Honeywell Sensepoint Fixed Gas Detector Instruction Manual
- October 30, 2023
- Honeywell
Table of Contents
Honeywell Sensepoint Fixed Gas Detector
INTRODUCTION
The Sensepoint range of flammable, toxic and Oxygen gas detectors offer users a low cost solution to their gas monitoring needs, in or out of doors and even in potentially explosive atmospheres. Supplied with a pre-wired junction box, a detector can be installed using conduit or armored cable and glands depending on individual site standards.
Sensepoint flammable and toxic gas detectors are designed for use in
potentially explosive atmospheres and allow for hands free, unhindered access,
to terminals via the hinged lid of the junction box. Installation should
follow national guidelines using suitably approved armored cable and glands or
conduit. Supplied with earth continuity plate for improved immunity to RFI the
junction box offers the installer a choice of 1/2”, 3/4” and M20 connection
via conduit or armored cable and Exe certified cable glands. Terminals are
suitable for use with screened 0.5mm2 (20AWG) to 2.5mm2 (14AWG) cross
sectional area cable, as needed to ensure minimum operating voltage at the
detector, depending upon installed cable length.
Sensepoint flammable, toxic and Oxygen gas detectors are designed for direct
connection with the Honeywell Analytics’ range of Touchpoint controllers.
Contact Honeywell Analytics for details.
FEATURE
One-Stop Shop
- Flammable, toxic and Oxygen versions available
- Suitable for indoor or outdoor use
- IP65 as standard
Proven Sensor Technology
- SurecellTM electrochemical sensors
- Poison resistant catalytic bead
- Fast and reliable
- Typical 2 to 5 years operational life
ATEX Certified
- Complies with the latest European standards
- Hazardous area approval AND performance
- Can be used for uncertified applications
Easy to Use
- Factory set operation
- Simple to replace
- Minimal training required
Friendly Installation
- Universal junction box
- One box, three entries
- Metric and NPT compatibility
- Includes earth continuity plate for added RFI protection
Range of Accessories
- Weather Housing (IP66)
- Flow adaptor
- Duct mounting kit
- Collecting cone
INSTALLATION DETAILS
Dimensions
- Sensepoint flammable and toxic gas detectors allow for hands free, unhindered access, to terminals via the hinged lid of the junction box.
- Supplied with earth continuity plate for improved immunity to RFI, the junction box offers the installer a choice of 1/2”NPT, 3/4”NPT and M20 connection via conduit or steel wire armored cable and Exe certified cable glands.
- Sensepoint flammable, toxic and Oxygen gas detectors are designed for direct connection with the Honeywell Analytics’ range of Touchpoint controllers. Contact Honeywell Analytics for details.
Flammable Version
- Terminal Arrangement
- Electrical Connections
Toxic & Oxygen Version
- Terminal Arrangement
- Electrical Connections
Technical Summary
General Specification
Use| Low cost, fixed point gas detector for the protection of personnel and
plant from flammable, toxic and Oxygen gas hazards
Detectable Gases
| Gas| Measuring Range| Operating Temperature*|
Ident Name| 1#| 2| 3| Min| Max*|
F| Flammable| 0-100% LEL| | | -40°C / -40°F| 50°C / 122°F|
O| Oxygen| 0-25% VOL| | | -15°C / 5°F| 40°C / 104°F|
C| Carbon Monoxide+| 0-200ppm| 0-500ppm| | -20°C / -4°F| 50°C / 122°F|
H| Hydrogen Sulphide+| 0-50ppm| 0-20ppm| 0-100ppm| -25°C / -13°F| 50°C /
122°F|
G| Hydrogen| 0-1000ppm| | | -5°C / 23°F| 40°C / 104°F|
L| Chlorine| 0-5ppm| 0-15ppm| | -20°C / -4°F| 50°C / 122°F|
S| Sulphur Dioxide| 0-15ppm| 0-50ppm| | -15°C / 5°F| 40°C / 104°F|
N| Nitrogen Dioxide| 0-10ppm| | | -15°C / 5°F| 40°C / 104°F|
A| Ammonia| 0-50ppm| 0-1000ppm| | -20°C / -4°F| 40oC / 104°F|
+ SureCellTM Sensing Technology| #Standard range| | | | Check certified
temperature|
Construction|
|
| Electrical| Flammable (0-100%LEL)**
3 wire mV bridge
| Toxic & Oxygen
2 wire loop powered 4-20mA
| Junction Box
Earth continuity plate
|
| 2.9-3.5V, 0.7W| (plus screen)| BK4 terminal block (4 way)|
| 200mA constant current| 16-30Vdc, O.9W| 4 x 0.5mm2 (20AWG) to 2.5mm2
(14AWG)|
| | | 1 x M20, 1 x 3/4″ NPT, 1×1/2″ NPT|
Material| Polyphenylene Sulphide (PPS)| Polyphenylene Sulphide (PPS)|
Fire retardant GFP|
Weight| 190g| 185g (205g oxygen)| 600g|
Certification| Ex II 2 G D EExd IIC| Ex II 2 G D EExd ia IIC| Ex II 2 G
D EExe II|
| T6 T85 Deg C| T4 T135 Deg C| T6 T85 Deg C|
| Tamb = -55°C to +55°C| Tamb = -55°C to +65°C| Tamb = -40°C to +50°C|
| BAS98ATEX2156X| BAS98ATEX2157X| SIRA04ATEX3018|
| SIRA03ATEX1116X| | |
| (Performance)| | |
Applicable Standards| This product complies with the relevant CE
standards including:|
| EMC to EN50270, Flammable to EN50054, Toxic to EN445544 (H2S only)|
Environmental
| IP Rating| IP65 standard, IP66 with weather protection in accordance
with EN60529:1992|
Operating Temperature| Dependent upon gas type and certification|
Operating Humidity Range| Continuous: 20-90%RH (non condensing),
Intermittent: 10-99%RH (non condensing)|
Operating Pressure| 90-110kPa|
Storage Conditions| Instrument -40°C to +50°C (-40°F to +122°F)|
Ordering Information
Our Product Range
Fixed Gas Monitoring
Honeywell Analytics offers a wide range of fixed gas detection solutions for a
diverse array of industries and applications including: Commercial properties,
industrial applications, semiconductor manufacturers, energy plants and
petrochemical sites.
- Detection of flammable, oxygen and toxic gases (including exotics).
- Innovative use of 4 core sensing technologies – paper tape, electrochemical cell, catalytic bead and infrared.
- Capability to detect down to Parts Per Billion (ppb) or Percent by Volume (%v/v).
- Cost effective regulatory compliance solutions.
Portable Gas Monitoring
When it comes to personal protection from gas hazards, Honeywell Analytics has
a wide range of reliable solutions ideally suited for use in confined or
enclosed spaces.
These include:
- Detection of flammable, oxygen and toxic gases
- Single gas personal monitors – worn by the individual
- Multi-gas portable gas monitors – used for confined space entry and regulatory compliance
- Multi-gas transportable monitors – used for temporary protection of area during site construction and maintenance activities
Technical Services
At Honeywell Analytics, we believe in the value of great service and customer
care. Our key commitment is providing complete and total customer
satisfaction. Here are just a few of the services we can offer:
- Full technical support
- Expert team on hand to answer questions and queries
- Fully equipped workshops to ensure quick turnaround on repairs
- Comprehensive service engineer network
- Training on product use and maintenance
- Mobile calibration service
- Customised programmes of preventative/corrective maintenance
- Extended warranties on products
Find out more: www.honeywellanalytics.com
Contact Honeywell Analytics:
Europe, Middle East, Africa
Life Safety Distribution AG Wilstrasse 11-U31 CH-8610 Uster
Switzerland
Tel: +41 (0)44 943 4300
Fax: +41 (0)44 943 4398
gasdetection@honeywell.com
Americas
Honeywell Analytics Distribution, Inc. 405 Barclay Bivd. Lincolnshire, IL
60069
USA
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
Fax: +1 847 955 8208
detectgas@honeywell.com
Asia Pacific
Honeywell Analytics Asia Pacific #508, Kolon Science Valley (1) 187-10 Guro-
Dong, Guro-Gu Seoul, 152-050,
Korea
Tel: +82 (0)2 2025 0307
Fax: +82 (0)2 2025 0329
analytics.ap@honeywell.com
Technical Services
ha.emea.service@honeywell.com
www.honeywell.com
Please Note:
While every effort has been made to ensure accuracy in this publication, no
responsibility can be accepted for errors or omissions. Data may change, as
well as legislation, and you are strongly advised to obtain copies of the most
recently issued regulations, standards, and guidelines. This publication is
not intended to form the basis of a contract.
H_Sensepoint_DS0326_V5_EMEA
10/07
© 2007 Honeywell Analytics
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>