or stop the unit by inserting or
pulling out the power plug.
If the supply cord is damaged, it must be replaced by the manufacturer, service agent or similarly qualified persons in order to avoid a hazard.
It is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD) to prevent electric shock or fire.
To prevent overheating, fire or electric shock: · Insert the power plug
properly. · Dust on the power plug should be periodically
wiped with a dry cloth.
Stop using the product if any abnormality/ failure occurs and disconnect the
power plug or turn off the power switch and breaker. (Risk of
smoke/fire/electric shock) Examples of abnormality/failure · The ELCB trips
frequently. · Burning smell is observed. · Abnormal noise or vibration of the
unit is
observed. · Water leaks from the indoor unit. · Power cord or plug becomes
abnormally hot. · Fan speed cannot be controlled. · The unit stops running
immediately even if it
is switched on for operation. · The fan does not stop even if the operation
is stopped. Contact your local dealer immediately for maintenance/repair.
Replacement or installation of power plugs shall be performed by authorised/qualified personnel only. The wires in this mains lead are coloured in accordance with the following code:
Terminals Red Black
Green/Yellow
wires live
neutral
earth
colours (BS Standard) brown blue green-yellow
Wiring colour may vary depending on a country wiring code’s standard.
This equipment must be earthed to prevent electrical shock or fire.
Prevent electric shock by switching off the power supply and unplug: – Before cleaning or servicing, – When extended non-use, or – During abnormally strong lightning activity.
CAUTION
Indoor unit and outdoor unit
Do not wash the indoor unit with water, benzine, thinner or scouring powder to
avoid damage or corrosion at the unit. Do not use for preservation of precise
equipment, food, animals, plants, artwork or other objects. This may cause
quality deterioration, etc. Do not use any combustible equipment in front of
the airflow outlet to avoid fire propagation. Do not expose plants or pet
directly to airflow to avoid injury, etc.
Do not touch the sharp aluminium fin, sharp parts may cause injury.
Do not switch ON the indoor unit when waxing the floor. After waxing, aerate
the room properly before operating the unit. Do not install the unit in oily
and smoky areas to prevent damage to the unit. Do not dismantle the unit for
cleaning purpose to avoid injury. Do not step onto an unstable bench when
cleaning the unit to avoid injury. Do not place a vase or water container on
the unit. Water may enter the unit and degrade the insulation. This may cause
an electric shock. Do not open window or door for long time during operation,
it may lead to inefficient power usage and uncomfortable temperature changes.
Prevent water leakage by ensuring drainage pipe is: – Connected properly, –
Kept clear of gutters and containers, or – Not immersed in water After a long
period of use or use with any combustible equipment, aerate the room
regularly. After a long period of use, make sure the installation bolts and
nuts does not deteriorate to prevent the unit from falling down.
Remote control
Do not use rechargeable (Ni-Cd) batteries. It may damage the remote control.
To prevent malfunction or damage of the remote control: · Remove the batteries
if the unit is not going to
be used for a long period of time. · New batteries of the same type must be
inserted following the polarity stated.
Power supply
Do not disconnect the plug by pulling the cord to prevent electric shock.
nanoeTM-G generator
Do not touch the sharp pin which may cause injury.
23
English
Safety Precautions
Safety Precautions
WARNING
This appliance is filled with R32 (mildly flammable refrigerant). If the
refrigerant is leaked and exposed to an external ignition source, there is a
risk of fire.
Indoor unit and outdoor unit
The appliance shall be installed, and/or operated in a room with floor area
larger than Amin (m²) and keep away from ignition sources, such as
heat/sparks/open flame or hazardous areas such as gas appliances, gas cooking,
reticulated gas supply systems or electric cooking appliances, etc. (Refer to
Table A of Installation instructions table for Amin (m²))
Be aware that refrigerant may not contain an odour, highly recommended to
ensure suitable flammable refrigerant gas detectors are present, operating and
able to warn of a leak.
Keep any required ventilation openings clear of obstruction.
Do not pierce or burn as the appliance is pressurized. Do not expose the
appliance to heat, flame, sparks, or other sources of ignition. Else it may
explode and cause injury or death.
Precaution for using R32 refrigerant
The basic installation work procedures are the same as conventional
refrigerant (R410A, R22) models.
Since the working pressure is higher than that of refrigerant R22 models, some
of the piping and installation and service tools are special. Especially, when
replacing a refrigerant R22 model with a new refrigerant R32 model, always
replace the conventional piping and flare nuts with the R32 and R410A piping
and flare nuts on the outdoor unit side. For R32 and R410A, the same flare nut
on the outdoor unit side and pipe can be used.
The mixing of different refrigerants within a system is prohibited. Models
that use refrigerant R32 and R410A have a different charging port thread
diameter to prevent erroneous charging with refrigerant R22 and for safety.
Therefore, check beforehand. [The charging port thread diameter for R32 and
R410A is 1/2 inch.] 24
Must always ensure that foreign matter (oil, water, etc.) does not enter the
piping. Also, when storing the piping, securely seal the opening by pinching,
taping, etc. (Handling of R32 is similar to R410A.) · Operation, maintenance,
repairing and
refrigerant recovery should be carried out by trained and certified personnel
in the use of flammable refrigerants and as recommended by the manufacturer.
Any personnel conducting an operation, servicing or maintenance on a system or
associated parts of the equipment should be trained and certified. · Any part
of refrigerating circuit (evaporators, air coolers, AHU, condensers or liquid
receivers) or piping should not be located in the proximity of heat sources,
open flames, operating gas appliance or an operating electric heater. · The
user/owner or their authorised representative shall regularly check the
alarms, mechanical ventilation and detectors, at least once a year, where as
required by national regulations, to ensure their correct functioning. · A
logbook shall be maintained. The results of these checks shall be recorded in
the logbook. · In case of ventilations in occupied spaces shall be checked to
confirm no obstruction. · Before a new refrigerating system is put into
service, the person responsible for placing the system in operation should
ensure that trained and certified operating personnel are instructed on the
basis of the instruction manual about the construction, supervision, operation
and maintenance of the refrigerating system, as well as the safety measures to
be observed, and the properties and handling of the refrigerant used. · The
general requirement of trained and certified personnel are indicated as below:
a) Knowledge of legislation, regulations
and standards relating to flammable refrigerants; and, b) Detailed knowledge
of and skills in handling flammable refrigerants, personal protective
equipment, refrigerant leakage prevention, handling of cylinders, charging,
leak detection, recovery and disposal; and, c) Able to understand and to apply
in practice the requirements in the national legislation, regulations and
Standards; and, d) Continuously undergo regular and further training to
maintain this expertise. e) Air-conditioner piping in the occupied space shall
be installed in such a way to protect against accidental damage in operation
and service.
f) Precautions shall be taken to avoid excessive vibration or pulsation to
refrigerating piping.
g) Ensure protection devices, refrigerating piping and fittings are well
protected against adverse environmental effects (such as the danger of water
collecting and freezing in relief pipes or the accumulation of dirt and
debris).
h) Expansion and contraction of long runs piping in refrigerating systems
shall be designed and installed securely (mounted and guarded) to minimize the
likelihood hydraulic shock damaging the system.
i) Protect the refrigerating system from accidental rupture due to moving
furniture or reconstruction activities.
j) To ensure no leaking, field-made refrigerant joints indoors shall be
tightness tested. The test method shall have a sensitivity of 5 grams per year
of refrigerant or better under a pressure of at least 0.25 times the maximum
allowable pressure (>1.04 MPa, max 4.15 MPa). No leak shall be detected.
1. Installation (Space) · Product with flammable refrigerants, shall
be installed according to the minimum room area, Amin (m²) mentioned in Table
A of the Installation Instructions. · In case of field charge, the effect on
refrigerant charge caused by the different pipe length has to be quantified,
measured and labelled. · Must ensure the installation of pipe-work shall be
kept to a minimum. Avoid use dented pipe and do not allow acute bending. ·
Must ensure that pipe-work shall be protected from physical damage. · Must
comply with national gas regulations, state municipal rules and legislation.
Notify relevant authorities in accordance with all applicable regulations.
· Must ensure mechanical connections be accessible for maintenance purposes.
· In cases that require mechanical ventilation, ventilation openings shall be
kept clear of obstruction.
· When disposal of the product, do follow to the precautions in #12 and comply
with national regulations. Always contact to local municipal offices for
proper handling.
2. Servicing 2-1. Service personnel · The system is inspected, regularly
supervised
and maintained by a trained and certified service personnel who is employed by
the person user or party responsible. · Ensure the actual refrigerant charge
is in accordance with the room size within which the refrigerant containing
parts are installed. · Ensure refrigerant charge not to leak. · Any qualified
person who is involved with working on or breaking into a refrigerant circuit
should hold a current valid certificate from an industry-accredited assessment
authority, which authorizes their competence to handle refrigerants safely in
accordance with an industry recognised assessment specification. · Servicing
shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel
shall be carried out under the supervision of the person competent in the use
of flammable refrigerants. · Servicing shall be performed only as recommended
by the manufacturer.
2-2. Work · Prior to beginning work on systems containing
flammable refrigerants, safety checks are necessary to ensure that the risk of
ignition is minimised. For repair to the refrigerating system, the precautions
in #2-2 to #2-8 must be followed before conducting work on the system. · Work
shall be undertaken under a controlled procedure so as to minimize the risk of
a flammable gas or vapour being present while the work is being performed. ·
All maintenance staff and others working in the local area shall be instructed
and supervised on the nature of work being carried out. · Avoid working in
confined spaces. Always ensure away from source, at least 2 meter of safety
distance, or zoning of free space area of at least 2 meter in radius. · Wear
appropriate protective equipment, including respiratory protection, as
conditions warrant. · Keep all sources of ignition and hot metal surfaces
away.
Safety Precautions
English
25
Safety Precautions
2-3. Checking for presence of refrigerant · The area shall be checked with an
appropriate refrigerant detector prior to and during work, to ensure the
technician is aware of potentially flammable atmospheres. · Ensure that the
leak detection equipment being used is suitable for use with flammable
refrigerants, i.e. non sparking, adequately sealed or intrinsically safe. · In
case of leakage/spillage happened, immediately ventilate area and stay upwind
and away from spill/release. · In case of leakage/spillage happened, do notify
persons down wind of the leaking/ spill, isolate immediate hazard area and
keep unauthorised personnel out.
2-4. Presence of fire extinguisher · If any hot work is to be conducted on the
refrigerating equipment or any associated parts, appropriate fire
extinguishing equipment shall be available at hand. · Have a dry powder or CO2
fire extinguisher adjacent to the charging area.
2-5. No ignition sources · No person carrying out work in relation to a
refrigerating system which involves exposing any pipe work that contains or
has contained flammable refrigerant shall use any sources of ignition in such
a manner that it may lead to the risk of fire or explosion. They must not be
smoking when carrying out such work. · All possible ignition sources,
including cigarette smoking, should be kept sufficiently far away from the
site of installation, repairing, removing and disposal, during which flammable
refrigerant can possibly be released to the surrounding space. · Prior to work
taking place, the area around the equipment is to be surveyed to make sure
that there are no flammable hazards or ignition risks. · “No Smoking” signs
shall be displayed.
2-6. Ventilated area · Ensure that the area is in the open or that it is
adequately ventilated before breaking into the system or conducting any hot
work. · A degree of ventilation shall continue during the period that the work
is carried out. · The ventilation should safely disperse any released
refrigerant and preferably expel it externally into the atmosphere.
26
2-7. Checks to the refrigerating equipment · Where electrical components are
being
changed, they shall be fit for the purpose and to the correct specification. ·
At all times the manufacturer’s maintenance and service guidelines shall be
followed. · If in doubt consult the manufacturer’s technical department for
assistance. · The following checks shall be applied to installations using
flammable refrigerants. – The actual refrigerant charge is in
accordance with the room size within which the refrigerant containing parts
are installed. – The ventilation machinery and outlets are operating
adequately and are not obstructed. – If an indirect refrigerating circuit is
being used, the secondary circuit shall be checked for the presence of
refrigerant. – Marking to the equipment continues to be visible and legible.
Markings and signs that are illegible shall be corrected. – Refrigerating pipe
or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components,
unless the components are constructed of materials which are inherently
resistant to being corroded or are properly protected against being so
corroded.
2-8. Checks to electrical devices · Repair and maintenance to electrical
components shall include initial safety checks and component inspection
procedures. · Initial safety checks shall include but not limit to:- That
capacitors are discharged: this
shall be done in a safe manner to avoid possibility of sparking. – That there
no live electrical components and wiring are exposed while charging,
recovering or purging the system. – That there is continuity of earth bonding.
· At all times the manufacturer’s maintenance and service guidelines shall be
followed. · If in doubt consult the manufacturer’s technical department for
assistance. · If a fault exists that could compromise safety, then no
electrical supply shall be connected to the circuit until it is satisfactorily
dealt with. · If the fault cannot be corrected immediately but it is necessary
to continue operation, an adequate temporary solution shall be used. · The
owner of the equipment must be informed or reported so all parties are advised
thereinafter.
3. Repairs to sealed components · During repairs to sealed components, all
electrical supplies shall be disconnected from the equipment being worked upon
prior to any removal of sealed covers, etc. · If it is absolutely necessary to
have an electrical supply to equipment during servicing, then a permanently
operating form of leak detection shall be located at the most critical point
to warn of a potentially hazardous situation. · Particular attention shall be
paid to the following to ensure that by working on electrical components, the
casing is not altered in such a way that the level of protection is affected.
This shall include damage to cables, excessive number of connections,
terminals not made to original specification, damage to seals, incorrect
fitting of glands, etc. · Ensure that apparatus is mounted securely. · Ensure
that seals or sealing materials have not degraded such that they no longer
serve the purpose of preventing the ingress of flammable atmospheres. ·
Replacement parts shall be in accordance with the manufacturer’s
specifications. NOTE: The use of silicon sealant may inhibit the effectiveness
of some types of leak detection equipment. Intrinsically safe components do
not have to be isolated prior to working on them.
4. Repair to intrinsically safe components · Do not apply any permanent
inductive or
capacitance loads to the circuit without ensuring that this will not exceed
the permissible voltage and current permitted for the equipment in use. ·
Intrinsically safe components are the only types that can be worked on while
live in the presence of a flammable atmosphere. · The test apparatus shall be
at the correct rating. · Replace components only with parts specified by the
manufacturer. Unspecified parts by manufacturer may result ignition of
refrigerant in the atmosphere from a leak.
5. Cabling · Check that cabling will not be subject
to wear, corrosion, excessive pressure, vibration, sharp edges or any other
adverse environmental effects. · The check shall also take into account the
effects of aging or continual vibration from sources such as compressors or
fans.
6. Detection of flammable refrigerants · Under no circumstances shall
potential
sources of ignition be used in the searching or detection of refrigerant
leaks. · A halide torch (or any other detector using a naked flame) shall not
be used.
7. The following leak detection methods are deemed acceptable for all
refrigerant systems
· No leaks shall be detected using detection equipment with sensitivity to
detect leakage of 5g/year of refrigerant or better under a pressure of at
least 0.25 times the maximum allowable pressure (>1.04 MPa, max 4.15 MPa), for
example, a universal sniffer.
· Electronic leak detectors may be used to detect flammable refrigerants, but
the sensitivity may not be adequate, or may need re-calibration. (Detection
equipment shall be calibrated in a refrigerant-free area.)
· Ensure that the detector is not a potential source of ignition and is
suitable for the refrigerant used.
· Leak detection equipment shall be set at a percentage of the LFL of the
refrigerant and shall be calibrated to the refrigerant employed and the
appropriate percentage of gas (25 % maximum) is confirmed.
· Leak detection fluids are also suitable for use with most refrigerants, for
example, bubble method and fluorescent method agents. The use of detergents
containing chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work.
· If a leak is suspected, all naked flames shall be removed/extinguished.
· If a leakage of refrigerant is found which requires brazing, all of the
refrigerant shall be recovered from the system, or isolated (by means of shut
off valves) in a part of the system remote from the leak. The precautions in
8 must be followed to remove the refrigerant.
Safety Precautions
English
27
Safety Precautions
8. Removal and evacuation · When breaking into the refrigerant circuit
to make repairs or for any other purpose conventional procedures shall be
used. However, it is important that best practice is followed since
flammability is a consideration. The following procedure shall be adhered to:
remove refrigerant -> purge the circuit with inert gas -> evacuate -> purge
with inert gas -> open the circuit by cutting or brazing. · The refrigerant
charge shall be recovered into the correct recovery cylinders. · The system
shall be purged with OFN to render the appliance safe. · This process may need
to be repeated several times. · Compressed air or oxygen shall not be used for
this task. · Purging shall be achieved by breaking the vacuum in the system
with OFN and continuing to fill until the working pressure is achieved, then
venting to atmosphere, and finally pulling down to a vacuum. · This process
shall be repeated until no refrigerant is within the system. · When the final
OFN charge is used, the system shall be vented down to atmospheric pressure to
enable work to take place. · This operation is absolutely vital if brazing
operations on the pipe work are to take place. · Ensure that the outlet for
the vacuum pump is not close to any potential ignition sources and there is
ventilation available. OFN = oxygen free nitrogen, type of inert gas.
28
9. Charging procedures · In addition to conventional charging
procedures, the following requirements shall be followed. – Ensure that
contamination of different
refrigerants does not occur when using charging equipment. – Hoses or lines
shall be as short as possible to minimize the amount of refrigerant contained
in them. – Cylinders shall be kept in an appropriate position according to the
instructions. – Ensure that the refrigerating system is earthed prior to
charging the system with refrigerant. – Label the system when charging is
complete (if not already). – Extreme care shall be taken not to over fill the
refrigerating system. · Prior to recharging the system it shall be pressure
tested with OFN (refer to #7). · The system shall be leak tested on completion
of charging but prior to commissioning. · A follow up leak test shall be
carried out prior to leaving the site. · Electrostatic charge may accumulate
and create a hazardous condition when charging and discharging the
refrigerant. To avoid fire or explosion, dissipate static electricity during
transfer by grounding and bonding containers and equipment before
charging/discharging.
10. Decommissioning · Before carrying out this procedure, it is
essential that the technician is completely familiar with the equipment and
all its details. · It is recommended good practice that all refrigerants are
recovered safely. · Prior to the task being carried out, an oil and
refrigerant sample shall be taken in case analysis is required prior to re-use
of recovered refrigerant. · It is essential that electrical power is available
before the task is commenced. a) Become familiar with the equipment and
its operation. b) Isolate system electrically. c) Before attempting the
procedure ensure
that: · mechanical handling equipment is
available, if required, for handling refrigerant cylinders; · all personal
protective equipment is available and being used correctly; · the recovery
process is supervised at all times by a competent person; · recovery equipment
and cylinders conform to the appropriate standards. d) Pump down refrigerant
system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes
place.
g) Start the recovery machine and operate in accordance with instructions.
h) Do not over fill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even
temporarily.
j) When the cylinders have been filled correctly and the process completed,
make sure that the cylinders and the equipment are removed from site promptly
and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigerating
system unless it has been cleaned and checked.
· Electrostatic charge may accumulate and create a hazardous condition when
charging or discharging the refrigerant. To avoid fire or explosion, dissipate
static electricity during transfer by grounding and bonding containers and
equipment before charging/discharging.
11. Labelling · Equipment shall be labelled stating that it
has been de-commissioned and emptied of refrigerant. · The label shall be
dated and signed. · Ensure that there are labels on the equipment stating the
equipment contains flammable refrigerant.
12. Recovery · When removing refrigerant from a system,
either for servicing or decommissioning, it is recommended good practice that
all refrigerants are removed safely. · When transferring refrigerant into
cylinders, ensure that only appropriate refrigerant recovery cylinders are
employed. · Ensure that the correct number of cylinders for holding the total
system charge are available. · All cylinders to be used are designated for the
recovered refrigerant and labelled for that refrigerant (i.e. special
cylinders for the recovery of refrigerant). · Cylinders shall be complete with
pressure relief valve and associated shut-off valves in good working order. ·
Recovery cylinders are evacuated and, if possible, cooled before recovery
occurs.
· The recovery equipment shall be in good working order with a set of
instructions concerning the equipment that is at hand and shall be suitable
for the recovery of flammable refrigerants.
· In addition, a set of calibrated weighing scales shall be available and in
good working order.
· Hoses shall be complete with leak-free disconnect couplings and in good
condition.
· Before using the recovery machine, check that it is in satisfactory working
order, has been properly maintained and that any associated electrical
components are sealed to prevent ignition in the event of a refrigerant
release. Consult manufacturer if in doubt.
· The recovered refrigerant shall be returned to the refrigerant supplier in
the correct recovery cylinder, and the relevant Waste Transfer Note arranged.
· Do not mix refrigerants in recovery units and especially not in cylinders.
· If compressors or compressor oils are to be removed, ensure that they have
been evacuated to an acceptable level to make certain that flammable
refrigerant does not remain within the lubricant.
· The evacuation process shall be carried out prior to returning the
compressor to the suppliers.
· Only electric heating to the compressor body shall be employed to accelerate
this process.
· When oil is drained from a system, it shall be carried out safely.
Safety Precautions
English
29
How to Use
To adjust airflow direction
(swing) AIR SWING Upper direction
Indicators
POWER TIMER nanoe
TECHNOLOGY
Upper direction: · Do not adjust the flap by hand. * For details operation,
refer “To Learn More….”
Lateral direction: · For lateral direction, it is
manually adjustable as shown.
Lateral direction
POWERFUL/ ECO
OFF/ON
MODE SLEEP
TEMP
FAN SPEED/ QUIET
AIR SWING
ON TIMER
OFF
SET CANCEL
AIR CONDITIONER
Not used in normal operation.
Press to turn the Wireless LAN feature ON or OFF.
Press to restore the remote control to default setting.
30
To adjust FAN SPEED and QUIET condition
FAN SPEED/ QUIET
FAN SPEED: · When AUTO FAN is selected, the fan speed is adjusted
automatically according to the operation mode.
QUIET: · This operation reduces airflow noise.
To switch between POWERFUL/ECO
POWERFUL/ ECO
(exit setting)
POWERFUL: To reach the desired temperature quickly · This operation is
automatically stop after 20 minutes. ECO: · To reduce power consumption for
better energy saving
without sacrificing comfort.
To enjoy fresher and cleaner environment
· This operation combines both nanoeTMX and nanoeTM-G (nanoeTM TECHNOLOGY).
· nanoeTM TECHNOLOGY automatically starts when the unit is turned on.
· Press
to turn ON or OFF this operation manually.
· This operation can be activated even when the unit is OFF. Note that the flap and fan speed will operate according to the remote control setting.
· If a power failure occurs during this operation, this operation resumes immediately when power resumes.
To connect to a network
See “To Learn More…” for details.
· For Wireless LAN Module operation setup, please refer to Setup Instructions Manual.
To maximise comfort while sleeping
SLEEP
· This operation provides you with a comfortable environment while sleeping.
It will automatically adjust the sleep pattern temperature during the
activation period.
· The indoor unit indicator will dim when this operation is activated. This is
not applicable if the indicator brightness has been manually dimmed.
· This operation is incorporated with the activation timer (0.5, 1, 2, 3, 4,
5, 6, 7, 8 or 9 hours). · This operation can be set together with timer. Sleep
operation has the priority over OFF timer. · This operation can be cancelled
by pressing the respective button until the sleep timer reaches 0.0h.
To set the timer
You can set the timer to turn on and off the unit at 2 different preset time.
123
ON TIMER
OFF
SET CANCEL
1 Select TIMER ON or Example:
TIMER OFF.
OFF at 22:00
· Each time pressed: OFF
(exit setting)
2 Set the time.
· To cancel the timer, press ON or OFF to select the respective setting or ,
then press . CANCEL
· If the timer has been cancelled manually or due to power failure, you can
restore the timer again. Press ON or OFF to select the respective setting or ,
then press . SET
· The nearest timer setting is displayed and will activate in sequence.
· The timer operation follows the clock setting on the remote control and will
repeat daily when timer has been set. For clock setting, refer to Quick Guide.
3 Confirm the setting. SET
How to Use
English
Note
, SLEEP
POWERFUL/
, ECO
· Can be selected at the same time.
· Can be activated in all modes.
FAN SPEED/
POWERFUL/
, QUIET
ECO
· POWERFUL, QUIET and FAN SPEED cannot be selected at the same time.
31
To Learn More…
Operation mode
AUTO : The POWER indicator blinks at the initial stage. The unit will select
an operation mode depending on the room temperature.
COOL : Provides efficient comfort cooling to suit your needs. DRY : Operates
at low fan speed for a gentle cooling operation.
Energy saving temperature setting
You may save energy when operating the unit within the recommended temperature
range. COOL : 26.0 °C ~ 28.0 °C / 79 °F ~ 82 °F.
Air flow direction
In COOL/DRY mode: The horizontal flap is fixed at middle position setting.
Once the temperature is achieved, the horizontal flap swings up/down
automatically.
In COOL/DRY mode: The horizontal flap swings up/down automatically.
Auto restart control When power is resumed after a power failure, the
operation will restart automatically with the last operation mode and airflow
direction. · This control is not applicable when TIMER is set.
nanoeTMX Inside Cleaning
Depending on the unit’s accumulated operation time, the nanoeTMX may be
activated only once a day after the unit is turned off standby mode. During
the nanoeTMX Inside Cleaning operation, the flap will open slightly with low
fan speed operation for 2.5 hours if the unit was in COOL/DRY mode, and 2
hours if the unit was in nanoeTM TECHNOLOGY, before the unit is turned off.
This is to remove viruses/bacteria from the surroundings. The Inside Cleaning
operation is complete when the fan stops and the flap closes. Do not turn off
the power supply during this operation. After a power failure, this operation
will not resume.
Operating conditions
Use this air conditioner in the temperature range indicated in the table.
Temperature °C (°F)
DBT
Indoor
WBT
DBT
Outdoor
WBT
COOL
Max. Min.
32 (89.6) 16 (60.8)
23 (73.4) 11 (51.8)
46 (114.8) 16 (60.8)
26 (78.8) 11 (51.8)
DBT: Dry bulb temperature, WBT: Wet bulb temperature
32
To Learn More… / Cleaning the Air Conditioner
Cleaning the Air Conditioner
Cleaning has to be carried out at regular intervals to ensure the unit is at
optimal performance. A dirty unit may cause malfunction and you may retrieve
“H 99” error code. Consult an authorised dealer.
· Before cleaning, switch off the power supply and unplug the unit.
· Do not touch the aluminium fin as the sharp parts may cause injury.
· Do not use benzine, thinner or scouring powder.
· Use soap ( pH 7) or neutral household detergent only.
· Do not use water hotter than 40 °C / 104 °F.
Indoor unit Front panel
Aluminium fin
AUTO OFF/ON
Air filters
nanoeTM-G Generator
Indoor unit
Do handle the unit surface with care to avoid scratches by sharp or rough
items (e.g. fingernails, tools, rings, etc). Wipe the unit gently with a soft
damp cloth. The coils and fans should be cleaned periodically by an authorised
dealer.
Front panel
Wash gently and dry.
How to remove front panel
2 Pull upward
Horizontal
1 Raise over horizontal level
Close it securely 2 Match and push in
Outdoor unit
Clean the debris that surround the unit. Clear any blockage from the drain
pipe.
nanoeTM-G Generator Once every 2 weeks
· Clean with dry cotton bud. · Do not touch during operation.
Air filters Once every 2 weeks
· Wash/rinse the filters gently with water to avoid damaging the surface.
· Dry the filters thoroughly under a shade, away from fire or direct sunlight.
· Replace any damaged filters.
Remove air filter
Attach air filter
English
AUTO OFF/ON
1
Hold
Remove from the unit Insert into the unit
horizontally
3 Close down 4 Press both ends and center of the front panel
33
Troubleshooting
The following symptoms do not indicate malfunction.
Symptom
Cause
POWER indicator blinks before the unit is switched on.
· This is the preliminary step to prepare for the TIMER operation after it has
been set.
· When Timer is set ON, the unit may start earlier (up to 15 minutes) before
the actual set time to achieve the desired temperature on time.
TIMER indicator is always ON.
· When Timer has been set, the Timer setting repeats daily.
Operation is delayed a few minutes after restarting. · The delay is a protection to the unit’s compressor.
Indoor fan stops occasionally during automatic fan · This is to help remove the surrounding odour. speed setting.
The room has a peculiar odour.
· This may be due to damp smell emitted by the wall, carpet, furniture or clothing.
Cracking sound during operation.
· Changes in temperature caused the unit to expand and contract.
Water flowing sound during operation.
· Refrigerant flow inside the unit.
Mist emerges from indoor unit.
· During cooling operation, the discharged cold air may condense to water vapour.
Outdoor unit emits water or steam.
· During cooling operation, condensation occurs on cold pipes and the condensed water may drip from the outdoor unit.
Discoloration of some plastic parts.
· Discoloration is subjected to the types of materials used in plastic parts. It is accelerated when exposed to heat, sun light, UV light or environmental factors.
After extended use, dust may cover the front panel, · The dust accumulation is due to the air purification effect of
grilles and the wall surrounding the unit.
negative ions from nanoeTM-G. Remove the dust regularly
with a clean dampened cloth.
Soft buzzing sound from indoor unit during nanoeTM TECHNOLOGY operation.
· It is normal when the nanoeTMX generator is working. If you are concerned about the sound, cancel the nanoeTM TECHNOLOGY operation.
Wireless LAN indicator is ON when the unit is OFF. · The unit’s wireless LAN connection with the router has been activated.
Check the following before calling for servicing.
Symptom Operation in COOL mode is not working efficiently.
Noisy during operation.
Remote control does not work. (Display is dim or transmission signal is weak.)
The unit does not work.
The unit does not receive the signal from the remote control.
The nanoeTM TECHNOLOGY indicator at the indoor unit is not ON when nanoeTM
TECHNOLOGY is activated.
Check
· Set the temperature correctly. · Close all doors and windows. · Clean or
replace the filters. · Clear any obstruction at the air inlet and air outlet
vents.
· Check if the unit has been installed at an incline. · Close the front panel
properly.
· Insert the batteries correctly. · Replace weak batteries.
· Check if the circuit breaker is tripped. · Check if timers have been set.
· Make sure the receiver is not obstructed. · Certain fluorescent lights may
interfere with the signal
transmitter. Consult an authorised dealer.
· Use the remote control to retrieve the error code and consult an authorised
dealer.
34
When…
The remote control is missing or a malfunction has occurred
1.Raise the front panel.
2.Press AUTO OFF/ON once to use in AUTO mode.
3.Press AUTO OFF/ON hold for 5 seconds until you hear 1 beep, then
AUTO OFF/ON
release to use in forced COOL mode. (This operation shall be performed
by service personnel)
4.Press AUTO OFF/ON again to turn off the unit.
The indicators are too bright · To dim or restore the indicators’ brightness on the unit, press seconds.
on the remote for 5
Conducting a seasonal inspection after extended period of non-use · Check the
batteries. · Check that there is no obstruction around the air inlets and
outlet vents. · Use AUTO OFF/ON on the unit to select COOL mode. For details,
refer “The remote control is missing or a malfunction has occurred” above.
After 15 minutes of operation, it is normal to have the following temperature
difference between the air inlet and outlet vents:
COOL: 8 °C / 14.4 °F
The units will not be used for an extended period · Activate nanoeTM
TECHNOLOGY mode for 2~3 hours to remove any moisture left in the internal
parts thoroughly. This is to prevent mould growth. · Turn off the power supply
and unplug the unit. · Remove the batteries from the remote control.
NON SERVICEABLE CRITERIAS TURN OFF THE POWER SUPPLY AND UNPLUG THE UNIT. Then consult an authorised dealer in the following conditions: · Abnormal noise during operation. · Water/foreign particles have entered the remote control. · Water is leaking from the indoor unit. · The circuit breaker switches off frequently. · The power cord becomes unnaturally warm. · The switches or buttons are not functioning properly.
Troubleshooting
English
35
Troubleshooting
How to retrieve error codes
If the unit stops and the TIMER indicator blinks, use the remote control to retrieve the error code.
1 Press for 5 seconds
3 Press for 5 seconds to
2 Press until you hear beep
ON
SET
sound, then write down the
TIMER
error code
OFF
CANCEL
4 Turn the unit off and
inform the error code to an
quit checking
authorised dealer.
· For certain errors, you may restart the unit for limited operation if there are 4 beeps when operation starts.
Diagnostic display
H 00 H 11 H 12 H 14
H 15
H 16
H 17 H 19 H 21
H 23
H 24 H 25 H 26 H 27
H 28
H 30 H 31 H 32
H 33
H 34
H 35
H 36
H 37 H 38 H 39
Abnormality/Protection control
No memory of failure
Indoor/outdoor abnormal communication
Indoor unit capacity unmatched
Indoor intake air temperature sensor abnormality
Outdoor compressor temperature sensor abnormality
Outdoor current transformer (CT) abnormality
Outdoor suction temperature sensor abnormality
Indoor fan motor mechanism lock
Indoor float switch operation abnormality
Indoor heat exchanger temperature sensor 1 abnormality
Indoor heat exchanger temperature sensor 2 abnormality
Indoor ion device abnormality
Minus ION abnormality
Outdoor air temperature sensor abnormality
Outdoor heat exchanger temperature sensor 1 abnormality
Outdoor discharge pipe temperature sensor abnormality
Abnormal swimming pool sensor
Outdoor heat exchanger temperature sensor 2 abnormality
Indoor/outdoor misconnection abnormality
Outdoor heat sink temperature sensor abnormality
Indoor/outdoor water adverse current abnormality
Outdoor gas pipe temperature sensor abnormality
Outdoor liquid pipe temperature sensor abnormality
Indoor/outdoor mismatch (brand code)
Abnormal indoor operating unit or standby units
Diagnostic display
H 41 H 50 H 51 H 52 H 58 H 59 H 64 H 67 H 70 H 71 H 72 H 85 H 97 H 98 H 99 F
11 F 16 F 17 F 18 F 87 F 90 F 91 F 93
F 94
F 95
F 96 F 97 F 98 F 99
Abnormality/Protection control
Abnormal wiring or piping connection
Ventilation fan motor locked
Ventilation fan motor locked
Left-right limit switch fixing abnormality
Indoor gas sensor abnormality
Eco sensor abnormality
Outdoor high pressure sensor abnormality
nanoe abnormality
Light sensor abnormality
DC cooling fan inside control board abnormality
Abnormality tank temperature sensor
Abnormal communication between indoor & wireless LAN module
Outdoor fan motor mechanism lock
Indoor high pressure protection
Indoor operating unit freeze protection
4-way valve switching abnormality
Total running current protection
Indoor standby units freezing abnormality
Dry circuit blocked abnormality
Control box overheat protection
Power factor correction (PFC) circuit protection
Refrigeration cycle abnormality
Outdoor compressor abnormal revolution
Compressor discharge pressure overshoot protection
Outdoor cooling high pressure protection
Power transistor module overheating protection
Compressor overheating protection
Total running current protection
Outdoor direct current (DC) peak detection
- Some error code may not be applicable to your model. Consult an authorised dealer for clarification.
36
Information
Information for Users on Collection and Disposal of Old Equipment and used
Batteries
[Information on Disposal in other Countries outside the European Union] These
symbols are only valid in the European Union. If you wish to discard these
items, please contact your local authorities or dealer and ask for the correct
method of disposal.
Note for the battery symbol (bottom two symbol examples): This symbol might be
used in combination with a chemical symbol. In this case it complies with the
requirement set by the Directive for the chemical involved.
Pb
WARNING
This symbol shows that this equipment uses a mildly flammable refrigerant. If the refrigerant is leaked, together with an external ignition source, there is a possibility of ignition.
This symbol shows that a service personnel should be handling this equipment with reference to the Installation Instructions.
This symbol shows that the Operation Instructions should be read carefully.
This symbol shows that there is information included in the Operation
Instructions and/or Installation Instructions.
Troubleshooting / Information
English
37
Memo
Memo
Panasonic Corporation
1006, Oaza Kadoma, Kadoma City, Osaka 571-8501, Japan Website:
http://www.panasonic.com
© Panasonic Corporation 2022
Printed in Malaysia
ACXF55-35690 SY0822-0
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>