Eterna VECOTWINSP Compact Emergency LED Twinspot Instruction Manual

June 10, 2024
1 by one

Eterna VECOTWINSP Compact Emergency LED Twinspot

Eterna-VECOTWINSP-Compact-Emergency-LED-Twinspot-
PRODUCT

Product Information

  • The Compact Emergency LED Twinspot is a product from Eterna Lighting that comes with a maintenance check record and an LED fitting. It has a battery that can last for three hours in emergency mode. The product is made in China and has the model number VECOTWINSP.
  • The product is designed for indoor use only and must be installed by a competent person following the current building and IEE wiring regulations. It is the responsibility of the buyer, installer, and/or user to ensure that the product is fit for the intended purpose. The batteries supplied with the product are consumable parts and may not be covered by any warranty offered.
  • When making electrical connections, ensure that the terminals are tightened securely, and no wire strands protrude. The luminaire has sealed LED lamps and is maintenance-free. No lamp replacement is required.
  • If the lamp does not remain lit for three hours after routine operation check, a new battery pack may be required.

Product Usage Instructions

  1. Before installation, switch off the mains and remove the appropriate circuit fuse or lock off MCB.
  2. Check that there are no obstructions hidden beneath the mounting surface before making fixing holes.
  3. Ensure that the fitting will be accessible after installation for maintenance and self-testing.
  4. Install the product in accordance with the current building and IEE wiring regulations.
  5. After installation, double-check any electrical connections made during installation.
  6. Carry out electrical tests specified in the current IEE wiring and building regulations.
  7. If the lamp does not remain lit for three hours after routine operation check:
  8. Switch off the electricity at the mains and allow batteries to fully discharge.
  9. Reconnect to the supply and allow charging for 24 hours.
  10. Test again for three hours.
  11. If the light does not remain lit, change the battery pack as follows:
  12. Switch off the electricity at the mains.
  13. Remove the battery pack by releasing the clips and disconnecting the lead.
  14. Replace with a new battery pack.
  15. Reconnect the lead and clips and switch on the electricity at the mains.
  16. Allow charging for 24 hours before testing again for three hours.
  17. To clean the fitting, use a soft dry cloth. Do not use any chemical or abrasive cleaners.
  18. If you experience any problems with the product, return it to the place of purchase. The Technical Team of Eterna Lighting will advise on any product-related issues, but they may not be able to provide specific instructions regarding individual installations.
  19. When disposing of the product, recycle it where facilities exist. Do not dispose of it with household waste.

Pack contents

  • 1 x LED fitting
  • 1 x Maintenance check record
EVENTUALLY, YOU MAY WANT TO REPLACE THIS PRODUCT
  • Regulations require the recycling of Waste from Electrical and Electronic Equipment (European “WEEE Directive” effective August 2005—UK WEEE Regulations effective 2nd January 2007). Environment Agency Registered Producer: WEE/GA0248QZ.
  • WHEN YOUR PRODUCT COMES TO THE END OF ITS LIFE OR YOU CHOOSE TO REPLACE IT, PLEASE RECYCLE IT WHERE FACILITIES EXIST – DO NOT DISPOSE WITH HOUSEHOLD WASTE.

CLEANING:

  • Clean this fitting only with a soft dry cloth. Do not use any chemical or abrasive cleaners.

IF YOU EXPERIENCE PROBLEMS:

  • If you believe your product is defective, please return it to the place where you bought it. Our Technical Team will gladly advise on any Eterna Lighting product, but may not be able to give specific instructions regarding individual installations.

READ THIS FIRST

  • This product must be installed by a competent person in accordance with the current building and IEE wiring regulations.
  • As the buyer, installer and/or user of this product it is your own responsibility to ensure that this fitting is fit for the purpose for which you have intended it. Eterna
  • Lighting cannot accept any liability for loss, damage or premature failure resulting from inappropriate use.
  • Switch off the mains before commencing installation and remove the appropriate circuit fuse or lock off MCB.
  • The batteries supplied with this fitting are consumable parts and therefore may be outside of any warranty offered.
  • This unit is suitable for indoor use only.
  • Before making fixing hole(s), check that there are no obstructions hidden beneath the mounting surface such as pipes or cables.
  • Ensure that the fitting will be accessible after installation for maintenance and self testing.
  • When making connections ensure that the terminals are tightened securely and that no strands of wire protrude. Check that the terminals are tightened onto the bared conductors and not onto any insulation.
  • You are advised at every stage of your installation to double-check any electrical connections you have made. After you have completed your installation there are electrical tests that should be carried out, these tests are specified in the current IEE wiring and building regulations.

LAMP REPLACEMENT

  • This luminaire has sealed LED lamps and is maintenance free, no lamp replacement is required.

BATTERY REPLACEMENT

  • If after routine operation check, the lamp does not remain lit for the three hour period, a new battery pack may be required.
  1. Switch off the electricity at the mains and allow batteries to fully discharge then reconnect to supply and allow charging for 24 hours.
  2. Test again for 3 hours, if light does not remain lit, then change the battery pack as follows:
  3. Unplug the battery lead.
  4. Remove the screws from the back of case that secure the battery pack in place and lift the battery pack out of the fitting.
  5. Write current date on the new battery pack and fit new battery pack securing in place.
  6. Reconnect battery.
  7. Restore power and allow charging for 24 hours.
  8. Perform full operation check and update test record.
REPLACEMENT BATTERY TYPE

3.6V 4Ah NI-CD batteries.

INDUSTRIAL BATTERIES

  1. Within certain products Eterna Lighting Ltd places lead acid, lithium ion, nickel cadmium & nickel metal hydride batteries on the market. Industrial batteries are subject to waste regulation under the Waste Batteries and Accumulators Regulations 2009 and should be disposed of responsibly. Purchasers may be able to dispose of their waste industrial batteries locally via legitimate licensed trade waste contractors. Eterna is obliged
    to take back, free of charge and within a reasonable time, waste industrial batteries of the same chemistry supplied to a Purchaser, for treatment and recycling and is required to do this in any calendar year new industrial batteries are placed on the market. In certain circumstances, this may include batteries not originally supplied by

  2. Eterna. If any Purchaser requires Eterna to take back Industrial batteries, they should write to the Operations Director, Eterna Lighting Ltd, Huxley Close, NN8 6AB, who will then advise on the necessary arrangements for the receipt, proper treatment and recycling of, the waste industrial batteries.

INSTALLATION

Choose the location of your new fitting giving consideration to all of the points listed above.

  1. Unclip and lift off front cover.

  2. Make cable entry hole using an appropriate hole cutter.

  3. Using the back of the fitting as a template, mark and drill out fixing holes on your mounting surface.

  4. Prepare fixing points to mounting surface as appropriate.

  5. Thread the supply cable through the cable entry and into the fitting.

  6. Secure the back of the fitting to the mounting surface using suitable fixings.

  7. Connect the un-switched supply cable to terminals marked L N.
    This product is double insulated. Do not connect any part to Earth.

  8. Mark the current date on the battery pack.

  9. Connect the battery lead.

  10. Refit the front cover.

  11. Restore the power and check fitting is working correctly. Three green LED lights should always be present indicating the fitting is charging and the lamp is healthy.

OPERATION CHECKS
  • Periodic testing should be carried out to ensure emergency lighting is operating correctly. Interruption of the supply, causing the fitting to be energised from the battery, should be carried out by the operation of a local keyswitch or other isolation device.
  • During this period all fittings should be examined visually to ensure that they are functioning correctly. At the end of the test period the supply shall be restored and all indicator lamps or devices checked to ensure that the normal supply has been restored.

DAILY:

  • Visual inspection of the battery charge LED.

EACH MONTH:

  • Isolate the power supply for a period sufficient to ensure that each lamp is illuminated. Endorse the test record form supplied.

ONCE EACH YEAR:

  • Isolate the power supply and check that the light is still illuminated after 3 hours. Endorse the test record form.
  • Because of the possibility of a failure of the normal lighting supply occurring shortly after a period of testing of the emergency lighting system or during the subsequent recharge period, all full duration tests shall wherever possible be undertaken preceding time of low risk to allow for battery recharge.
  • NOTE: please keep this instruction booklet and the test record in a safe place. A fire officer or other authorised person may want to see your record of inspection and testing.

IMPORTANT NOTES:

  • The control gear must be operated only within the enclosure supplied. The gear must not be operated outside of the enclosure.
  • The battery charging circuit and control gear are separated from the mains by at least basic (single layer) insulation.
  • When energised by a constant mains supply, the battery will be constantly charged whether or not the lamp is illuminated. On failure of the constant mains supply, the fitting will switch automatically using transistorised switching from battery charging to battery discharge powering the lamp whether or not the lamp was illuminated before the power failure. Both the mains and battery supplies incorporate fuse protection, see fitting for location and rating.
Product Code: Product Description:

Product Location:
Installation Date:| Installation Test Duration:
Installed By:
Month|

Test

| Year:| Year:| Year:| Year:| Year:
---|---|---|---|---|---|---
Sign| Date| Sign| Date| Sign| Date| Sign| Date| Sign| Date
01| Short|  |  |  |  |  |  |  |  |  |
02| Short|  |  |  |  |  |  |  |  |  |
03| Short|  |  |  |  |  |  |  |  |  |
04| Short|  |  |  |  |  |  |  |  |  |
05| Short|  |  |  |  |  |  |  |  |  |
06| Short|  |  |  |  |  |  |  |  |  |
07| Short|  |  |  |  |  |  |  |  |  |
08| Short|  |  |  |  |  |  |  |  |  |
09| Short|  |  |  |  |  |  |  |  |  |
10| Short|  |  |  |  |  |  |  |  |  |
11| Short|  |  |  |  |  |  |  |  |  |
12| 3 Hour Endurance|  |  |  |  |  |  |  |  |  |