PIONEER WYT040GLHI22M4 Multi Zone Series Ductless Air Conditioner Heat Pump Instruction Manual

October 30, 2023
Pioneer

PIONEER WYT040GLHI22M4 Multi Zone Series Ductless Air Conditioner Heat Pump

WYT040GLHI22M4 Multi Zone Series Ductless Air Conditioner Heat
Pump

IMPORTANT NOTICE:
Please read this manual carefully before installing or operating your new air conditioning system. Be sure to save this manual for future reference.

Signal Cable Wiring Diagram(s) for Multi-Circuit Condenser Units

Note Prior to Installation:

The connection cables must be plugged to the corresponding terminals as shown below. Terminal A on the outdoor unit must be connected with Terminal A on the indoor unit, B to B, and so on.

Signal Cable Wiring Diagram\(s\)

CAUTION
CROSS-WIRING IS A VERY EASY MISTAKE TO MAKE. ALWAYS DOUBLE CHECK THAT THE LINE GOING FROM A GIVEN TERMINAL BLOCK IS CORRESPONDING TO THE CORRECT ONE INDOOR.

Connecting Refrigerant Piping for Multi-Circuit Condenser Units

Note Prior to Installation:

The process for connecting the copper refrigerant lines for indoor and outdoor are given in the full installation manual. Repeat the process for connection and leak-checking according to the amount of zones to be installed. All pipe sets use a 1/4” diameter size for the liquid (smaller) side, but the gas (bigger) line may require the usage of adapters to convert the 3/8” size to 1/2” or 5/8”. Use the included adapters according to the zone combination to be installed, and refer to the installation manual for proper torquing values. Connecting Refrigerant Piping for Multi-Circuit Condenser
Units

Regarding the Scope of this Technical Document

Note Prior to Installation:

This manual is intended to supplement the default User and Installation Manual that is found packaged together with the indoor air handler, when used for installation of a Multi-Zone system. The process to install a multi-split system is nearly identical to single-split, with the addition of some repeated steps, and using the additional details found herein.

Allowable Zone Combinations for Multi-Circuit Condenser Units

Outdoor Unit Model Number

|

YN020GLFI22M2D

|

YN030GLFI22M3D

|

YN040GLFI22M4D

---|---|---|---

Number of Available Zones

|

Two (2)

|

Three (3)

|

Four (4)

**Two Zones Utilized (Allowable Combinations in BTU)**

|

**** 9000 + 9000
9000 + 12000
12000 + 12000

|

**** 9000 + 9000      12000 + 12000
9000 + 12000    12000 + 18000
9000 + 18000    18000 + 18000

|

9000 + 9000      12000 + 18000
9000 + 12000     12000 + 24000
9000 + 18000     18000 + 18000
9000 + 24000     18000 + 24000
12000 + 12000 24000 + 24000

**Three Zones Utilized (Allowable Combinations in BTU)**

| |

**** 9000 + 9000 + 9000
9000 + 9000 + 12000
9000 + 9000 + 18000
9000 + 12000 + 12000
9000 + 12000 + 18000 12000 + 12000 + 12000

|

9000 + 9000 + 9000
9000 + 9000 + 12000
9000 + 9000 + 18000
9000 + 9000 + 24000
9000 + 12000 + 12000
9000 + 12000 + 18000
9000 + 12000 + 24000
9000 + 18000 + 18000
9000 + 12000 + 12000
12000 + 12000 + 18000
12000 + 12000 + 24000
12000 + 18000 + 18000

**Four Zones Utilized (Allowable Combinations in BTU)**

| | |

9000 + 9000 + 9000 + 9000
9000 + 9000 + 9000 + 12000
9000 + 9000 + 9000 + 18000
9000 + 9000 + 9000 + 24000
9000 + 9000 + 12000 + 12000
9000 + 9000 + 12000 + 18000
9000 + 12000 + 12000 + 12000
12000 + 12000 + 12000 + 12000

  • Different models of all available matching indoor units can be combined together in any order to create a multi zone split system, up to a quantity of the number of available circuits.
  • Not all available circuits need to be utilized with an attached indoor unit. 66% or higher of the total capacity utilization is recommended.
  • Every indoor unit attached to a multi zone system will operate at a random, self-regulated capacity, based on the actual demand it measures from the zone it is serving (Between 30% to 100% of its rated capacity) or turn OFF as needed.
  • Outdoor units will also self-regulate their total output capacity, based on the total demand it reads from all of the simultaneously running indoor units at any given moment, up to its maximum rating capacity.
  • With multi-split systems, the total demand from the outdoor unit, will seldomly exceed 75% of the total available capacity of the combined indoor unit group due to load fluctuations of each indoor unit. Therefore, total attached indoor unit capacity can be selected up to 133% of the supporting outdoor unit’s rated capacity.
  • Although very seldom, if the total demand from the combined group of indoor units exceeds the rated capacity of the outdoor unit, the capacity of each indoor unit will be attenuated accordingly.
  • For high demand applications, max loading limits may need to be reduced up to 20% to avoid underperformance risks during some extreme conditions.
  • The BTU order of attached indoor units has no effect on performance.

Anchoring the Outdoor Unit

The outdoor unit can be anchored to the ground or to wall-mounted brackets. The following is a list of different outdoor unit sizes and the distance between their mounting feet. Prepare the installation base of the unit according to the dimensions found below:

Pioneer WYT Series Multi Split MODEL/Type (Circuit/Series)| D| E| F| G| H| I| K| M
---|---|---|---|---|---|---|---|---
YN020GLFI22M2D (Dual-Circuit, E-Star)| 845 mm 33-1/4 in.| 693mm 27-1/4 in.| 336 mm 13-1/4 in.| 586 mm 23-1/16 in.| 375 mm 14-3/4 in.| 347.5 mm 13-11/16 in.| 58.6 mm 2-5/16 in.| 63 mm 2-1/2 in.
YN030GLFI22M3D (Triple-Circuit, E-Star)| 900 mm 35-7/16 in.| 650 mm 25-9/16 in.| 315 mm 12-3/8 in.| 623 mm 24-1/2 in.| 374 mm 14-3/4 in.| 347 mm 13-11/16 in.| 61 mm 2-3/8 in.| 56 mm 2-3/16 in.
YN040GLFI22M4D (Quad-Circuit, E-Star)| 940 mm

37 in.

| 910 mm 35-13/16 in.| 340 mm 13-3/8 in.| 600 mm 23-5/8 in.| 400 mm 15-3/4 in.| 375 mm 14-3/4 in.| 80 mm 3-1/8 in.| 45 mm 1-3/4 in.

Anchoring the Outdoor Unit
If installing the unit on the ground or on a concrete mounting platform, do the following:

  1. Mark the positions for four expansion bolts based on dimensions in the “Unit Mounting Dimensions” chart.
  2. Pre-drill holes for expansion bolts.
  3. Clean concrete dust away from holes.
  4. Place a nut on the end of each expansion bolt.
  5. Hammer expansion bolts into each hole.
  6. Remove the nuts from expansion bolts, and place the outdoor unit onto the bolts.
  7. Put washers onto each expansion bolt, then replace each of the nuts.
  8. Using a wrench, tighten each nut until snug.

WHEN DRILLING INTO CONCRETE, WEAR EYE PROTECTION AT ALL TIMES

Allowable Connected Piping Length and Elevation Differences

Note Prior to Installation:

When installing multiple indoor units to work with a single outdoor unit, ensure that the length of the refrigerant pipe and the drop height between the indoor and outdoor units meet the requirements illustrated in the following diagram:

Allowable Connected Piping Length and Elevation
Differences

Unit: m/ft.

Unit Type 2 Zone 3 Zone 4 Zone
Max. length for all rooms 30/100 50/165 60/200
Max. length for one indoor unit 20/65 25/80 25/80
Max. height difference between indoor/outdoor unit 15/50 15/50 15/50
Max. height difference between indoor units 30/100 30/100 30/100

Rebalancing Refrigerant Levels Based on Combined Piping Length

For installations with connected lengths beyond standard, charge additional R410a based on the below:

Unit Type Pre-Charged For: Amount of Refrigerant to Add:
2-Zone 15/50 (Total Attached) 20g x (L1+L2-15M)
3-Zone 23/75 (Total Attached) 20g x (L1+L2+L3-23M)
4-Zone* 30/100 (Total Attached) 20g x (L1+L2+L3+L4-30M)

(L1+L2+L3+L4-100ft)

Unit: m/ft. * For any 24K BTU air handlers attached, let L for that length equal 2L.

The design and specifications of this product are subject to change without prior notice as development continues. Consult with the sales agency or manufacturer for details. Refer to the equipment nameplate for all other applicable specifications.

Customer Support

Parker Davis HVAC International, Inc.
3250 NW 107 Avenue, Doral, FL 33172 – USA
Tel : (305) 513-4488
Fax : (305) 513-4499
E-mail : [email protected]
Website: www.pd-hvac.com

Pioneer product line, parts, and supplies are available online for convenient ordering at:
www.highseer.com
www.pioneerminisplit.com

Scan the below code to visit our support page where you can find more installation materials:

REV080922

PIONEER Logo

Documents / Resources

| PIONEER WYT040GLHI22M4 Multi Zone Series Ductless Air Conditioner Heat Pump [pdf] Instruction Manual
WYT040GLHI22M4, YN020GLFI22M2D, WYT040GLHI22M4 Multi Zone Series Ductless Air Conditioner Heat Pump, Multi Zone Series Ductless Air Conditioner Heat Pump, Ductless Air Conditioner Heat Pump, Air Conditioner Heat Pump, Conditioner Heat Pump, Heat Pump
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Pioneer User Manuals

Related Manuals