MICRO CONTROL SYSTEMS RM6G1 Series Variable Speed Drive Installation Guide

June 10, 2024
MICRO CONTROL SYSTEMS

RM6G1 Series Variable Speed Drive
Installation GuideMICRO CONTROL SYSTEMS RM6G1 Series Variable Speed
Drive

RM6G1 Series Variable Speed Drive

Any questions regarding this release, contact: [email protected]
Micro Control Systems, Inc. 5580 Enterprise Parkway Fort Myers, Florida 33905
(239)694-0089 FAX: (239)694-0031 www.mcscontrols.com
Information contained in this document has been prepared by Micro Control Systems, Inc. and is copyright © protected 2023.
Copying or distributing this document is prohibited unless expressly approved by MCS.

VFD-R2 / VFD-R4 MODELS RM6G1 Hardwired Diagram

MICRO CONTROL SYSTEMS RM6G1 Series Variable Speed Drive -
Diagram

VFD-R2 / VFD-R4 MODELS
RM6G1 Hardwired VFD SETTINGS

Key features include: Start/Stop, 0-10V Speed Reference, Speed Reference Feedback

RM6G1 Parameters & Values| Parameter Description| Comments

| Value| Comments| Default values in parenthesis (xxxxxx)| Mfg / User

A1-05| DF-HD| Heavy Duty Mode| HD:heavy duty mode| Set mode first HD
A1-04|  | Input Voltage Setting| 100.0~300.0V(220V series) 240.0~500.0V (380V series)| Set to Motor Voltage
A3-16| 0| Display| 0: Disable – Alternately Display|
A3-23| 104| Dual Display| 104 – Left side shows output amps / Right side shows Main Display|
B1-00| 2| Primary Frequency Selection| 2: Analog Input (Vin 1)|
B1-02| 1| Primary Start Command| 1: Digital Input (X1)|
B1-04| 1| Primary

Direction Command

| 1: Digital Input (X1)|
B1-10| 1| Stop Method| 1: Coast to stop|
b1-11| 1| Reverse Operation Selection| 1: Disabled|
C1-01| 10/15| Acceleration Time (sec)| 10 sec – Acceleration Time from Min Frequency to Max Frequency| 15 sec for Centrifugal
C1-02| 10/60| Deceleration Time (sec)| 10 sec -Deceleration Time from Max Frequency to Min Ffrequency| 60 sec for Centrifugal
D2-02| 0.50| Frequency Lower Limit (%)| 0.50 = 50%| 0.70=70% for Centrifugal
E1-01| Maximun Output Voltage Based on Motor Voltage| 0.0-300.0V (220V series)

0.0~550.0V (380V series)

| Set to Motor Votage
E1-03| Base Voltage| 0.0-300.0V (220V series)

0.0~550.0V (380V series)

| Set to Base Voltage

E2-01

| Model 200V| 010| 016| 022| 031| 042| 060| 075| 090| 112| 150| 185| 220| 275| 346| 410| 500| 700| 840|
Rated Output (A)| 8| 11| 17| 25| 33| 46| 63| 75| 90| 115| 150| 185| 220| 295| 346| 432| 585| 700
Model 400V| 009| 012| 018| 023| 031| 039| 045| 058| 075| 091| 110| 144| 180| 216| 253| 304| 377| 415| 480| 585| 700| 860| 960
Rated Output (A)| 6| 9| 14| 18| 24| 30| 39| 45| 61| 75| 91| 115| 150| 180| 216| 253| 310| 377| 432| 480| 585| 700| 866
H1-00| +2| Multi-Function Input Terminal (X1)| +2 FWD Command (X1)

VFD-R2 / VFD-R4 MODELS RM6G1 MODBUS VFD SETTINGS

MICRO CONTROL SYSTEMS RM6G1 Series Variable Speed Drive - Diagram
1

VFD-R2 / VFD-R4 MODELS RM6G1 MODBUS VFD SETTINGS

Key features include: Start/Stop, 0-10V Speed Reference, Speed Reference Feedback

RM6G1 Parameters & Values| Parameter Description| Comments

| Value| Comments| Default values in parenthesis (xxxxxx)| Mfg / User

A1-05| DF-HD| Heavy Duty Mode| HD:heavy duty mode| Set mode first HD
A1-04|  | Input Voltage Setting| 100.0~300.0V(220V series) 240.0~500.0V (380V series)| Set to Motor Voltage
A3-16| 0| Display| 0: Disable – Alternately Display|
A3-23| 104| Dual Display| 104 – Left side shows output amps / Right side shows Main Display|
B1-00| 3| Primary Frequency Selection| 3: Modbus Communications|
B1-02| 2| Primary Start Command| 2: Modbus Communications|
B1-04| 2| Primary Direction Command| 2: Modbus Communications|
B1-10| 1| Stop Method| 1: Coast to stop|
b1-11| 1| Reverse Operation Selection| 1: Disabled|
C1-01| 10/15| Acceleration Time (sec)| 10 sec – Acceleration Time from Min Frequency to Max Frequency| 15 sec for Centrifugal
C1-02| 10/60| Deceleration Time (sec)| 10 sec -Deceleration Time from Max Frequency to Min Ffrequency| 60 sec for Centrifugal
D2-02| 0.50| Frequency Lower Limit (%)| 0.50= 50%| 0.70=70%
for Centrifugal
E1-01| Maximun Output Voltage Based on Motor Voltage| 0.0-300.0V (220V series)
0.0~550.0V (380V series)| Set to Motor Votage
E1-03| Base Voltage| 0.0-300.0V (220V series)
0.0~550.0V (380V series)| Set to Base Voltage

E2-01

| Model 200V| 010| 016| 022| 031| 042| 060| 075| 090| 112| 150| 185| 220| 275| 346| 410| 500| 700| 840|
Rated Output (A)| 8| 11| 17| 25| 33| 46| 63| 75| 90| 115| 150| 185| 220| 295| 346| 432| 585| 700
Model 400V| 009| 012| 018| 023| 031| 039| 045| 058| 075| 091| 110| 144| 180| 216| 253| 304| 377| 415| 480| 585| 700| 860| 960
Rated Output (A)| 6| 9| 14| 18| 24| 30| 39| 45| 61| 75| 91| 115| 150| 180| 216| 253| 310| 377| 432| 480| 585| 700| 866
H1-00| -22| Multi-Function Input Terminal (X1)| -22 FWD External Fault – Interlock Relay|
H5-00| 1| Comm. Address| 1: Modbus Address|
H5-01| 38400| Baud Rate| 38400 Baud Rate on Modbus Communication|
H5-04| 2| Comm. Overtime Disposal (COT)| 2: Keep Running on Loss of Communication (Interlock will stop VFD)|
H5-05| 5| Comm. Overtime(COT)| 0.0 ~ 100.0 sec – Time Out|

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MICRO CONTROL SYSTEMS User Manuals

Related Manuals