JOTUL GF 520 DV Direct Vent Gas Stove Instruction Manual Direct Vent Gas Stove
- October 30, 2023
- Jotul
Table of Contents
GF 520 DV Direct Vent Gas Stove
Direct Vent Gas Stove
Product Information
-
Model Number: 130139_Rev 1 GF 520 DV 12/22
-
Appliance Type: Gas Stove
-
Location: Aftermarket, permanently located, manufactured home
or mobile home (where not prohibited by local codes) -
Gas Type: Natural Gas / Propane
-
Certifications: CSA P.4.1-15
Product Usage Instructions
Before using the Direct Vent Gas Stove, please read and follow
all installation and operation instructions carefully. Failure to
do so could result in property damage, personal injury or loss of
life.
Suggested Tools for Installation and Service
The following tools are recommended for installation and
service:
- T-Handle (required in Massachusetts)
Fuel Conversion
The Direct Vent Gas Stove is only for use with the types of gas
indicated on the rating plate. If you need to convert the stove to
use a different type of gas, a conversion kit is supplied with the
appliance.
Initial Break-in
During the initial stages of operation, smoke and odor may occur
depending upon temperatures generated over time. This curing
condition can be alleviated by promoting fresh air circulation
within the immediate vicinity of the appliance. Refer to page 23
for further information.
Operation Sound
Cast iron and steel components expand and contract with
temperature fluctuations that are often accompanied by creaking or
pinging sounds. This is the result of natural thermal activity. The
optional blower fan will also generate a slight hum at the low
setting and progressively increase with the velocity of forced
air.
Installation Requirements for the Commonwealth of
Massachusetts
If you are installing the Direct Vent Gas Stove in the
Commonwealth of Massachusetts, it must be installed by a licensed
master or journeyman plumber or gas-fitter. The following
requirements must also be met:
- If there is not one already present, a carbon monoxide detector
must be installed on each floor.
Table of Contents
The user manual includes the following sections:
- Specifications
- Initial Assembly
- General Information
- Safety Information
- Installation Requirements
- Floor Protection
- Clearances
- Vent Requirements
- Vertical Termination
- Horizontal Termination
- Fuel Conversion
- Gas Connection
- Gas Pressure
- High Altitude Adjustment
- Optional Equipment
- Firebox Panel Kits
- Burner Media Installation (Log Set)
130139_Rev 1 GF 520 DV 12/22
Jøtul GF 520 DV and Jøtul GF 520 DV MV
Direct Vent Gas Stove
Installation and Operation Instructions
Certified to ANSI Z21.88-2019 · CSA 2.33-2019 and CAN/CGA 2.17-M17.
INSTALLER: Leave this manual with the appliance. OWNER: Retain this manual for
future reference.
WARNING: If the information in these instructions is not followed exactly, a
fire or explosion may result causing property damage, personal injury or loss
of life.
Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not
touch any electrical switch; do not use any phone in your building. · Leave
the building immediately. · Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions. · If you cannot
reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
In the Commonwealth of Massachusetts, a carbon monoxide (CO) detector shall
be installed in the same room as the appliance.
This appliance may be installed in an aftermarket, permanently located,
manufactured home or mobile home, where not prohibited by local codes. This
appliance is only for use with the types of gas indicated on the rating plate.
A conversion kit is supplied with the appliance.
! DANGER
HOT GLASS WILL CAUSE BURNS. DO NOT TOUCH GLASS UNTIL COOLED. NEVER ALLOW
CHILDREN TO TOUCH GLASS.
A barrier designed to reduce the burn hazard from the glass viewing area is
provided with this appliance and shall be installed for the protection of
children and other at-risk individuals.
1
130139 Rev 1 GF 520 DV 12/22
THIS OWNER’S MANUAL PROVIDES INFORMATION TO ENSURE SAFE INSTALLATION AND EFFICIENT, DEPENDABLE OPERATION. PLEASE READ THESE INSTRUCTIONS IN THEIR ENTIRETY AND MAKE THEM AVAILABLE TO ANYONE USING OR SERVICING THE APPLIANCE. DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THIS APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION WILL VOID THE WARRANTY, CERTIFICATION AND LISTING OF THIS APPLIANCE. THIS APPLIANCE MUST BE INSTALLED AND MAINTAINED BY A QUALIFIED SERVICE TECHNICIAN OR AGENCY.
Suggested Tools for Installation and Service
· External regulator (for Propane only)
· Piping which complies with local code
· Manual shut-off valve –
T-Handle required in Massachusetts
· Sediment trap – if required by code
· Tee joint
· Pipe wrench
· 1/4″ nut driver
· Pipe sealant
· Gloves
· 10 mm open end wrench · Safety glasses
· 1/2″, 7/16″ open end wrench · Torx T-20 screwdriver for
· Phillips head screwdriver
Fuel Conversion
· Flat head screwdriver
PLEASE NOTE: Initial Break-in
It is normal for smoke and odor to occur during the initial stages of
operation, depending upon temperatures generated over time. This “curing”
condition can be alleviated by promoting fresh air circulation within the
immediate vicinity of the appliance. Please see page 23 for further
information.
Operation Sound
Please be aware that cast iron and steel components expand and contract with
temperature fluctuations that are often
accompanied by “creaking” or “pinging” sounds. This is the result of natural
thermal activity. The optional blower fan will also generate a slight hum at
the low setting and progressively increase with the velocity of forced air.
2
Installation Requirements for the Commonwealth of Massachusetts
THIS PRODUCT MUST BE INSTALLED BY A LICENSED MASTER OR JOURNEYMAN PLUMBER OR
GAS-FITTER WHEN INSTALLED IN THE COMMONWEALTH OF MASSACHUSETTS. 1. If there is
not one already present, on each floor
level where there are bedroom(s), a carbon monoxide detector and alarm shall
be placed in the living area outside the bedroom(s). The carbon monoxide
detector shall comply with NFPA 720 (Current Edition). 2. A carbon monoxide
detector shall: a) Be located in the room that houses the appliance or
equipment; b) Be either hard-wired or battery powered or both; and c) Shall
comply with NFPA 720 (Current Edition). 3. A Product-approved vent terminal
must be used, and if applicable, a Product-approved air intake must be used.
Installation shall be in strict compliance with the manufacturer’s
instructions. A copy of the installation instructions must remain with the
appliance or equipment at the completion of the installation. 4. A Manual gas
supply line shut-off valve must be installed.
Natural Gas / 63.49% Propane / 64.61%
Based on CSA P.4.1-15
Jøtul GF 520 DV MV
Natural Gas / 61.47% Propane / 62.15%
Based on CSA P.4.1-15
Jøtul GF 520 DV
Table of Contents
1. Specifications………………………………… 4 2. Initial Assembly …………………………….. 5 3.
General Information……………………… 6 4. Safety Information ……………………….. 6 5.
Installation Requirements………………..7
Floor Protection ……………………………………….. 7 Clearances …………………………………………….. 7-8
6, Vent Requirements ………………………. 9
Vertical Termination………………………………….. 11 Horizontal Termination…………………………. 11-13
7. Fuel Conversion………………………. 14-18 8. Gas Connection …………………………….18 9. Gas
Pressure………………………………….19 10. High Altitude Adjustment …………….19 11. Optional
Equipment …………………….20
Firebox Panel Kits ………………………………….. 20
12. Burner Media Installation
Log Set ……………………………………………………..21
River Rocks …………………………………….. 22
Tumbled Stones ………………………………………..22
Glass …………………………………………….. 22 13. System Check …………………………….. 23 14. Flame
Picture Adjustment …………… 24 15. Operation Guidelines…………………… 25
Manual Operation…………………………………….26
16. Maintenance …………………………………31
Annual Cleaning ……………………………………….31 Glass Care & Replacement ………………………..31
Safety Screen Replacement ……………………. 33 Battery Replacement …………………………….. 34
17. Appendix …………………………………….. 35
Illustrated Parts Lists …………………………..36-39
18. Warranty Statement …………………….44 19 Lighting Instructions …………………….45
! WARNING:
FIRE HAZARD. CAN CAUSE SEVERE INJURY OR DEATH. THE APPLIANCE CAN TURN ON
SUDDENLY. KEEP AWAY FROM THE APPLIANCE BURNER WHEN OPERATING THE REMOTE
SYSTEM.
130139_Rev 1 GF 520 DV 12/22
Jøtul GF 520 DV
Direct Vent Gas Heater
Manufactured and Distributed by: Jøtul North America 55 Hutcherson Dr.
Gorham, Maine 04038
Certified Test Standards
This appliance complies with National Safety standards and is tested and
listed by Intertek Testing Services of Middleton, Wisconsin to ANSI
Z21.88-2019 · CSA 2.33-2019, “Vented Gas Fireplace Heater” and CAN/CGA
2.17-M17.
We recommend that our gas products be installed and serviced by professionals
who are certified in the U.S. by the National Fireplace Institute® (NFI) as
NFI Gas Specialists.
! WARNING:
READ AND UNDERSTAND ALL OPERATING INSTRUCTIONS BEFORE ATTEMPTING TO OPERATE
THIS APPLIANCE. DO NOT ALLOW ANYONE TO OPERATE THIS APPLIANCE WHO HAS NOT READ
AND UNDERSTOOD THESE INSTRUCTIONS. KEEP THE REMOTE CONTROL TRANSMITTER WHERE
CHILDREN CANNOT REACH IT.
! WARNING:
SEVERE INJURY. THIS APPLIANCE CAN BE SET TO OPERATE THERMOSTATICALLY. BE AWARE
THAT THE STOVE MAY BE VERY HOT EVEN WHEN THE BURNER IS NOT APPARENTLY
OPERATING. KEEP CHILDREN AWAY FROM THE APPLIANCE.
3
130139 Rev 1 GF 520 DV 12/22
1. Specifications
Input Rates
Natural Gas 16,500 BTU/hr. minimum input 30,000 BTU/hr. maximum input
Propane 16,500 BTU/hr. minimum input 29,000 BTU/hr. maximum input
Inlet Pressure: Natural Gas:
Propane:
MIN 5.0 WC (1.25 kPa)
12.0 WC (3.0 kPa)
MAX 7.0 WC (1.74 kPa)
14.0 WC (3.48 kPa)
Manifold Pressure: MIN
MAX
Natural Gas:
1.12 WC (.3 kPa) 3.80 WC (.95 kPa)
Propane:
2.9 WC (.72 kPa) 11.0 WC (2.74 kPa)
· Steady State Efficiency: 70.01% NG / 71.72% LP
· CSA P4. 1-15 Fireplace Efficiency:
GF 520 DV
NG – 61.47%
LP – 62.15%
GF 520 DV MV
NG – 63.49% LP – 64.61%
· Factory Air Shutter Open Settings: NG – 1/16″ LP – 1/8″
· On Demand Pilot Mode (DV MV Only)
· Ambient Temperature Range: 32 -122°F (0 – 50°C)
11 5/8″ 165 mm
6 1/2″ 165 mm
17 1/2″ 444 mm
Miscellaneous Hardware Bag Contents · Fuel Conversion Kit , LP ………………………158329
· Rock Wool Embers, 1 oz. ……………………… 157259 · GF 520 DV Manual ……………………………..
130139 · Rear Intake Air Diverter ……………………….226861 · Sheet Metal Screws,
2…………………………….117917
Options & Accessories · Beach Fire Log Set ………………………………158263 · Black
Reflective Panel…………………………..158342 · Fluted Liner………………………………………….158228 ·
Fuel Conversion Kit , LP ………………………158329 · Fuel Conversion Kit, NG – …………………..
158330 · Optional Blower Kit………………………………158333
! SAFETY BARRIER SCREEN The front door and side glass panels of this appliance
are equipped with integrated Certified Safety Barrier Screens which must
remain installed at all times. Should a screen become damaged, contact your
authorized Jøtul dealer for original equipment replacement assemblies.
23 3/8″ 594 mm
19 3/8″ 492 mm
12 1/2″ 318 mm
17 1/2″ 444 mm
39 1/16″ 992 mm
12 1/12″ 318 mm
7 7/8″ 200 mm
39 1/2″ 1003 mm
Figure 1.1 Dimensioned views, GF 520 DV 4
2. Initial Assembly
STOP! FOR EASIEST ACCESS, INSTALL FUEL CONVERSION AND FIREBOX PANELS BEFORE
REMOVING THE STOVE FROM THE PALLET.
Unpacking the Stove
EXCEPT AS NOTED, ALL INSTRUCTIONS ARE ORIENTED FACING THE FRONT OF THE STOVE.
- Open the Firebox
Remove the Top Plate and set aside.
Remove the Front Plate by lifting it up off of the front plate hooks. See fig. 2.1. · Remove the Latch Tool from the shipping pallet and use it to remove the Glass Panel by pulling the two latch hooks out to disengage them from the glass frame. Fig. 2.2. · Tilt the glass frame forward, then lift it straight up and out of the spring glass retainer.
2. Remove the Miscellaneous Hardware kit from the firebox and inspect the contents. Refer to the list on the previous page and contact your dealer if any items are missing.
3. Optional Equipment and Burner Media: See Sections 10 and 11 for specific installation instructions.
130139_Rev 1 GF 520 DV 12/22
The stove is heavy.
! DO NOT DRAG THE STOVE. Have assistance available to move the stove into
position. Place removed parts on a blanket, towel, or other protective
material.
Figure 2.1 Remove Front Plate.
Figure 2.2 Disengage the glass frame latches to open the firebox.
RE-INSTALL THE TOP PLATE BEFORE CONNECTING VENT PIPE TO THE STOVE.
5
130139 Rev 1 GF 520 DV 12/22
3. General Information
THIS HEATER MUST BE INSTALLED AND
MAINTAINED BY A QUALIFIED SERVICE AGENCY.
The installation and repair of this appliance must be done
by a qualified service person. Failure to properly install and maintain this
heater could result in an unsafe or hazardous installation, which may result
in a fire, explosion, property damage, personal injury or loss of life.
This appliance should be inspected before use and at least
annually. More frequent cleaning may be required due to excessive lint from
carpeting, bedding material, etc. It is imperative that control compartments,
burners, and circulating air passageways of the appliance be kept clean. See
Maintenance section for details.
THIS APPLIANCE MUST NOT BE CONNECTED
TO A CHIMNEY OR FLUE SERVING ANY OTHER APPLIANCE.
The installation must conform to local codes. Your local
Jøtul dealer can assist you in determining what is required in your area for a
safe and legal installation. Some areas require a permit to install a gas
burning appliance. Always consult your local building inspector, or authority
having jurisdiction, to determine what regulations apply in your area.
CODE COMPLIANCE : Your local officials have final
authority in determining if a proposed installation is acceptable. Any
requirement that is requested by the local authority having jurisdiction, that
is not specifically addressed in this manual, defaults to local code. In the
absence of local codes, the installation requirements must comply with the
current edition of National codes. In the U.S., these requirements are
established in the National Fuel Code, ANSI Z223.1.(NFPA 54) current edition.
In Canada, the codes have been established in CAN/CGA B149 Fuel Installation
Code, current edition.
The appliance, when installed, must be electrically
grounded in accordance with local codes or, in absence of local codes, with
the National Electrical Code, ANSI/ NFPA 70, or the Canadian Electrical Code,
CAN/CSA C22.1.
CAUTION: Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation.
Verify operation after servicing.
DO NOT OPERATE THIS STOVE IF ANY PART HAS
BEEN UNDER WATER. Call a qualified service technician to inspect the heater
and to replace any part of the control system and any gas control which may
have been under water.
4. Safety Information
Due to the high operating temperatures this appliance should be located out of
traffic and away from furniture and draperies. Maintain proper clearance to
combustible mantels and fireplace trim.
Children and adults should be alerted to the hazards of high surface
temperatures and should stay away to avoid burns or clothing ignition.
Young children should be supervised while they are in the same room as the
appliance. Toddlers, young children and others may be susceptible to
accidental contact burns. A physical barrier, such as a child guard, is
recommended to be used if there are at-risk individuals in the house. To
restrict access to a fireplace or stove, install an adjustable safety gate to
keep toddlers, young children and other at-risk individuals out of the room
and away from hot surfaces.
This appliance includes permanent, integrated safety barriers
designed to reduce the risk of burns from the hot viewing glass. These
barriers shall remain installed for the protection of children and other at-
risk individuals.
The appliance must not be operated with the front door open or ajar.
A damaged screen barrier must be replaced only with Jøtul GF
520 Front Replacement Screen 226647, or Side Replacement Screen 226648,
available from any Jøtul Authorized Dealer.
Any safety screen, guard, or barrier removed for servicing an
appliance must be replaced prior to operating the appliance. See maintenance
instructions.
Clothing or other flammable materials should not be placed on
or near the fireplace.
Never allow anyone to use the fireplace if they are unfamiliar with its
operation.
NEVER store or use gasoline or any other flammable vapors or liquids in the
vicinity of this appliance.
Never burn any solid materials (wood, cardboard, paper, coal, etc.) in this
appliance. Use with natural gas or propane fuel ONLY.
Do not slam or strike the glass panel.
This appliance is NOT for use with aftermarket glass doors.
Wear gloves and safety glasses while installing or performing maintenance
procedures on this appliance.
6
130139_Rev 1 GF 520 DV 12/22
5. Installation Requirements
Location
In selecting a location for the stove, consider the following points: 1) Heat
distribution 2) Vent termination requirements 3) Gas supply line routing 4)
Traffic areas, furniture, draperies, etc.
The stove may be located on or near conventional construction materials,
however, proper clearance to combustibles must be maintained in order to
provide adequate air circulation around the appliance. Also, it is important
to provide adequate access around the stove for servicing and operation.
The clearance and hearth specifications listed in this manual are the minimum
requirements for combustible material. A combustible material is anything that
can burn (i.e. sheet rock, wall paper, wood, fabrics etc.). These surfaces are
not limited to those that are visible and also include materials that may be
located behind non-combustibles.
If you are not sure of the combustible nature of a material, consult your
local fire officials. Remember, “Fire Resistant” materials are considered
combustible: they are difficult to ignite, but will burn. Also, “fire-rated”
sheet rock is considered combustible.
Stove and Vent Clearance Requirements
Minimum Clearances from the Stove to Combustibles:
Rear: Ceiling: Corner: Side:
Measured from: 1 1/2″ (38 mm) Rear Shroud 21″ (534 mm) Top Plate 3 3/8″ (86 mm) Side Plate 10″ (254 mm) Side Plate
Minimum Clearances between Vent Pipe and Combustible Materials:
Horizontal Run:
Off the top of the pipe
2″ (51 mm)
Off the sides and bottom
1″ (25 mm)
Vertical Run: All sides
1″ (25 mm)
Floor Protection
The Jøtul GF 520 DV has been approved for installation directly on combustible
floor materials. No additional floor protection is required, however, we
recommend that the stove be installed on a non-compressible, solid surface.
38″
5 5/8″ 143 mm
965 mm
10″ 254 mm
16-5/8″ 422 mm
16″ 406 mm
WARNING:
!
INSTALLING THIS STOVE ON A COMPRESSIBLE SURFACE SUCH
AS A THICK CARPET OR FOAM
FLOOR MAT WILL CAUSE THE STOVE
TO SETTLE AFTER INSTALLATION WHICH MAY
CREATE LEAKS IN THE VENTING SYSTEM!
24″ 610 mm
Figure 5.1. Corner Wall clearances.
7
130139 Rev 1 GF 520 DV 12/22
Alcove Installation
Maximum Alcove Depth:
24″ (607 mm)
Minimum Alcove Width*:
44″ (1118 mm)
Minimum Alcove Ceiling Height
from floor:
82″ (2802 mm)
- Alcove clearances are determined through testing in specific construction configurations which often result in greater clearances than an open stove installation.
Clearance to Combustible Materials Above Stove
Minimum Mantle Height from floor: 59 7/8″ (1521 mm) with 24″ (610 mm) maximum
mantle depth.
7 15/16″ 202 mm
22″ 559 mm 10″ 254 mm
Figure 5.2 Alcove Clearances.
44″ 1117 mm
1 1/2″ 38 mm
24″ 607 mm 10″ 254 mm
Distance to Gas Supply
Suggested gas supply location is within 12″ of the rear of the center line of
the stove.
Distance to Electrical Supply
A grounded permanent electrical supply should be installed within 6 ft. of the
center line of the exhaust pipe.
24″ 610 mm
82″ 2083 mm
21″ 533 mm
59 7/8″ 1521 mm
38 7/8″ 987 mm
1 1/2″ 38 mm
Figure 5.3. Mantel and Ceiling Clearances.
8
Mobile Home Installation
The GF 520 DV is approved for installation in a mobile home in the U.S. and
Canada with the following requirements:
The stove must be secured to the floor of the mobile home.
Provision must be made to secure an electrical ground
between the stove and the mobile home chassis.
The stove must be installed in accordance with Title 24 CFR,
Part 3280-Manufactured Home Construction and Safety Standard in the U.S.
In Canada, comply with CSA Z240.4, Gas Equipped Recreational Vehicles and
Mobile Housing.
Always contact your local officials about installation
restrictions and requirements in your area.
130139_Rev 1 GF 520 DV 12/22
THIS APPLIANCE MAY BE INSTALLED AS AN OEM INSTALLATION IN A MANUFACTURED
(MOBILE) HOME AND MUST BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’S
INSTRUCTIONS AND THE MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARD, TITLE
24 CFR, PART 3280. THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE OF GAS THAT IS
INDICATED ON THE STOVE’S RATING PLATE. A GAS CONVERSION KIT IS PROVIDED WITH
THE GF 520 DV GAS STOVE.
THIS APPLIANCE MAY BE INSTALLED IN AN AFTERMARKET PERMANENTLY LOCATED,
MANUFACTURED (MOBILE) HOME, WHERE NOT PROHIBITED BY LOCAL CODES.
Procedure
1. Using the two #12 x 3 1/2″ screws used to secure the stove to the shipping
pallet, secure the GF 520 DV to the floor of your mobile home through the two
holes at the bottom of the base of the stove. If needed, longer hardware can
be used.
Shipping/Mobile Home Screws
Figure 5.4 Mobile Home Installation
Figure 5.5 Mobile Home Installation
9
130139 Rev 1 GF 520 DV 12/22
6. Venting Requirements
The Jøtul GF 520 DV gas stove may be installed with a vertical or horizontal
termination and must conform to the configuration requirements described
below.
This appliance is approved for use with vent systems from the following
manufacturers: · DuraVent DirectVent Pro and GS Series · American Metal
Products (Amerivent) · Security Chimneys International, Ltd. (Secure Vent) ·
Selkirk Metalbestos (Direct Temp) · Metal-Fab, Inc. (Sure-Seal Direct Vent) ·
Industrial Chimney Corp. (ExcelDirect) · Bernard Dalsin Mfg. (Pro Form) ·
Olympia Chimney Supply, Inc. (Ventis Direct Vent)
Use parts of one manufacturer only – DO NOT MIX VENT COMPONENTS FROM DIFFERENT
MANUFACTURERS IN THE SAME SYSTEM.
Installation of any components not manufactured or approved by Jøtul or
failure to meet all clearance requirements will void all warranties and could
result in property damage, bodily injury, or serious fire.
The approved vent configurations described in this manual are derived from
extensive testing under controlled laboratory conditions. Gas appliance
performance can be negatively affected by variables present in the
installation environment, i.e: atmospheric pressure, strong prevailing winds,
adjacent structures and trees, snow accumulation, etc. These conditions should
be taken into consideration by the installer and stove owner when planning the
vent system design.
IMPORTANT
· JOINT SEALING REQUIREMENT: APPLY A 1/8″ BEAD OF HIGH-TEMPERATURE SEALANT OR
MIL-PAC® TO THE MALE SECTION OF THE INNER VENT PIPE. THE CEMENT SHOULD FORM A
SEAL BETWEEN THE INNER AND OUTER PIPES.
· NEVER MODIFY ANY VENTING COMPONENT, OR USE ANY DAMAGED VENTING PRODUCT.
· THE GAS APPLIANCE AND VENT SYSTEM MUST BE VENTED DIRECTLY TO THE OUTSIDE OF
THE BUILDING AND NEVER ATTACHED TO A CHIMNEY SERVING A SOLID FUEL OR GAS
BURNING APPLIANCE. EACH DIRECT VENT GAS APPLIANCE MUST HAVE ITS OWN SEPARATE
VENT SYSTEM. COMMON VENT SYSTEMS ARE PROHIBITED.
· IF THE VENTING SYSTEM IS DISASSEMBLED FOR MAINTENANCE OR ANY OTHER REASON,
IT MUST BE PROPERLY REASSEMBLED AND RESEALED IN ACCORDANCE WITH THE ORIGINAL
VENT MANUFACTURER’S INSTRUCTIONS.
CONFIRM THAT ALL INTERLOCKING JOINTS ARE TIGHTLY RE-SECURED AND THAT ALL SEALS
ARE MAINTAINED INTACT. REINSTALL ANY FASTENERS AND REPLACE AS NECESSARY.
Figure 6.1. DO NOT USE SILICONE SEALANT.
SEALANT
RE-INSTALL THE TOP PLATE BEFORE CONNECTING VENT TO THE STOVE.
Vent Restriction
The GF 520 DV is equipped with an Exhaust Restrictor Plate which enables
regulation of the exhaust gas flow. The plate prevents overly-strong draft
that can cause poor combustion and weak flame picture. Follow the guidelines
below and on the following pages to determine the correct restrictor plate
setting for your particular installation.
Exhaust Restrictor
The Exhaust Restrictor plate is located on the rear of the firebox. It is
adjusted by rotating the dial on the back shroud within a range beginning at
the factory-set, fully open position (no restriction) to a fully restricted
position. See Figs. 6.2 and 6.3. The Minus (-) and Plus (+) signs on the dial
relate to degrees of restriction, from zero to approximately 70%. The three,
lettered positions correlate to the termination zones (A,B,C) diagramed in
figure 6.2. Use the diagram to determine the degree of restriction and shutter
setting that correlates to your vent configuration.
Adjusting Exhaust Restrictor Plate: 1. Use a 1/4″ nut driver to loosen the
screw and then use the
pivot tab to set the dial to the position appropriate to your termination
zone. See figs. 6.2-6.4, page 11. 2. Re-tighten the screw after adjustment.
10
Approved Horizontal and Vertical Vent Terminations
· ALL VENTING MUST TERMINATE (END) WITHIN ONE OF THE DESIGNATED AREAS.
· SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT CORRESPONDS TO THE VENT
TERMINATION AREA IN THE MATRIX. When termination is exactly on a division
line, use the less restrictive position. For example, if termination is 10
feet high and offset 7 feet, restriction should be set at Position B.
· Up to two 45° elbows or one additional 90° elbow is permitted in addition to
the first elbow, however, a 5 foot reduction in horizontal length must be made
for each additional elbow whether 45° or 90°.
VERTICAL RISE
30 ft. (9.14 m)
10 ft. (3.05 m)
7 ft. (2.13 m)
130139_Rev 1 GF 520 DV 12/22
TERMINATION NOT
APPROVED
3 ft. (0.91 m)
2 ft. (0.61 m)
TERMINATION NOT
APPROVED
6″ (152mm) min. horz. run
3 ft. (0.91 m)
7 ft. (2.13 m)
12 ft. (3.66 m)
HORIZONTAL RUN
Figure 6.2. Vent Termination Restriction Zones – NG / LP. See also Snorkel
Termination vent run restrictions, pg. 12.
20 ft. (6.10 m)
Top Plate
Rear Heat Shield
Figure 6.3. Use a 1/4″ nut driver to loosen the Restrictor screw.
C
B A
Figure 6.4. Determine the dial notch position appropriate to your vent
configuration as designated in Fig 6.2. Pivot the dial to align the screw with
that notch.
11
130139 Rev 1 GF 520 DV 12/22
Vertical Vent Termination
This appliance may be vertically vented through a ceiling or to a roof
termination using the following guidelines:
The termination should fall within the shaded areas of the
grids depicted in the Vent Matrix, fig. 6.2, page 11.
Maximum Horizontal run is 20 ft. (152 cm) See Fig. 6.2 for
related termination zone limitations.
Minimum Vertical Termination is 6 ft. (183 cm).
Total run, including offsets, must not exceed 30 ft. (9.14m).
Vent Terminus Clearance: In no case shall any discharge
opening on the cap be less than 18 in. (457 mm) horizontally from the roof
surface. See fig. 6.6.
Steep roofs, nearby trees, and predominantly windy
conditions can contribute to poor draft and/or promote draft reversal.
Increasing the height of the vent may alleviate these conditions.
Use Wall Straps to support an offset pipe run at intervals of
three feet to avoid excessive stress on the offsets.
A firestop is required at every floor. The floor opening
should be framed to 10″ X 10″ inside dimension.
Any venting that is exposed in living space above the first
floor must be enclosed. Always maintain the required 1″ clearance from all
sides of the vertical vent system. Insulation in attic space must be retained
by an insulation barrier.
Allowable minimum vent run is 1′ vertical with 6″ horizontal.
Sheet Metal Screw
Air Intake Diverter
Figure 6.5. Install the Air Intake Diverter. NOTE: Install with the bends facing DOWN.
Air Intake Diverter
The GF 520 DV comes with an Air Intake Diverter in the miscellaneous kit. This
is to be installed in installations with a vertical installation greater than
10 ft, in installations with excessive draft conditions, or when the flame
picture shows a flame with weak rear flame and a large front flame.
Installation Instructions:
Using a 1/4″ driver, use the two sheet metal screws provided in the misc. kit
to secure the Air Diverter to the Rear Burner Skirt. Install the Air Diverter
with the bends facing downward. See fig. 6.5.
Horizontal Overhang
Vertical Wall
min.
min.
Termination Cap
18 min.
Lowest Discharge Opening
Figure 6.6. Vertical vent termination height above roof.
12
130139_Rev 1 GF 520 DV 12/22
Any horizontal run of vent must be level or have a
1/4 in. rise for every foot of run toward the termination cap. NEVER ALLOW THE
VENTING TO RUN DOWNWARD FROM STOVE TO TERMINATION; A DOWNWARD VENT RUN TRAPS
HEAT AND CREATES A FIRE HAZARD.
The horizontal termination cap must maintain a 3″ clearance
to any overhead combustible projections 2 1/2″ or less. It must also maintain
12″ clearance from projections exceeding 2 1/2″.
A direct vent terminal may not be recessed into a wall or
siding.
Install a Vinyl Siding Standoff (Dura-Vent #950) between
the vent termination and an exterior wall covered by vinyl siding material to
prevent potential heat damage to the siding.
Figure 6.6. Co-linear Termination is permitted with 2 foot (62 cm) maximum
horizontal run (A).
RE-INSTALL THE TOP PLATE BEFORE CONNECTING VENT TO THE STOVE.
Horizontal Termination
Any horizontal termination must fall within the shaded
portion of the vent window matrix shown in fig. 6.2.
Any horizontally-terminated vent run must include a
minimum 12″ (61 cm) vertical rise with a minimum 6″ horizontal run. See figs.
6.8, 6.9, 6.10.
Horizontal termination requirements:
- Maximum vertical run is 30 ft. (9.14m) 2) Maximum horizontal run is 20 ft.
(6.1 m)
ELBOW RESTRICTION: Up to two 45° elbows or one 90°
elbow may be used in addition to the first elbow.
The horizontal run must be reduced by 5 feet for each
additional elbow, whether 45° or 90°.
Wall Cut-out Opening: A minimum 10″ X 10″ (250 mm x
250 mm) square hole is required for proper pipe clearances through a combustible wall.
Horizontal Vent Pipe Clearance to Combustible Material:
From Top Surface: 2″ (51 mm) From Sides: 1″ (25 mm)
DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULATION.
70.25″ 1784 mm
39″ 991 mm
Figure 6.8. Recommended Horizontal Termination.
1.5″ 38 mm
67″ 1702 mm
13
130139 Rev 1 GF 520 DV 12/22
SNORKEL TERMINATION:
· HORIZONTAL RUN MUST NOT EXCEED 2 FEET (61 CM). A 14″ (356mm) or 36″ (914mm)
snorkel termination is approved in conformance with the vent rise/run and
termination clearance specifications published in this manual. See figs. 6.9
6.10. The snorkel termination must comply with grade and building clearance
requirements per local and national building codes.
2″ 51 mm
Max 18″ Length
Min 12″ Length
58″ 1473 mm
39″ 991 mm
1.5″ 38 mm
55″ 1397 mm
69″ 1753 mm
Max 24″ 610 mm Length
36″ 914 mm Snorkel
1.5″ 38 mm
80.5″ 2045 mm
44.5″ 1130 mm
Figure 6.9. Optional Snorkel Termination
Any horizontally terminated vent run must include a minimum 1 ft. (61 cm)
vertical rise.
At minimum vertical run, the total horizontal run (A) must not exceed 5 ft.
(152.4 cm).
Figure 6.10. Minimal Pipe Exposure Clearances. 2 FT. MAX. HORIZONTAL RUN (A)
TO SNORKEL TERMINATION
36″ Snorkel
5.75″ 146mm 16.75″
24″ Vertical Pipe and 90 Degree Elbow
425 mm 23.5″ 597 mm
Th6i”cWknaellss 18″ Pipe Length
12″ Pipe Length
6″ 152 mm
5.75″ 146 mm
90 Degree Elbow to Unit
7″ 178 mm 3.75″ 95 mm
45EDlbeogwree
Figure 6.11. Optional Corner Installation Clearances
14
6″ Pipe Length
16.75″ 425 mm Center Pipe
Horizontal Termination Clearance Requirements
130139_Rev 1 GF 520 DV 12/22
2 1/2 12 64 mm 305 mm 3
76 mm
N
V Vent Terminal
X Air Supply
Terminals Prohibited in this Area
Figure 6.11. Vent Terminal Clearances, Canada and United States
Figure 6.11. Termination Clearance to overhangs.
A
Clearance above grade, veranda, porch, deck, or balcony
B Clearance to window or door that may be opened
Canadian Installations 1 12 in. (30 cm) 12 in. (30 cm)
C Clearance to permanently closed window
Vertical clearance to ventilated soffit located D above the terminal within a
horizontal distance of
2 ft. (60 cm) from the center line of the terminal E Clearance to unventilated
soffit
F Clearance to outside corner
12 in. (30 cm)
18 in. (46 cm) 12 in. (46 cm) 12 in. (46 cm)
G Clearance to inside corner
12 in. (46 cm)
H
Clearance to each side of center line extended above a gas meter or regulator
I Clearance to service regulator vent outlet
Clearance to nonmechanical air supply inlet to J building or the combustion
air inlet to any other
appliance
3 ft. (91 cm) within a height 15 ft. above the meter/regulator assembly
3 ft. (91 cm)
12 in. (30 cm)
K Clearance to a mechanical air supply inlet
6 ft. (1.83 m)
L
Clearance above paved sidewalk or paved driveway located on public property
M Clearance under veranda, porch, deck, or balcony
N
Clearance to propane tank relief valve and filler connection
7 ft. (2.13 m) 3 12 in. (30 cm) 4 5 ft. (1.52 m) 5 / 10 ft. (3.05 m) 6
U.S. Installations 2 12 in. (30 cm)
9 in. (23 cm) We recommend 12 in. to prevent condensation on a window. 9 in.
(23 cm) We recommend 12 in. to prevent condensation on a window.
18 in. (46 cm)
12 in. (46 cm) 9 in. (23 cm) We strongly recommend 12 in. particularly where
strong winds prevail. 9 in. (23 cm) We strongly recommend 12 in. particularly
where strong winds prevail.
-
- 9 in. (23 cm)
3 ft. (91) cm above if within 10 ft. (3 m) horizontally
- 9 in. (23 cm)
-
12 in. (30 cm) 4 5 ft. (1.52 m) 5 / 10 ft. (3.05 m) 6
- In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
- In accordance with ANSI Z223.1/NFPA 54, National Fuel Gas Code
- For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, the
clearance will be in accordance with local installation codes and the requirements of the gas supplier.
- A vent shall not terminate directly above a sidewalk or driveway which is located between two single family dwellings and serves both dwellings.
- Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
- Minimum clearance to tanks not filled on site.
- Minimum clearance to tanks filled on site from bulk truck.
15
130139 Rev 1 GF 520 DV 12/22
7. Fuel Conversion
The GF 520 DV gas stove is shipped from the factory equipped to burn NATURAL
GAS only. If PROPANE gas is to be used as fuel, the appliance must first be
converted by using the Propane Conversion Kit 158331 included with the stove.
Use Natural Gas Conversion Kit 158332 to revert back to Natural gas.
WARNING: THE CONVERSION KIT IS TO BE INSTALLED BY AN AUTHORIZED SERVICE
TECHNICIAN IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTION AND ALL CODES AND
REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN SERIOUS INJURY OR PROPERTY DAMAGE. THE QUALIFIED
AGENCY PERFORMING THIS WORK ASSUMES RESPONSIBILITY FOR THIS CONVERSION.
IN CANADA: THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE
REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN
ACCORDANCE WITH THE REQUIREMENTS OF THE CAN1-B149.1 AND .2 INSTALLATION CODE.
Fuel Conversion Procedure
1. Turn off gas supply to stove.
2. Remove top and front cast. Release the glass frame latches to remove the
glass frame and open the firebox. Tilt the glass frame forward and lift it out
of the stove. See initial assembly page 5.
3. Open the Controls Compartment under the firebox. If opening the Controls
Compartment for the first time, loosen the Air Shutter wing nut located below
the firebox floor and rotate the handle 180°. Push the Air Shutter handle as
far back as it will travel. See fig. 7.1.
4. Lift out Rear Burner Skirt.
5. Remove the Burner: Lift the front of the burner base to disengage it from
the support brackets and pull it forward off of the burner injector. Then tilt
it side-to-side and pull it out through the firebox opening. Fig. 7.2.
5. Change the Burner Injector. See fig. 7.3. Using a 1/2″ open end wrench or
deep-well socket, remove the burner injector from the orifice holder and
replace it with the injector supplied in the conversion kit.
CAUTION: DO NOT OVER TIGHTEN!
Tools required: · 1/2″ or 13 mm wrench or deep-well socket, · Torx T20 screw
driver
Conversion Kit Contents: · 1, regulator tower labeled LP · 2 regulator tower
Torx Screws · LP orifice: #52 · 1, Pilot Injector – BL .020 for NG – 226758
.013 for LPG – 226759 · Label A – to be completed and applied to
the lower door hinge. · Label B – apply to the stove’s Rating Plate · Small
valve label – apply to valve body · Instructions
Figure 7.1. Rotate the Air Shutter Handle 180° and push Air Shutter FULLY back to disengage burner from injector.
Figure 7.2. Remove Burner. 16
Replace Burner Injector
Figure 7.3. Injector and Pilot conversion. The Air Shutter MUST be flipped for
LP conversion.
Pilot Hood
Replace Pilot Injector
130139_Rev 1 GF 520 DV 12/22
Figure 7.3. Injector and Pilot conversion. The Air Shutter MUST be flipped for
LP conversion.
17
130139 Rev 1 GF 520 DV 12/22
Fuel Conversion, cont’d.
6. Change the Pilot Injector, Fig 7.3. · Use the 7/16″ wrench to loosen the
pilot hood, hold the pilot mounting bracket with pliers to prevent bending the
pilot bracket.
· Lift the Pilot Hood and remove the pilot injector and replace with one in
fuel conversion kit. Replace the pilot head and orient the hood to project
flame to the Flame Sensor and burner carry-over ports. Be sure to orient the
hood to project flame to the Flame Sensor and the burner carry-over ports.
7. Flip the Air Shutter. Carefully bend open the Air Shutter Handle and flip
the Air Shutter so it displays “LP”. Carefully bend the Air Shutter Handle
back around the Air Shutter. See fig 7.3
8. Replace the Burner. Tilt the burner assembly downward to engage the
venturi tube with air shutter assembly. BE CERTAIN THE BURNER IS LEVEL AND
SECURELY ENGAGED WITH THE FRONT SUPPORTS ON THE FIREBOX FLOOR.
ApLpalbyeSl mHaelrle
Remove black rubber gasket
Variable regulator tower
Figure 7.7. Regulator tower removal and replacement
Figure 7.4. GF 520 DV Control Compartment. Image shown with optional blower.
18
130139_Rev 1 GF 520 DV 12/22
9. Replace the variable regulator. Using a Torx T-20 screwdriver, remove the
three specialty screws from the regulator tower on the front of the valve.
Note: To help identify which screws to remove, refer to the new regulator in
the kit. See fig. 7.7.
10. Remove the regulator tower and the rubber diaphragm.
11. Install the new variable regulator tower from the kit. Be sure that the
gasket is properly positioned and tighten screws securely.
12 . Apply the identification labels to the stove so that they can be seen by
any person that may be servicing the stove.
· Label “A”: Apply Control Compartment Door, next to the lighting
instructions.
· Label “B”: Apply to the Rating Plate.
· Small valve sticker: Apply to valve.
11. Reassemble the stove and apply gas to the system.
12. Leak Check: Check for leaks using a soapy water solution or digital gas
detector.
NEVER USE OPEN FLAME TO CHECK FOR GAS LEAKS. AVOID WETTING THE IFC UNIT OR
MOTORIZED REGULATOR WHEN CONDUCTING LEAK CHECK.
13. Confirm correct gas pressure. Use a manometer to check pressures as
specified under Section 9, Gas Pressure (page 20).
14. Adjust the Air Shutter. Fig. 7. 7 The factory setting for NG is 1/16″
open. Adjustment may be necessary to provide the best flame picture depending
upon the specific vent configuration.
· Start with the shutter set open to 1/16″.
· Push the shutter stem back (to the rear) to restrict air.
· Pull the shutter stem forward (toward yourself) to open the shutter and add
oxygen to the fuel mix.
With some experimentation, you will find the shutter position that works best
for that particular installation.
· Run the stove at least 15 minutes to let the burner settle-in before making
further adjustments in very small increments (1/16″ – 1/8″)
Apply Small Conversion Label
to valve
Apply Label “A” to Controls Compartment Door
OPEN CLOSED
Figure 7.7. Air shutter adjustment.
Figure 7.6. Conversion label “A” location.
19
130139 Rev 1 GF 520 DV 12/22
8. Gas Supply Connection
Route the gas supply line to the flex line behind the unit.
Gas installation should be approximately 12″ from the center line on either
side of the unit.
The gas supply line should be 3/8″ npt with a 1/2″ diameter
supply, or the appropriate size to provide sufficient gas pressure to the
valve regardless of the input setting.
The use of Flexible Gas Appliance Connectors is
acceptable in many areas in the U.S. However, Canadian methods vary depending
on local code.
ALL INSTALLATIONS MUST COMPLY WITH LOCAL
CODE OR IN THE ABSENCE OF LOCAL CODE, MUST COMPLY WITH THE MOST RECENT EDITION
OF THE NATIONAL FUEL GAS CODE ANSI Z223.1/ NFPA 54 OR CAN-B149.
All codes require a gas shut-off valve (gas cock) and union,
to be installed in the supply line, and in the same room as the appliance.
This allows for the disconnection of the stove for servicing and maintenance.
See fig. 8.1.
A T-HANDLE GAS COCK IS REQUIRED IN MASSACHUSETTS TO COMPLY WITH CODE 248CMR.
Secure all joints tightly using appropriate tools and sealing
compounds. For propane units be sure to use compounds that are propane
resistant. Turn on gas supply and test for gas leaks at all joints.
1/2 x 3/8 Flare Shut-off Valve
3/8 NPT x 3/8 Flare Fitting
3/8 Flex Tubing
3/8Nipple
Gas Stub
1/2 x 3/8 Reducer
3/8 Union 3/8 Close Nipple 3/8 Shut-off Valve
Figure 8.1. Gas supply line connection alternatives.
9. Gas Pressure
Correct gas pressure is essential for efficient and safe operation of the GF
520 DV gas stove. It is important that the correct pressure is established at
the time of the installation. Proper gas pressure provides a consistent flow
of gas to the appliance and is instrumental in checking for gas leaks.
Pressure Test: Attach a manometer to the appropriate test point on the valve.
See fig. 9.1.
The gauge connections are located on the front of the valve. Connections are
identified by:
A – for Manifold Pressure (the amount of gas that is coming out of the valve
to the burner.)
B – for Inlet or Supply Pressure (the amount of gas coming to the valve.)
ALWAYS TEST PRESSURES WITH VALVE CONTROL KNOB SET ON HIGH.
BA Figure 9.1. Pressure test points.
INLET GAS PRESSURES (inches water column)
MIN MAX
NATURAL GAS 5.0 7.0
PROPANE
11.0 14.0
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing on that system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply line by closing its
individual manual gas shut-off valve (gas cock) during any pressure testing of
the gas supply piping
system that is equal to or less than 1/2 psig (3.5 kPa).
MANIFOLD PRESSURES (inches water column) MIN MAX
NATURAL GAS 1.6 3.5
PROPANE
6.4 10.0
20
10. Accessories
Firebox Panel Kit
Black Reflective Glass Panel Kit 158342
Reflective Black Glass Contents: · Rear Panel ……………….226763
· Cotton Gloves, 2 · Instructions
Tools: · Flat head screw driver
·1/4″ hex socket
INSTALL FUEL CONVERSION KIT BEFORE INSTALLING PANEL KIT.
THE PANEL IS FRAGILE. SUPPORT WITH BOTH HANDS.
HANDLE THE GLASS PANELS WITH THE COTTON GLOVES PROVIDED TO MINIMIZE
FINGERPRINTS. SKIN OILS ARE DIFFICULT TO REMOVE FROM THE
GLASS SURFACE.
130139_Rev 1 GF 520 DV 12/22
ORIENT GLASS PANEL WITH THE SMOOTH SIDE FACING OUT.
1. Set the Rear Panel, bottom first, behind the pilot assembly shield and
resting on the rear shelf. See fig. 10.1.
2. Use a flat head screwdriver to bend the rear tab at 45° to keep glass from
falling forward. See fig. 10.2.
3. Repeat the process for the tab on the opposite side.
NOTE: If the Glass Panel is installed in a location prone to vibration, the
retainer tab can be adjusted to hold the glass tighter.
1. Remove the Baffle by removing the two M6 nuts in the upper front corners
of the firebox.
2. Use a 1/4″ hex socket to loosen the screw on one of the retaining tabs.
Rotate the tab until it is holding the glass panel tight to the firebox and
tighten the screw.
3. Replace the Baffle.
Retainer Tab
Figure 10.1. Install Rear Panel.
Figure 10.2. Bend Side Tabs 21
130139 Rev 1 GF 520 DV 12/22
Firebox Panel Kit
Fluted Panel Kit 158288
Fluted Panel Kit Contents: · Rear Panel ……………… 226943 · Instructions
Tools: · Flat head screw driver
INSTALL FUEL CONVERSION KIT BEFORE INSTALLING PANEL KIT.
1. Use the screwdriver to bend out the front tab of the retainer clips on
each side slightly, only enough to allow the screwdriver access from the
front. See fig. 10.3.
2. Install the bottom of the panel first, then stand the panel against the
rear wall of the firebox. See fig. 10.4.
3. Insert the screwdriver underneath the tab previously bent and twist to
bend the tab against the panel. Repeat this step on the other side and bend
the tabs equally so the panel is centered and retained in the firebox. See fig
10.5.
Figure 10.4. Install Panel.
Retainer Tab
Figure 10.3. Bend the front tab on each side slightly. 22
Figure 10.5. Bend both tabs fully to retain Panel.
Optional Wall Thermostat 750003
Use only a 750 millivolt DC two-wire circuit wall thermostat with this
appliance. The thermostat should be placed in the same room as the heater,
typically 5 feet off the floor. Avoid drafty areas or any area that may affect
the accuracy of the thermostat.
The thermostat should be connected to the terminal block using a minimum of 16
gauge wire with a maximum length of 25 feet of wire.
Connect either of the two thermostat wire leads to either of two terminals on
the terminal block located to the right of the main gas valve. Do not
overtighten the connections. IT IS NOT NECESSARY TO DISCONNECT ANY OTHER
WIRES. See Fig. 10.7.
For thermostatic operation, the On/Off/T-Stat switch on the back of the stove
must be in the T-stat position, and the pilot light must be running, as it is
the power source for the thermostat.
At the thermostat, the two wires should be connected to the two connection
screws on the thermostat base plate per the manufacturer’s instructions.
130139_Rev 1 GF 520 DV 12/22
Optional Remote Control 224910
When using a remote, the remote receiver should be wired to the terminal block
in the same way the as the thermostat. See the instructions under Optional
Wall Thermostat. The remote receiver can be places on the bottom right of the
Control Compartment.
Follow the operating instructions included with the Remote Control unit.
CAUTION:
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING THE CONTROLS. WIRING
ERRORS CAN CAUSE IMPROPER OR DANGEROUS OPERATION. ALWAYS VERIFY PROPER
OPERATION AFTER SERVICING THE APPLIANCE.
Figure 10.6. Remote Receiver Location. Shown with optional blower.
TH
TP TH TP VALVE
THERMOPILE
TERMINAL BLOCK
ROCKER SWITCH
ON
OFF
STAT
OPTIONAL THERMOSTAT
or REMOTE CONTROL
Figure 10.7. Accessory wiring diagram.
23
130139 Rev 1 GF 520 DV 12/22
Optional Blower 158333
Kit Contents:
· Left Blower Assembly · Snapstat
· Right Blower Assembly · Snapstat Bracket
· Wiring Harness
· Snapstat Finger Guard Assembly
· Flange Nuts (6)
· Green Grounding Strap
· Sheet Metal Screws (3)
Tools Required: · 10mm socket and ratchet · 1/4″ driver · Light · Gloves
Read these instructions before beginning the installation.
1. Unpack and check the contents of the blower kit. Contact your dealer if
any damage is evident or parts are missing.
2. Identify the Right Blower Assembly. The Right Blower Assembly has the air
hole cutout on one side.
3. Attach the pink connectors from the Green Gounding Strap to the prong at
the bottom of the blower as shown in fig. 10.8.
4. With the arrows on the blower facing up and out, rotate the blower behind
the burner gas line and mount to the studs on the factory installed blower
brackets.
· Do not connect blower to power supply until all
wire connections have been made.
· This blower must be electrically grounded in
accordance with local codes or, in the absence of local codes, with the
current ANSI/NFPA 70, National Electrical Code or CSA C22.1Canadian Electrical
Code.
· This unit is supplied with a three-prong
(grounding) plug for protection against shock hazard and should be plugged
directly into a properly grounded three-prong receptacle. DO NOT CUT OR REMOVE
THE GROUNDING PRONG FROM THE PLUG.
· Always disconnect the power supply when
performing any service on the stove.
Figure 10.8. Grounding Strap connection point. Figure 10.9. Install the right side blower.
Figure 10.10. Rotate the Left side blower to fit behind the burner gas line.
24
130139_Rev 1 GF 520 DV 12/22
5. Attach the Blower to the brackets using two M6 flange nuts as shown in fig
10.9.
6. Identify the Left Blower Assembly. The Left Blower assembly has a solid
plate on the front.
7. Attach the yellow connector from the Green Grounding Strap to the prong at
the bottom of the Right Blower Assembly.
8. With the arrows facing up and out, rotate the Left Blower Assembly behind
the burner gas line onto the studs on the blower brackets and secure with two
M6 flange nuts. See fig 10.11
9. Secure the Green Grounding Strap to the rear of the control box using the
supplied sheet metal screw. See fig 10.12
10. Attach the Blower Control Box to the pilot holes in the rear wall in the
controls compartment using two sheet metal screws provided. See fig 10.12.
CAUTION: DO NOT PINCH WIRES WHEN INSTALLING CONTROL BOX!
11. Route the power cable plug through the square hole at the bottom of the
controls compartment.
Grounding Strap connection point Figure 10.12. Blower Control Box and power routing.
Figure 10.11. Secure nuts on studs. Tighten securely.
Figure 10.13. Secure the Snapstat bracket securely.
25
130139 Rev 1 GF 520 DV 12/22
12. Install the Snapstat Bracket to the stud at the bottom of the firebox
using the provided M6 flange nut.
13. Install the Snapstat into the bracket ensuring that it sits flush on the
firebox. If snapstat is not snug against the firebox, the bracket may need to
be bent by hand to make a secure fit. See fig 10.14.
14. Install the black and blue wires from the control harness to the
Snapstat.
15. Bend the protective cover open enough to slide over the snapstat.
16. Manipulate the Snapstat harness through the protective cover then attach
the protective cover assembly to the stud at the bottom of the firebox using a
second M6 flange nut. Bend the cover shut. See fig 10.15.
17. Attach the 4 connectors from the wire harness to the four terminals on
the Left and Right Blower Assemblies.
18. Connect power cord to outlet.
Blower Operation
The optional variable-speed blower will enhance heat circulation around the
firebox and out into the room. The blower is controlled by a heat activated
switch (snapstat) that will ONLY function when the control switch is in AUTO
setting. After the fire has been burning for a time, the snapstat will react
to the heat and activate the blower. Fan speed may be manually adjusted with
the rheostat knob. If the burner turns off, the blower will be shut off
automatically when the stove cools down.
If automatic blower circulation is not desired, place the blower control
switch in the MANUAL position.
Speed Control
Figure 10.16. Blower Controls
Manual or Automatic
Modes
Figure 10.14. Install Snapstat and attach pink connectors.
Figure 10.15. Install the Snapstat cover using a second M6 nut and tigheten
securely. 26
BLOWER
G
G
W
W BK BK
BK P
BK
POWER SUPPLY
BL
BK
GY SNAPSTAT
BK BK P
RHEOSTAT
PP P BL GY BR
BR P = QuickConnector Pin
SWITCH
AUTO OFF MANUAL
Figure 10.17. Blower Wiring Diagram
11. Install Burner Media
130139_Rev 1 GF 520 DV 12/22
Do not install burner media until after all other accessory installations or
component adjustments have been completed.
Log Set 158263
NOTE: LOG COMPONENTS ARE FRAGILE. WEAR SAFETY GLOVES AND HANDLE LOGS WITH
CARE.
Contents:
1 Rear Log ……………………….226921 #2 Left Side Log…………………226922 #3 Right Side Log
………………226923 #4 Left Middle Log …………….226924 #5 Right Middle Log…………..226925
Ember Stones ……………….6 oz.
1
Figure 11.1. Set the #1 Rear Log on the rear pins, one on the Burner and one
on the Burner Skirt.
Avoid Ember Stones in this area
Inspect the log parts and report any damage to your dealer. DO NOT INSTALL
DAMAGED LOGS.
1. Rear Log: Engage the holes in the underside of Rear Log #1 with two pins,
one on the burner base and one on the burner skirt. Fig 11.1
2. Place 12-15 Ember Stones on each side of the rear of the Burner as shown
in fig. 11.2. KEEP EMBER STONES AWAY FROM THE PILOT CARRY-OVER AREA AND BURNER
PERIMETER.
Figure 11.2. Place 12-15 Ember Stones on each side of the Burner. Avoid the Pilot carry-over area.
3. Right Side Log: Engage the hole on the underside of Right
Log #3 with the pin on the right side of the burner. Lean
the other side against Rear Log #1. Align the groove on the
bottom of Right Log #3 with the large bump on Rear Log #1. Fig 11.3
3
Figure 11.3. Rest the end of the #3 Right Log in the small pocket on the Base
Log.
27
130139 Rev 1 GF 520 DV 12/22
4. Left Side Log: Engage the hole on the underside of Left Side Log #2 with the pin on the left side of the burner. Lean the other side against Rear Log
1. Align the indentation on Left Side Log #2 with the small bump on Rear Log
1.
5. Right Middle Log: Engage the holes on the underside of Right Middle Log #5
with the two pins on the middle right of the Burner as shown.
6. Left Middle Log: Engage the hole on the underside of Left Middle Log with
the pin on the middle left of the Burner. Rest the other side of the log on
Right Middle Log #5.
7. If desired, spread the Ember Stones over the Burner Base in a thin layer.
DO NOT COVER GAS PORTING HOLES ON THE SIDES OR FRONT OF THE BURNER. PLACE
STONES OVER THE REAR PORTS ONLY AND UP TO THE REAR FLANGE OF THE BURNER. KEEP
EMBER STONES AWAY FROM THE PILOT CARRY-OVER AREA AND BURNER PERIMETER.
2
Figure 11.4. Place #2 Left Side Log on the far left pin and rest the other end
on the bump on #1 Rear Log.
5
The Rock Wool included the Miscellaneous Kit is intended as an enhancement to
replicate glowing embers. Use a toothbrush or tweezers to sparingly apply
small pinches of fibers over the front of the burner base after the log
components have been installed. The ample supply of rock wool is provided for
ease of handling and application purposes only. DO NOT USE THE ENTIRE QUANTITY
OF ROCK WOOL. Use no more than 1/4 of the material supplied.
Please be aware that sooting may occur with Propane fuel under minimum vent
configurations. Should soot develop, use a soft brush to clean the log and
remove some or all of the rock wool from the burner.
Figure 11.5. Place #5 Right Middle Log on the two middle right pins on the
burner.
4
Figure 11.6. Place #4 Left Middle Log on the middle left pin on the burner and
rest the other end on #5 Right Middle Log. Arrange Ember Stones over the
Burner Base.
28
130139_Rev 1 GF 520 DV 12/22
12. System Check
1. PURGING THE GAS LINE: When lighting the appliance for the first time, it
will take a few moments to clear the gas line of air. Once this purge is
complete, the appliance will operate as described in the lighting
instructions. From a cold start, it may be helpful to let the pilot light burn
in mode for 10 – 15 minutes to establish positive draft, before turning the
burner on. See the procedure on the inside back cover of this manual.
Subsequent burner starts will not require purging the gas line unless the
supply line is shut off.
2. PILOT FLAME: You can monitor the pilot flame located behind the burner at
the rear of the firebox. The pilot flame should be steady – not lifting or
floating. The flame should be blue in color around the pilot hood, with traces
of yellow toward the outer edges. Fig. 12.1.
The pilot flame should engulf the top 1/8″ of the thermocouple and thermopile
. The pilot flame should project from the pilot hood port toward the burner
carryover ports. Adjust the pilot flame using the adjustment screw to the left
of the valve regulator. See fig. 12.2.
3. See Flame Appearance / Air Shutter for air shutter settings and
adjustments. Note: The more offsets there are in the vent system, the greater
the need for an air shutter adjustment.
1/8 (3mm) Min.
Thermocouple
1 (25mm)
3/8 (8mm) Min.
Thermopile
Figure 12.1. Normal pilot flame projection.
WARNING:
!
PILOT ADJUSTMENT SHOULD ONLY BE PERFORMED BY A QUALIFIED,
PROFESSIONAL SERVICE TECHNICIAN
Adjustment screw
Figure 12.2. Pilot flame regulation.
INITIAL FIRING PROCESS Heat-curing the Stove Paint
This appliance has been painted with the highest quality coating used in the
hearth industry. Manufacturers have selected this product because it has been
proven durable, colorfast, and beautiful at temperatures up to 1200°F/650°C.
Although the paint has been air-dried at the factory, it must be heat-cured in
order to maximize its coating properties and durability. This process occurs
during initial firing of the appliance and will generate odor and some visible
smoke. We recommend you do the following BEFORE operating the appliance for
the first time:
1. Ventilate: Open doors and windows and use a fan to circulate fresh air
throughout the room.
2. Vacate: The fumes are non-toxic, but can be uncomfortable for babies,
small children, pregnant women, elderly, pets, or anyone having breathing
difficulties.
Gas Appliance Curing Process
1. After the installer has confirmed proper burner function at all heat
levels, the homeowner should operate the appliance at a low setting for
several hours, followed by several hours operation at a high setting.
2. Off-gassing by paint and log set ceramic material may leave a white,
powdery deposit on the inside surface of the glass panel. This residue must be
removed using a nonabrasive hearth gas appliance glass cleaner or warm water
to prevent permanent etching of the glass.
DO NOT USE AMMONIA-BASED CLEANERS. DO NOT CLEAN HOT GLASS.
See OPERATION sections, pages 31-32, for detailed, dayto-day operating
procedures.
29
130139 Rev 1 GF 520 DV 12/22
13. Flame Appearance /
Air Shutter Adjustment
The GF 520 DV gas stove is shipped from the factory equipped to burn Natural
gas and the air inlet shutter has been set to provide optimal combustion
efficiency under a variety of venting configurations. The air shutter may be
adjusted, however, to accommodate the conditions of your individual
installation and to provide the desired flame picture. Other installation-
related variables can also affect the flame picture:
Too large an air setting – the appliance will generate a flame that is blue
and transparent, or an “anemic” flame.
Too small an air setting – the appliance will generate very long yellow flames
resulting in black soot deposits on the logs, on the inside walls of the
appliance, and potentially on the exterior termination cap. Sooting is caused
by incomplete combustion in the flames and/ or insufficient combustion air
entering the air shutter opening.
CLOSE Restrict oxygen
OPEN Increase oxygen
Figure 13.1. Pull the shutter forward to increase primary air. Push it back to
restrict air.
To adjust the air shutter: 1. Loosen the wing nut shown in fig. 13.1. Slide
the Air Shutter
Handle forward toward yourself to open the air shutter and back to provide
less air. Before making any adjustments, start at the mid-point of the total
range of adjustment.
2. Allow the stove to burn for 15-20 minutes on the HIGH setting, observing
the flame continuously. If the flame appears weak, slow, or sooty, increase
the air shutter opening in 1/16″ – 1/8″ increments until the desired flame
picture is achieved. Allow the flames a few minutes to “settle-in” after each
adjustment.
3. Tighten the wing nut to secure the shutter at the desired setting.
Figure 13.2. Log Set burner flame picture. 30
14. Operation
Important Notes
1. For the first several hours of operation, it is common to detect some odor
as the metal and manufacturing materials cure under heat. This condition is
temporary and can be alleviated by allowing plenty of fresh air to circulate
through the area.
2. Condensation may develop on the glass upon each lighting of the appliance.
This “fog” will disappear as the glass heats.
3. IMPORTANT: It will be necessary to clean the glass after the first few
fires. A white powdery residue will be evident which results from the burner
media curing. Use a nonabrasive hearth gas appliance glass cleaner and warm
water.
IF THE GLASS IS NOT CLEANED, THIS RESIDUE CAN CAUSE THE GLASS TO BECOME
PERMANENTLY ETCHED.
DO NOT USE AMMONIA-BASED CLEANERS.
4. Keep the control compartments and area under the appliance free of dust.
Always keep the appliance area clear and free from combustible materials,
gasoline and other flammable liquids.
5. This appliance can be operated with a continuously burning pilot flame.
Exercise caution when using household products containing combustible vapors.
6. CAUTION: DO NOT OPERATE THIS APPLIANCE WITH ANY OF THE GLASS PANELS
REMOVED, CRACKED OR BROKEN. REPLACEMENT OF THE GLASS SHOULD BE DONE ONLY BY A
LICENSED OR QUALIFIED SERVICE PERSON. USE ONLY REPLACEMENT GLASS PROVIDED BY
YOUR AUTHORIZED JØTUL DEALER. NEVER SUBSTITUTE ANY OTHER TYPE OF GLASS.
REMOVE GLASS ONLY FOR ROUTINE MAINTENANCE.
ALWAYS HANDLE GLASS CAREFULLY.
130139_Rev 1 GF 520 DV 12/22
WARNING: READ AND UNDERSTAND ALL OPERATING INSTRUCTIONS BEFORE ATTEMPTING TO
OPERATE THIS APPLIANCE. DO NOT ALLOW ANYONE TO OPERATE THIS APPLIANCE WHO HAS
NOT READ AND UNDERSTOOD THESE INSTRUCTIONS. KEEP THE REMOTE CONTROL
TRANSMITTER WHERE CHILDREN CANNOT REACH IT.
WARNING: SEVERE INJURY. THIS APPLIANCE CAN BE SET TO OPERATE THERMOSTATICALLY.
BE AWARE THAT THE APPLIANCE MAY BE VERY HOT EVEN WHEN THE BURNER IS NOT
APPARENTLY OPERATING. KEEP CHILDREN AWAY FROM THE APPLIANCE.
WARNING: OBSERVE CAUTION NEAR THE GLASS PANEL. THE GLASS MAY SHATTER IF STRUCK
BY AN OBJECT. ALWAYS HANDLE THE GLASS PANEL WITH CARE.
31
130139 Rev 1 GF 520 DV 12/22
Rocker Switch
Pilot Volume Adjustment Screw
Regulator Knob Control Knob
Igniter Button
Inlet Pressure Port Manifold Pressure Port
Burner Operation
Familiarize yourself with the controls of the GF 520 DV and be sure that
anyone else using the appliance is also familiar with the controls and
operation procedures. Always follow the Lighting Instructions on the inside
back cover of this manual and also located on the inside the Controls Access
Panel.
This appliance is equipped with an ignition device that lights the pilot
automatically. Do not try to light the pilot by hand.
Once the pilot is lit, burner operation is controlled by the rocker switch
located at the left corner of the Control Access Panel. See fig. 14.2.
ON / OFF – use for manual control of the burner. T-STAT – use for optional
thermostatic or remote control operation. The burner will be controlled by
those accessories.
DV MV ONLY: This appliance is equipped with a timed valve that will shut off
the pilot light after seven (7) days if there has been not call for heat
within that time. Re-ignite the pilot following the lighting instructions on
the rating plate on the rear of the stove or on page 43 of this manual.
Exercise caution when using household products containing combustible vapors.
32
15. Maintenance
NOTICE: THIS APPLIANCE AND VENT SYSTEM MUST BE
INSPECTED ANNUALLY BY A QUALIFIED GAS TECHNICIAN. Keep this manual for
reference. IMPORTANT: ALWAYS TURN OFF THE GAS SUPPLY AND DISCONNECT POWER FROM
THE APPLIANCE BEFORE ANY SERVICE WORK IS PERFORMED.
GLASS AND SAFETY SCREEN BARRIERS DO NOT OPERATE THIS APPLIANCE IF ANY
OF THE GLASS PANELS OR SAFETY SCREEN BARRIERS IS REMOVED, CRACKED, DAMAGED OR
MISSING. REPLACE DAMAGED COMPONENTS USING ONLY GENUINE JØTUL PARTS AVAILABLE
FROM ANY JØTUL AUTHORIZED DEALER. REPLACEMENT SHOULD BE DONE ONLY BY A
LICENSED OR QUALIFIED SERVICE PERSON. CAUTION: HANDLE BROKEN GLASS WITH CARE.
REMOVE THE LOG SET AND USE A VACUUM TO CLEAN ANY REMAINING GLASS FRAGMENTS
FROM THE BURNER AND FIREBOX.
Annual Cleaning
Vent System
The entire vent system, including the chimney if
appropriate, should be inspected every year. If the venting is disassembled
for any reason, it should be reassembled and sealed according to the vent
manufacturer’s instructions provided at the initial installation. DO NOT USE
SILICONE SEALANT.
Burner System
Periodically inspect the firebox, valve compartment, convection airways and
optional blower to BE CERTAIN THAT THE FLOW OF COMBUSTION AND VENTILATION AIR
IS UNOBSTRUCTED.
The valve compartment should be vacuumed regularly to
remove dust and debris. Vacuum more frequently if there are pets in the home.
Use a soft brush attachment and handle log set components
carefully.
The pilot assembly and burner base should be inspected and
cleaned annually by a qualified technician. Replace any component showing
evidence of corrosion.
130139_Rev 1 GF 520 DV 12/22
Glass Care
Clean the glass only when necessary. Wipe the surface with a clean, dampened,
soft cloth. Follow with a dry, soft towel. Take care not to scratch the glass
surface. WARNING: DO NOT USE ABRASIVE CLEANERS ON THE GLASS. NEVER CLEAN THE
GLASS WHEN IT IS HOT. DO NOT USE AMMONIA-BASED CLEANING SOLUTIONS.
Glass and Gasket Inspection
It is important that the glass gasket be inspected at least annually. Examine
the ribbon gasket for signs of deterioration and make sure the gasket has a
positive seal. Replace the gasket if necessary. Refer to the replacement parts
list on page 39.
NOTE: INSPECT THE GLASS SURFACE FOR SCRATCHES AS THESE CAN WEAKEN THE PANEL
TENSILE STRENGTH. REPLACE THE PANEL IF ANY SCRATCHES ARE FOUND. USE ONLY DOOR
GLASS KIT 158067 AND SIDE GLASS PANEL 158080. DO NOT SUBSTITUTE ANY OTHER TYPE
OF GLASS.
Front Door Glass & Gasket Replacement Kit 158335
Read through these instructions before beginning the procedure
Tools: Needle nose pliers or flathead screwdriver
1. Lift and remove the Top Plate and Front Plate 2. Use the Latch Tool to
pull each latch hook forward to
disengage them from the glass frame. Fig. 2.2, page 5. 3. Lift the glass frame
up and off of the firebox. 4. The glass panel is held in place by four tabs at
the frame
corners. Use a screwdriver or small pliers to pry these up just enough to
release the glass panel. See fig. 11.1, page 34. 5. Remove the old gasket
material. 6. Wrap the new gasket material evenly around the edge of the glass,
peeling back the protective strip to expose the adhesive as you go, leaving a
1/2″ overlap at the top. Press the adhesive side down onto the glass surface.
Do not stretch the gasket. 7. Place the gasketed glass within the frame and
carefully bend each of the corner retainer tabs back just enough to secure the
glass in the frame. The Replacement Glass kit includes 4 Tinnerman compression
clips for use in case a tab should break. The clips engage over the edge of
the frame sides.
33
130139 Rev 1 GF 520 DV 12/22
Side Glass & Gasket Replacement Kit 158080
Extra Retainer Clips included with
Read through these instructions before beginning the procedure. Replacement
Glass Tool List: · Two 10mm wrenches
· 1/4 inch drive
· 4mm hex key
Replace the Side Glass Panel
1. Lift off the Top Plate. 2. Remove the Front Plate. 3.Use the Latch Tool to
pull each latch hook forward to
disengage the glass frame from the firebox. Lift the glass frame up and off of
the stove. See figs. 2.1 and 2.2 pg 5.+ 4. Remove the 10mm nut and bolt from
the rear top side of the side assembly. 5. LOOSEN the 10mm bolt on the inside
front of the side screen assembly. 6. LOOSEN the 10mm bolt on the inside back
of the side screen assembly. 7. Remove the side assembly by tipping and
lifting off the unit. 8. Remove the four 10mm nuts holding the side glass
frames.
Gasket
Integrated Retainer Tab
Figure 15.1. Front Glass replacement.
Glass Frame Glass Panel
Figure 15.3.Remove the Nut and Bolt from the rear top of the Side Assembly
Figure 15.4. Loosen the bolt on the inside front of the Side Assembly
34
9. Install replacement side glass and gasket:
· Wrap the new gasket material evenly around the edge of the glass, peeling
back the protective strip to expose the adhesive, leaving a 1/2″ overlap at
the end seam. Press the adhesive side down onto the glass surface. Do not
stretch the gasket.
· Place the panel within the frame, ensuring the gasket seam is on the top.
10. Replace the Side Glass Frame. Place the front of the frame in the channel
on the firebox then swing the frame onto the four retaining studs. Using the
four 10mm nuts previously removed.
11. Replace the Side Assembly and tighten the two loosened bolts on the
inside front and back of the side assembly.
12. Replace the 10mm bolt and screw removed form the rear top side of the
side assembly.
13. Replace the front and top plates.
130139_Rev 1 GF 520 DV 12/22
Figure 15.6. Remove the side assembly and set aside.
Figure 15.5. Loosen the bolt on the inside rear of the Side Assembly Figure 15.7. Remove the nuts holding the glass frame. 35
130139 Rev 1 GF 520 DV 12/22
Safety Screen Maintenance and Replacement
Cleaning
The integrated, Invisimesh® safety screens, located in front of the door and
side glass panels, should be periodically cleaned to remove dust, lint, and
other air-bourne debris. Over time, and with continuous exposure to heat,
these materials can contribute to variations in the screen hue.
Remove the front plate and clean both sides of the screen using a fine, soft
bristle brush or vacuum attachment.
APPLY ONLY VERY GENTLE PRESSURE TO AVOID DAMAGING THE SCREEN.
226647 Front Safety Screen Replacement
Tools: #4 hex key
The front safety screen is easily accessible from the back of the front plate.
.
Use a #4 Hex Key to remove the eight button head screws and retainer brackets
as shown in fig. 15.8.
The replacement screen and frame installs as a single unit using the original
eight brackets and screws. Screen material must sit flush to inner cast rib.
Figure 15.8. Remove front screen retainer screws and brackets.
Side Safety Screen Replacement 226648
Tool List: · Two 10mm wrenches
· 1/4″ Driver · #4 hex key
1. Follow steps 1-7 in the instructions for the side glass replacement kit on
pg. 34 to remove the side assembly.
2. Use the 4mm hex key to remove the four button head screws and two screen
brackets.
3. Remove the old screen and place the new screen on the side assembly with
the screen material resting against the cast rib of the side plate.
4. Replace the screen brackets and screws.
5. Follow steps 11-13 in the instructions for the side glass replacement kit
on pg. 34-35 to reassemble the stove.
Figure 15.9. Remove side screen retainer screws and brackets.
36
130139_Rev 1 GF 520 DV 12/22
37
Figure 16.1 GF 520 DV Firebox and Cast Iron Assembly
130139 Rev 1 GF 520 DV 12/22
No. Part No. Description
1 117917
Screw, HWH SMA #8 x 1/2 SL Blk Oxide – PIC
2 226725 Convection Air Shroud, GF520
3 227013 Weldment, Restrictor Outer, GF520
4 223241 Gasket, Exhaust Restrictor / Washer
5 120004 Washer, Fender, 6.4mm ID x18mm OD x 1.6mm, Zinc,
DIN 9021 – PIC
6 225469 Inner Restrictor Rod, GF 305/500
7 225466 Restrictor Plate, GF 305/500
8 10502392 Top Plate, Front, MB, GF 520
9 226858 Heat Shield, Top Plate, GF520
10 9962
Bolt, Hex Cap M6x10 DIN 6928 8.8 Ser Flange Zinc –
PIC
11 22476392 Light Box, Delay Door Mount, MB
12 157601 Accent Light Wire Harness, Single Light, Proflame 2
Stoves
13 117967
Screw, Pan Head #7 x 3/8 PH SMA Zinc – PIC
14 222943 Light Bulb, 130 Volt, 35 Watt
15 222974 Glass, Ceramic, Light Fixture
16 222977 Gasket, Light Cover
17 22476792 Light Shade, Stoves, MB
18 117968 Nut, M6 Serrated Flange plain – PIC
19 225942 Latch, Glass Frame, GF305 DV IPI
20 129322 Adapter Pipe, 6.625 dia
21 129118
Gasket, Starter, 6.75″ ID x 8.25″ OD – PIC
22 118034 Screw, M6 x 12, Button Head, Hex Socket, Blk Oxide
23 226658 Screen Retainer, GF520
24 117130
Bolt, Hex Head Serr Flange M6x12 Blk – PIC
25 10502292 Side Plate, MB, GF 520
26 226659 Front Plate Hanger, Right Side, GF520
27 226667 Support Bracket, Top Plate, GF520
28 226647 Screen, Assembly, Front, GF 520
29 22665492 Glass Frame, GF520, MB
30 129124 Gasket, Tadpole, .25 X 1.25 Nominal, Graphite, Self
Adhesive (70 in)
31 226723 Glass, Ceramic, Front, GF 520
32 220042 Clip, U Type (Tinnerman) – PIC
33 226666 Glass Frame, Side, GF520
34 226724 Glass, Ceramic, Side, GF 520
35 129124 Gasket, Tadpole, .25 X 1.25 Nominal, Graphite, Self
Adhesive (46 in)
No. Part No. Description
36 9911
Bolt, Hex Cap, M6x45, DIN 933, Class 8.8, Blk – PIC
37 118039 Sleeve, .375″ OD X .312″ ID X 1.188″, SS – PIC
38 118408 Spacer, .400″ID x .500″ OD .625″LG
39 226467 Spring, 1.5″ Length 316 SS
40 226655 Retainer Glass Frame, GF520
41 226608 Firebox Weldment, GF520
42 226918 Blower Chevron, GF520
43 129159 Lanyard, Rating Plates
44 22666592 Access Door Controls, GF520, MB
45 222664 Protection Cap, M8 Hex, Black
46 99115
Bolt, Hex Head M8 x 12 Blk – PIC
47 10502892 Base Plate, MB, GF 520
48 22666492 Access Wall Controls, GF520
49 226660 Retainer, Side to Base, GF520
50 10502692 Base, Side Plate, MB, GF 520
51 117875 Bolt, M8 x 20, Hex Serrated Flange Hd Class 8.8 Black
Oxide
52 226648 Screen, Assembly, Side, GF 520
53 226657 Front Plate Hanger, Left Side, GF520
54 117975
Nut,Wing M6 Zinc – PIC
55 226955 Handle, Air Shutter
56 220734 Gasket, 2.25″ OD x 188″ ID x .125″ T – PIC
57 226677 Handle, Air Shutter, GF520
58 158219 Replacement Burner Assembly, GF520
59 221390 Primary Air Shutter Asby
60 220018 Orifice, #37
45025 Orifice, #52 / LP
61 223231 Orifice Holder, Drop In Assembly, 12.5″ Tube
62 225525 Grommet, Silicone, Pilot Plug, GF500/160/305
63 222280 Gasket, Drop In Orifice Holder
64 226919 Intake Air Diverter, GF520
65 226745 Pilot Assembly, NG, Flat Brkt, SS Body, 18″ Tube, w/LP
Injector
66 226670 Rear Shelf, GF520
67 226861 Intake Air Diverter, Rear Shelf, GF520
68 226948 Panel Retainer, GF520
69 226656 Baffle, Firebox, GF520
70 10502492 Top Plate, Rear, MB, GF 520
71 226668 Rear Shroud, GF520
72 226857 Rear Heat Shield Top Plate
38
GF 520 DV Illustrated Parts Breakdown
Use only parts available from Jøtul authorized dealers.
130139_Rev 1 GF 520 DV 12/22
Figure 16.2 GF 520 DV Valve Assembly and Optional Blower
No. Part No. Description
1 117917
Screw, HWH SMA #8 x 1/2 SL Blk Oxide
2 226662 Valve Bracket, GF520
3 117911
Screw, Pan Head, Phillips, 10-32×3/8″, Zinc
4 222292 Elbow, 90 deg, Brass 3/8 NTP X 3/8″ Dia Flare
5 117922 Nut, Hex M4, DIN 934, Plain – PIC
6 117921
Screw, Pan Head, Phillips, M4 X 14, Blk Oxide
7 117920 Screw, Pan Head, Phillips, M4 X 8, Zinc
8 118055 Kepnut, M4, Ext. Tooth Lockwasher, Stl, Zinc
9 226939 Fan Mounting Bracket, GF520
10 129154 Terminal Block, 2 Pole 77 series – PIC
11 3902576 Igniter Bracket
12 3902573 Piezo Ignitor Button
13 226310 Flex Tube, 3/8″ OD x 36″, 3/8″ Female Flare
Connectors
14 223215 Adapter, Straight, Brass, 3/8 NTP x 3/8″ Dia
Flare
No. Part No. Description
15 117968 16 158333 17 225063
18 225069 19 222951
20 220617 21 158 22 129153
23 226950
24 226661 25 222263
226946
Nut, M6 Serrated Flange plain Replacement Blower, Flat Pack, GF520 Snapstat Finger Guard, GI450 DVII/45i/545/645 Snapstat Shield, GI450 DVII/45i/545/645 Bracket, Snapstat, Firebox Mounted, GI 450/545/645 Snapstat, 120-110 °F, Normally Open – YELLOW Replacement Harness, Burner Switch, GF520 DV Switch, Rocker, SPDT, Black, Ctr Off, Marked “ON-OFF-STAT” – PIC Switch Box, Ignition On/Off, GF520 DV / DVMV Controls Board, GF520 DV Valve DV MV Valve
39
130139 Rev 1 GF 520 DV 12/22
This page is intentionally left blank. 40
130139_Rev 1 GF 520 DV 12/22
This page is intentionally left blank. 41
130139 Rev 1 GF 520 DV 12/22
18. Jøtul Gas Product
Warranty
This warranty policy applies to gas products identified by the Jøtul trade
name as set forth below. A. LIMITED FIVE YEAR WARRANTY – Cast Iron, Steel
Doors, Surround Components, Firebox: Jøtul North America Inc. (JØTUL)
warrants, to the original retail purchaser, that those components of the Jøtul
Gas Stove or Fireplace specified above will be free of defects in material and
workmanship for a period of five (5) years from the date of purchase. This
warranty is subject to the terms, exclusions and limitations set forth in the
following text. B. LIMITED TWO YEAR WARRANTY – Burner, Ceramic Burner, Burner
Treatments, Firebox Panels: JØTUL warrants, to the original retail purchaser,
that those components of the Jøtul Gas Stove or Fireplace specified above will
be free of defects in material and workmanship for a period of two (2) years
from the date of purchase. Ceramic burners are warranted against functional
defects for a period of two (2) years from the date of purchase. This warranty
is subject to the terms, exclusions, and limitations set forth in the
following text. C. LIMITED TWO YEAR WARRANTY – Enamel Finish: JØTUL warrants,
to the original retail purchaser, the enamel finish on cast iron components of
the Jøtul Stove or Fireplace Insert specified above against peeling or fading
for a period of two (2) years from the date of purchase. This warranty is
subject to the terms, exclusions and limitations set forth below. D. LIMITED
ONE YEAR WARRANTY – Gas & Electrical Components (controls, plumbing, valve,
blower): JØTUL warrants, to the original retail purchaser, that those
components of the Jøtul Gas Stove or Fireplace specified above will be free of
defects in material and workmanship for a period of one (1) year from the date
of purchase. This warranty is subject to the terms, exclusions, and
limitations set forth in the following text.
JØTUL will repair or replace (including parts & labor), at its option, any of
the above components determined by JØTUL to be covered by this warranty. You
must, at your own expense, arrange to deliver or ship the component to an
authorized Jøtul dealer and arrange for pickup or delivery of the component
after repairs have been made. If, upon inspection, JØTUL determines that the
component is covered by this warranty, the repair or replacement will be made
as set forth above. This warranty is not transferable and is extended only to,
and is solely for the benefit of, the original retail purchaser of the Jøtul
Gas Stove or Fireplace. This paragraph sets forth the sole remedy available
under this warranty in the event of any defect in the Jøtul Gas Stove or
Fireplace. The warranty period for any replaced component will be the
remaining unexpired portion of the warranty period for the original component.
Please retain your dated sales receipt in your records as proof of purchase.
EXCLUSIONS AND LIMITATIONS NOTICE: This warranty is void if installation or
service is performed by someone other than an authorized installer, service
agency or gas supplier, or if installation is not in conformance with the
installation and operating instructions contained in this owner’s manual or
local and/or national fire and building regulations. A listing of local
authorized installers, service agencies and gas suppliers can be obtained from
the National Fireplace Institute at http://www.nficertified.org/. This
warranty does not cover the following: 1) Repair or replacement of parts that
are subject to normal wear and tear during the warranty period or to parts
that may require replacement in connection with normal maintenance. These
parts include lamp bulbs, paint, gaskets, and glass (except to the extent such
parts suffer damage from thermal stress).
- Damage due to incorrect installations not in conformance with the
installation instructions contained in this owner’s manual or local and/or
national fire and building regulations. 3) Damage due to service performed by
an installer, service agency or gas supplier, unless otherwise agreed to in
writing by JØTUL. 4) Labor or other costs associated with the repair of gas
controls, plumbing, burners, log set, lamp bulbs, or sheet metal firebox
beyond the warranty period. 5) Damage caused by unauthorized modification, use
or repair. 6) Damage to enameled surfaces caused by improper operation or
misuse, including use that is not in conformance with the operating
instructions contained in this owner’s manual. Such damage can typically be
identified by bubbling, cracking, or discoloration of the enamel finish. 7)
Costs incurred by travel time and/or loss of service. 8) Damage incurred while
the Jøtul Gas Stove or Fireplace is in transit. IN NO EVENT SHALL JØTUL, ITS
PARENT COMPANY, SHAREHOLDERS, AFFILIATES, OFFICERS, EMPLOYEES, AGENTS OR
REPRESENTATIVES BE LIABLE OR RESPONSIBLE TO YOU FOR ANY SPECIAL, INDIRECT,
INCIDENTAL, CONSEQUENTIAL, PUNITIVE OR OTHER SIMILAR DAMAGES, INCLUDING, BUT
NOT LIMITED TO, LOST PROFITS, LOST SALES, INJURY TO PERSON OR PROPERTY, OR
DAMAGES TO A STRUCTURE OR ITS CONTENTS, ARISING UNDER ANY THEORY OF LAW
WHATSOEVER. ALL IMPLIED WARRANTIES, INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, OR OTHERWISE, ARE
LIMITED IN DURATION TO THE LENGTH OF THIS WRITTEN WARRANTY. EXCEPT AS
EXPRESSLY SET FORTH HEREIN, JØTUL MAKES NO ORAL, WRITTEN OR OTHER WARRANTY
WITH RESPECT TO JØTUL GAS STOVES OR FIREPLACES. Some states do not allow the
exclusion or limitation of incidental or consequential damages, or limitations
on the length of implied warranties. Therefore, the above exclusions or
limitations may not apply to you. This warranty gives you specific legal
rights, and you may have other rights, which vary from state to state. JØTUL
reserves the right to discontinue, modify or change the materials used to
produce the Jøtul Gas Stove or Fireplace. JØTUL shall have the right to
replace any defective component with substitute components determined by JØTUL
to be of substantially equal quality and price. The dollar value of JØTUL’s
liability for breach of this warranty shall be limited exclusively to the cost
of furnishing a replacement component. JØTUL shall not in any event be liable
for the cost of labor expended by others in connection with any defective
component. Any costs or expenses beyond those expressly assumed by JØTUL under
the terms of this warranty shall be the sole responsibility of the owner(s) of
the Jøtul Gas Stove or Fireplace. No dealer, distributor, or other person is
authorized to modify, augment, or extend this limited warranty on behalf of
JØTUL. NO MODIFICATION OR CHANGE TO THIS WARRANTY WILL BE EFFECTIVE UNLESS IT
IS MADE IN A WRITTEN DOCUMENT MANUALLY SIGNED BY AN AUTHORIZED OFFICER OF
JØTUL. An authorized installer may have been provided with certain information
related particularly to the Jøtul Gas Stove or Fireplace; however, no
authorized installer or other person who may service the appliance is an agent
of JØTUL. No inference should be made that JØTUL has tested, certified, or
otherwise pronounced any person as qualified to install or service the
appliance. JØTUL shall not be liable or otherwise responsible for any error or
omission by a person installing or servicing a Jøtul Gas Stove or Fireplace.
If you believe your Jøtul Gas Stove or Fireplace is defective, you should
contact your nearest authorized Jøtul dealer, who will process a warranty
claim. IN ORDER TO QUALIFY FOR WARRANTY COVERAGE, JØTUL MUST RECEIVE NOTICE OF
A POSSIBLE DEFECT WITHIN SIXTY (60) DAYS OF THE DATE THE DEFECT IS FIRST
DISCOVERED, OR REASONABLY COULD HAVE BEEN DISCOVERED.
This warranty is given by Jøtul North America, Inc., 55 Hutcherson Drive, Gorham, Maine 04038 USA
42
LIGHTING INSTRUCTIONS
130139_Rev 1 GF 520 DV 12/22
FOR YOUR SAFETY, READ BEFORE LIGHTING.
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION
MAY
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.
A. This appliance has a pilot which must be lit by hand. When lighting the
pilot, follow these instructions exactly.
B. BEFORE LIGHTING, smell all around the appliance area for gas. Be sure to
smell next to the floor because some gas is heavier than air and will settle
to the floor.
WHAT TO DO IF YOU SMELL GAS: · Extinguish any open flame. · Open windows. · Do
not light any appliance. · Do not touch any electrical switches. · Do not use
any phone in your building. · Immediately call your gas supplier from a neigh-
bor’s phone.
· If your gas supplier cannot be reached, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use
tools. If the knob will not push in or turn by hand, do not try to repair it.
Call a qualified technician. Force or attempted repair may result in a fire or
explosion.
D. Do not use this appliance if any part has been under water. Immediately
call a qualified service technician to inspect the appliance and to replace
any part of the control system and any gas control which has been under water.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the BURNER ON/OFF switch to “OFF”, or set the thermostat to lowest
setting (if used).
3. Confirm that the gas supply line shut-off valve is open.
Control Valve Control Knob
ON
PILOT
OFF
4. Push in Valve Control knob slightly and turn clockwise to “OFF”.
NOTE: Knob cannot be turned from “PILOT” to “OFF” unless the knob is pushed in slightly. Do not force.
5. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “B” in the safety information above on this page. If you do not smell gas, go to the next step.
6. Push in Valve Control knob slightly and turn counter-
clockwise
to “PILOT”.
7. Push in control knob all the way and hold in.
Immediately light the pilot by triggering the spark ignitor (push the red button repeatedly) until pilot lights. Continue to hold the control knob in for about one minute after the pilot lights. Release knob and it should spring back. The pilot should remain lit. If it goes out, repeat Steps 5 through 7.
· If knob does not return when released, stop and immediately call your service technician or gas supplier.
· If pilot will not stay lit after several tries, turn the control knob to OFF and call your service technician or gas supplier.
Pilot Assembly
8. Turn Valve Control knob counter-clockwise to “ON”.
9. Set the BURNER switch to “ON”, or set thermostat (if used) to desired temperature.
10.NOTE: MV MODELS ONLY – the pilot will
automatically shut off if there is no call for heat within
seven days. Relight the pilot following the preceding
steps in order.
TO TURN OFF GAS TO THE APPLIANCE:
1. Place BURNER switch in” OFF” position. The pilot 2. For complete shutdown, depress the Valve Control Knob
will remain lit for normal service.
and turn clockwise to “OFF”. Do not force.
43
130139 Rev 1 GF 520 DV 12/22
December 2022 130139_Rev. 1
This appliance must be installed in conformance with local and national building regulations. Before beginning the installation, it is important that these instructions be carefully read and understood. Jøtul maintains a policy of continual product development. Consequently, products may differ in specification, color or type of accessories from those illustrated or described in various publications.
Your stove has a unique serial number stamped on the rating plate located in
the control compartment. Please record the serial number in the space below.
You may also wish to attach your purchase receipt to this page for future
reference.
MODEL NAME: Jøtul GF 520 DV
SERIAL NUMBER:___
DATE OF PURCHASE:____
AUTHORIZED DEALER:__
ADDRESS ___
PHONE: ____
INSTALLER: __
FUEL TYPE: ____
FUEL CONVERSION:
NO ___ YES__
INSTALLATION DATE: _____
INSTALLATION TECHNICIAN: __
Jøtul North America 55 Hutcherson Dr. Gorham, Maine 04038-2634
Jøtul ASA P.O. Box 1411 N-1602 Fredrikstad Norway
44
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>