Jetmaster JM Quadro Outdoor Wood Fire and BBQ Grill Instruction Manual

June 10, 2024
Jetmaster

Jetmaster JM Quadro Outdoor Wood Fire and BBQ Grill

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
PRODUCT

IMPORTANT: Read all instructions carefully before starting installation. Failure to follow these instructions may result in a fire hazard and will void the warranty. Due to continued product improvement, The Fireplace Ltd reserves the right to change product specifications without prior notification. Please check to ensure you have the latest installation instructions. 08/2022

IMPORTANT

THE JETMASTER UNIT IS TO BE INSTALLED BY A CERTIFIED FIREPLACE INSTALLER, APPROVED NZHHA INSTALLATION TECHNICIAN.

JETMASTER FIREBOX DIMENSIONS

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-1

Note : All dimensions are in (mm)

| A| B| C| D
---|---|---|---|---
CAVITY FRAMING| 1050| 1400| 800| 500

Table 1 E 2 x 160 dia. or 2 x (100 x200) F 1275 height of Hebel cell Timber frame-out with 75mm Hebel cell on a steel base.

A TIMBER BASE IS NOT ACCEPTABLE
Please note that these dimensions (based on Hebel Block margins) are the absolute minimum sizes – widths (A & B) maybe increased if desired.

IMPORTANT: If the firebox is raised it must be placed on top of a 75mm Hebel panel which is placed on top of a steel structure or masonry blocks. Height of 500mm is recommended. A TIMBER BASE IS NOT ACCEPTABLE Please note that these dimensions (based on Hebel Block margins) are the absolute minimum sizes – widths (A & B) maybe increased if desired.

TIMBER FRAME PLAN – RECESS

Note : If the appliance is exposed not under protective cover please recess the appliance. Min =40mm/Max recess = 100mm

min 2 x 160mm dia. or equal square or rectangle shaped air vents to be wall mounted

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-3

Drawing Not To Scale

  • 800mm + recess value (refer to Table 2)
  • Hebel Non Combustible material (e.g Promatect H)
  • Maximum 100mm recess 1400mm
  • Floor Protector (refer to Table 4)
  • Rock Wool Insulation
  • Optional Finishing : Stone, Brick, Plaster on Brick
TIMBER FRAME CROSS SECTION – RECESS DETAIL

min 25mm from flue pipe casing to combustible material

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-4

Note : All external airvents must be bird & rodent proofed with permanently fixed screen

It is important to ensure the Jetmaster fire box is seated at the required finished Floor Protector level

  • Flue Pipe Casing
  • S/S Flue Pipe
  • Hebel Rock Wool Insulation (Glue rock wool using fire cement to the firebox & gather)
  • min 2 x 160mm dia or equal square or rectangle shaped air vents to be wall Note: All external air vents must be bird & rodent proofed with permanently fixed screen
  • Hebel Block Non Combustible material (e.g Promatect H)
  • C (see Table 2)
  • Maximum 100mm recess
  • Secure firebox with 2 x12mm dynabolts for earthquake retraints

FLOOR PROTECTOR REQUIREMENTS

Table 4

| A| B| C| D
---|---|---|---|---
Hardwood Floor| 900| 900| 900| 900
Carpeted Floor| 900| 900| 900| 1200
Tiled Floor| 900| 900| 900| 1200
Concrete Floor| 500| 500| 500| 500

Product Usage Instructions:

  1. Step 1: Before starting the installation process, it is important to read all instructions carefully to avoid any fire hazards. Ensure that you have the latest installation instructions.
  2. Step 2: The Jetmaster unit must be installed by a certified fireplace installer who is an approved NZHHA installation technician.
  3. Step 3: Check the Jetmaster firebox dimensions in Table 1 before starting installation. Note that all dimensions are in mm.
  4. Step 4: If the firebox is raised, it must be placed on top of a 75mm Hebel panel which is placed on top of a steel structure or masonry blocks. A height of 500mm is recommended. A timber base is not acceptable.
  5. Step 5: Follow the Timber Frame Plan – Recess and Timber Frame Cross Section – Recess Detail to recess the appliance. Ensure that you install a minimum of 2 x 160mm dia. or equal square or rectangle shaped air vents to be wall mounted.
  6. Step 6: Use Hebel Non-Combustible material (e.g Promatect H) and Rock Wool Insulation for the installation. Optional Finishing: Stone, Brick, Plaster on Brick.
  7. Step 7: Refer to Table 4 for floor protector requirements based on the type of flooring.
  8. Step 8: Secure firebox with 2 x12mm dynabolts for earthquake retraints.
  9. Step 9: Follow the Flue Installation and Flue Penetration & Chimney Chase Air Ventilation instructions for proper installation.
  10. Step 10: After installation, ensure that the appliance is in good working condition before use.

GENERAL NOTES – SOLID FUEL

FUELTHE APPLIANCE AND FLUE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH AS/NZS2918:2001 AND THE APPROPRIATE REQUIREMENTS OF THE RELEVANT BUILDING CODE OR CODES.MIXING OF APPLIANCE OR FLUE SYSTEM COMPONENTS FROM DIFFERENT SOURCES OR MODIFYING THE DIMENSIONAL SPECIFICATION OF COMPONENTS MAY RESULT IN HAZARDOUS CONDITIONS. WHERE SUCH ACTION IS CONSIDERED, THE MANUFACTURER SHOULD BE CONSULTED IN THE FIRST INSTANCE.CRACKED AND BROKEN COMPONENTS, e.g. GLASS PANELS OR CERAMIC TILES, MAY RENDER THE INSTALLATION UNSAFE.DO NOT USE FLAMMABLE LIQUIDS OR AEROSOLS TO START OR REKINDLE THE FIRE OR IN THE VICINITY OF THIS APPLIANCE WHEN OPERATING.DO NOT STORE FUEL WITHIN HEATER INSTALLATION CLEARANCES. WHEN OPERATING THIS APPLIANCE AS AN OPEN FIRE USE A FIRE SCREEN.THIS APPLIANCE SHOULD BE MAINTAINED AND OPERATED AT ALL TIMES IN ACCORDANCE WITH THESE INSTRUCTIONS.USE OF SOME TYPES OF PRESERVATIVE-TREATED WOOD AS A FUEL CAN BE HAZARDOUS. IFINSTALLEDINACOMMERCIALSETTINGASACRIFICIALPLATEMUSTBEFITTEDTOTHEBACK OFTHE FIRE TOCOMPLYWITH JM FIREBOXWARRANTY CONDITIONS. THE FLUE SYSTEM SHOULD BE CLEANED EVERY 12 MONTHS. AS/NZS2918:2001GENERALNOTES–SOLID FUEL

HEBEL CUT-OUT PLAN
Hebel Panels × 8 (1200mm x 600mm x 75mm) – Does not include floor protector. Cut-out plan – Appendix A.

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-5 Jetmaster-JM-Quadro-Outdoor-Wood-
Fire-and-BBQ-Grill-FIG-6

MARGIN SET
All Hebel Block margins have been made to fit firebox timber frame trim out dimensions (see Hebel cut-out plan). Suggested method to cut Hebel Block – skill saw fitted with masonry blade. Under no circumstance is the width of the vertical margin legs to be less than 150mm and the height of the margin lintel to be less than 300mm Where a board finish is required around the fire, ensure allowance is made to place non combustible internal wall lining (eg: Promatect H) to cover the extent of the Hebel panel surround (shown shaded). Directly touching the firebox with any board or plaster finish will cause cracking from heat expansion. Allow 2mm minimum space away from the firebox. Bond Hebel Block together using appropriate adhesive eg: Gorilla Grip or similar (non- solvent based) & secure with screws for added strength

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-7

TIMBER FRAMING PREPARATION

IMPORTANT : The appliance must be located a minimum of 1200mm away from combustible adjacent walls (e.g. exterior of house)

The appliance, gather, flue and Hebel panel weighs approx. 400kg. Ensure the base structure can withstand this load. Refer to the minimum framing dimensions as per table 2. Allow a temporary lintel height (see table 2 ‘B’) from the finished floor protector level until the firebox and flue system is installed. Install front nogs on edge to increase chimney chase dimension. Ensure suitable air vents (2 x 160mm diameter or equivalent) in place to vent firebox space – these maybe located in the floor or in the side wall space. Ensure vents must be bird and vermin proofed.

FIREBOX INSTALLATION

  • All dimensions shown for the framing trim out and Hebel cell are based on a maximum frontal clearance between the timber framing and the rear of the firebox fascia, being not more than 15mm.
  • Locate floor protector in trim out cavity. If on a concrete floor, suggest a mortar screed to the underside of the floor protector. If on a wooden floor, screw or dynabolt in place.
  • Locate stud openings on both sides.
  • Position and ensure a strip of glass rock wool insulation is between the inner hebel leg face and the firebox. Nail through stud into hebel leg to secure in place.
  • Locate and position firebox, fit and seal gather in cavity. Earthquake restraints may be positioned by drilling through firebox into the floor protector, in a position midway beneath the log-pan. Two 12mm dynabolts or similar will suffice. Do not over tighten and deform firebox.
  • Attach rock wool to the sides & back of the firebox and gather. DO NOT BLOCK OFF the air entry between the inner flue pipe and flue pipe casing or the air circulation between the vent holes in the cavity.
  • Once the flue system is installed, place a minimum 300mm hebel block over the front face of the firebox and gather.
  • Ensure the hebel block does not rest on top of the firebox. A Lintel Bar may be required.

MASONRY MINIMUM CAVITY SIZE

MODEL A B Temporary Lintel C D E – Vents
1050 1150 700 1200 100 860 2 x 160dia. or 2 x 100x 200

Note : If the appliance is exposed not under protective cover please recess the appliance . Min =40mm/Max recess = 100mm. Add recess dimension to B dimension in Table 2.

PLAN-RECESSDETAIL

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-8

CROSS SECTION

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-9

  1. Locate and position firebox, fit and seal gather in cavity using fire cement (exhaust cement) and bolts (supplied), to the firebox.
  2. Note : Pop rivet back of gather to firebox if required (refer to Cross Section). Earthquake restraints may be positioned by drilling through firebox into the floor protector, in a position midway beneath the log-pan. Two 6mm dynabolts or similar will suffice. Do not over tighten and deform firebox.
  3. Attach rock wool (supplied) to the sides of the firebox and gather (using fire cement).
  4. DO NOT BLOCK OFF the air entry between the inner flue pipe and flue pipe casing or the air circulation between the vent holes in the cavity.
  5. Refer to Table 4, for minimum hearth size.

CAVITY PREPARATION

A minimum 75mm thick Floor protector is only required if finished surface is combustible e.g:timber.Please note that these dimensions (based on Masonry margins) are the absolute minimum sizes -widths (A & B) maybe increased if desired. If you intend on recessing the firebox, please add the recess value to Dimension ‘B’.

WARNING : Minimum cavity sizes leave NO MARGIN FOR ERROR . If the cavity is larger than minimum dimensions (A & B) close up the lateral sides using Hebel block, concrete block or similar (do not use any combustible material).Refer to Table 2 for the minimum cavity dimensions and temporary lintel height measurements, until the firebox and flue system is installed. Note: Temporary lintel height is measured from finished floor protector level.Ensure suitable air vents (min. 2 x 160mm diameter or equivalent) in place to vent firebox space -these maybe located in the rear or in the side wall space; make allowance (min. 2 x 160mm diameter or equivalent) at the top of the chimney chase, Pg. 13. Ensure vents are bird and vermin proofed

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-10

SOLID FUEL

Note : 2 x flue lengths are supplied as a minimum for free standing outdoor built installations. If the outdoor fire structure is attached to the house the flue will need to be extended and meet the following requirements;

  1. Install first length of flue pipe crimped end down, inside gather collar. Rivet flue pipe in 3 places around gather collar. Place bottom flue spider bracket around gather flue pipe collar, secure in position by tightening up coach bolt/screw (supplied). Seal flue with fire
  2. Install second length of the flue pipe crimped end down and fix by riveting in at least 3 places around the flue pipe joint.
  3. Install first length of the flue pipe casing by positioning on installed bottom flue spider bracket crimped end up.
  4. Position flue spacer at the flue pipe joint.
  5. Repeat steps 1 – 4 to the required flue height. As per AS/NZS2918:2001 4.9.1
  6. a. “the flue pipe shall extend not less than 4.6m above the top floor protector”.
  7. b. “the minimum height of the flue system within 3m distance from the highest point of the roof shall be 600mm above that point”.
  8. c. “the minimum height of a flue system further than 3m from the highest point of the roof shall be” a minimum “1000mm above roof penetration”.
  9. d. “no part of any building lies in or above a circular area described by a horizontal radius of 3m about the flue system exit”.
  10. The last length of flue pipe needs to extend past the flue pipe casing by at least 150mm or flush with the top of the casing cover spigot when fitted – sizing/measuring and cutting down should be carried out prior to the flue pipe casing being fitted over the flue pipe.
  11. Before fitting casing cover, place the spider in opposition with the spider post facing down between the flue pipe and flue pipe casing. Secure spider in position. Place the casing cover over the flue pipe, press down firmly onto the spider. Check airway around the casing cover is clear, then secure in position using three stainless steel rivets.
  12. Fit cowl to top of flue – DO NOT RIVET IN POSITION. In high wind areas, it is recommended that the cowl be secured in position with a stainless steel self tapping screw, this will enable the cowl to be removed for cleaning. Discuss Bird Proofing needs with your installer.
  13. If flue is concealed in a chase, allow for air vents (2 x 80mm diam. or equivalent) at the highest possible point on the chimney chase or alternatively, allow a min 25mm air space between the casing cover spigot and the outer casing. Refer to pg. 12.

MINIMUM HEIGHT OF FLUE SYSTEM EXIT
As per AS/NZS 2918:2001 4.9.1 Fig 4.9

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-11

CHIMNEY CHASE AIR VENTILATION

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-12

Note : All external air vents & ceiling penetrations must be bird & rodent proofed with permanently fixed screens

FLUE PENETRATION

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-13

CHIMNEY CHASE MINIMUM TRIM OUT

Table 3

MODEL FLUE SYSTEM MINIMUM TRIM OUT DIMENSION
X (min) Y (min)
1050 300/400 450

Note : A minimum 25mm clearance from flue pipe casing to combustible material must be maintained. A Minimum clearance of 200mm above Heat Shield must be maintained.

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-14

MINIMUM FLOOR PROTECTOR SIZE

Table 4

MODEL A B C
Floor Level 1400 1000 75
Raised 500mm 1400 800 75

A minimum 75mm thickness refers only to Hebel Block – for solid fuel installations. Minimum 100mm thickness required if poured concrete

Jetmaster-JM-Quadro-Outdoor-Wood-Fire-and-BBQ-Grill-
FIG-16

Quadro Hebel Cutting Plan
Hebel Panels x 8 (1200mm x 600 x 75mm)

  • Base (3): A1 (1200×600) + A2(1200×200) + A3(150×800)
  • Rear (2): B1 (1200×600) + B2(1200×600)
  • Sides RHS (2) : C1 (1200×600) + C2(1200×200)
  • Sides LHS (2): D1(1200×600) + D2(1200×200)
  • Front Face Above Appliance (1): E2(350×1200)
  • Front Face Above Appliance (1) : E1(300×1200)
  • Front Face LHS & RHS (2): F1 (50×850) + F2(50×850)

Remaining black areas are free to be used for packing;

  • 40mm under the appliance
  • 25mm between the hebel cell and framing

IMPORTANT : Read all instructions carefully before starting installation. Failure to follow these instructions may result in a fire hazard and will void the warranty. Due to continued product improvement, The Fireplace Ltd reserves the right to change product specifications without prior notification. Please check to ensure you have the latest installation instructions.