COMPLEE KLY-S72-96-DR-A-B Digital Synchroscope User Manual

June 10, 2024
COMPLEE

COMPLEE KLY-S72-96-DR-A-B Digital Synchroscope User Manual

Introduction

  1. This instrument applies as the synchronizing indicator in between power network and generator. When the voltage, frequency in between generator and power network is nearly consistency within defined time, the LED light roulette will slow down until the light stop at SYNC led (i.e. Synchronizing), and then generator can connect to the power network. Synchroscope can indicate the difference on frequency and phase angle in between generator and power network.
  2. The meter is designed competitively by single chip with advanced arithmetic and accurate control.

Technical Specification

  • Operating Voltage UN: AC 57V, 63V b. AC 100V, 110V
  1. AC 220V, 230V, 240V d. AC 277V e. AC 380V, 400V, 415V f. AC 440V, 450V
  2. Voltage range:75%UN~115%UN
  3. Frequency range:40~70Hz
  4. Power consumption:≤4VA
  5. Overload:Continuous 2×UN short time 2×UN, 3s
  6. Electrical angle 15°~345° LED resolution ratio 15° Electrical angle 345°~0°~15° LED resolution ratio 3°
  7. Measuring accuracy of phase angle ±1.5º
  8. Voltage measuring error: ±1.0%UN
  9. Time error: ±10ms
  10. Blocking voltage(No indication on phase angle difference): Low voltage blocking voltage: 70%UN High voltage blocking voltage: 120%UN
  11. LED display:Electrical angle ±15°(physical angle±30°)green LED display,remaining sight angle in red LEDs
  12. Node capacity of relay output:AC 250V/5A, DC 30V/5A
  13. Pulse width of relay output: 1000ms
  14. workingenvironment:Temperature: -10℃ ~+55℃ RH:5%~95%,No condensation
  15. storageenvironment:Temperature:-25℃ ~+70℃

Application Instruction

Display of front panel

LED indicates the instant phase error Δф,the resolution ratio of red LED is 15º. The resolution ratio of green LED is 3º within the range of synchronized point ±15º. During normal operation period, only one LED lights among the circular bar graph will light, the position of LED is stimulated the actual phase angle difference. Details see below diagram:

KLY-S96-D,KLY-S96-DR-A/B

Installation Metho

Condition of synchronization for Type D synchroscope

Voltage difference of UBB and UGEN < 10%UN; Frequency difference of Fbus and Fgen < 0.5Hz; Phase angle 345°~15°

All above conditions are satisfied.

Condition of synchronization and predefined table for Type

DR-A synchroscope

  1. User mustprecisely set up 3 parameters; voltage difference( △ U), frequency difference( △ F)and deferred time(Time), Each parameter
    is defined by 16 pos rotary DIP switch (from 0 to F), each pos has its corresponding value, see below table for details:
Switch position 0 1 2 3 4 5 6 7
△ U(%) 1 2 3 4 5 6 7 8
△ F(Hz) 0.05 0.07 0.09 0.11 0.13 0.15 0.17 0.19
Time(ms) 50 80 110 140 170 200 230 260
Switch position 8 9 A B C D E F
△ U(%) 9 10 11 12 13 14 15 16
△ F(Hz) 0.21 0.23 0.25 0.27 0.29 0.31 0.33 0.35
Time(ms) 290 320 350 380 410 440 470 500
  1. When turned on, users can find the code switch failure early through the panel indicating of code switch position. Voltage difference( △ U), frequency difference( △ F)and deferred time(Time) code switch position indicates in turn, each indicates about 3 seconds. The top LED light represents the switch position is 0, the LED lights in clockwise turn represents the switch position plus 1, until The top left three green LEDs light in turn respectively represents the current switch position is voltage difference(△ U), frequency difference( △ F)and deferred time(Time).
  2. Condition on synchronized signal release:

Voltage difference of UBB and UGEN < △ U×UN; Frequency difference of Fgen and Fbus < △ F;
The moment before phase angle difference is 0º,and ahead of time = Time.
All above conditions are satisfied, the synchronized signal will be

Connection Diagram

  1. KLY-S72/96-D synchroscope

  2. KLY-S144-D synchroscope

  3. KLY-S72/96-DR-A/B synchroscope
    Outline Drawing