MICRO CONTROL SYSTEMS RM6G1 Series Variable Speed Drive Installation Guide
- June 10, 2024
- MICRO CONTROL SYSTEMS
Table of Contents
- RM6G1 Series Variable Speed Drive
- VFD-R2 / VFD-R4 MODELS RM6G1 Hardwired Diagram
- | Value| Comments| Default values in parenthesis (xxxxxx)| Mfg / User
- VFD-R2 / VFD-R4 MODELS RM6G1 MODBUS VFD SETTINGS
- | Value| Comments| Default values in parenthesis (xxxxxx)| Mfg / User
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
RM6G1 Series Variable Speed Drive
Installation Guide
RM6G1 Series Variable Speed Drive
Any questions regarding this release, contact:
support@mcscontrols.com
Micro Control Systems, Inc. 5580 Enterprise Parkway Fort Myers, Florida 33905
(239)694-0089 FAX: (239)694-0031
www.mcscontrols.com
Information contained in this document has been prepared by Micro Control
Systems, Inc. and is copyright © protected 2023.
Copying or distributing this document is prohibited unless expressly approved
by MCS.
VFD-R2 / VFD-R4 MODELS RM6G1 Hardwired Diagram
VFD-R2 / VFD-R4 MODELS
RM6G1 Hardwired VFD SETTINGS
Key features include: Start/Stop, 0-10V Speed Reference, Speed Reference Feedback
RM6G1 Parameters & Values| Parameter Description| Comments
| Value| Comments| Default values in parenthesis (xxxxxx)| Mfg / User
A1-05| DF-HD| Heavy Duty Mode| HD:heavy duty mode| Set mode first HD
A1-04| | Input Voltage Setting| 100.0~300.0V(220V series) 240.0~500.0V (380V
series)| Set to Motor Voltage
A3-16| 0| Display| 0: Disable – Alternately Display|
A3-23| 104| Dual Display| 104 – Left side shows output amps / Right side shows
Main Display|
B1-00| 2| Primary Frequency Selection| 2: Analog Input (Vin 1)|
B1-02| 1| Primary Start Command| 1: Digital Input (X1)|
B1-04| 1| Primary
Direction Command
| 1: Digital Input (X1)|
B1-10| 1| Stop Method| 1: Coast to stop|
b1-11| 1| Reverse Operation Selection| 1: Disabled|
C1-01| 10/15| Acceleration Time (sec)| 10 sec – Acceleration Time from Min
Frequency to Max Frequency| 15 sec for Centrifugal
C1-02| 10/60| Deceleration Time (sec)| 10 sec -Deceleration Time from Max
Frequency to Min Ffrequency| 60 sec for Centrifugal
D2-02| 0.50| Frequency Lower Limit (%)| 0.50 = 50%| 0.70=70% for Centrifugal
E1-01| Maximun Output Voltage Based on Motor Voltage| 0.0-300.0V (220V series)
0.0~550.0V (380V series)
| Set to Motor Votage
E1-03| Base Voltage| 0.0-300.0V (220V series)
0.0~550.0V (380V series)
| Set to Base Voltage
E2-01
| Model 200V| 010| 016| 022| 031| 042| 060| 075| 090| 112| 150| 185|
220| 275| 346| 410| 500| 700| 840|
Rated Output (A)| 8| 11| 17| 25| 33| 46| 63| 75| 90| 115| 150| 185|
220| 295| 346| 432| 585| 700
Model 400V| 009| 012| 018| 023| 031| 039| 045| 058| 075| 091| 110| 144|
180| 216| 253| 304| 377| 415| 480| 585| 700| 860| 960
Rated Output (A)| 6| 9| 14| 18| 24| 30| 39| 45| 61| 75| 91| 115|
150| 180| 216| 253| 310| 377| 432| 480| 585| 700| 866
H1-00| +2| Multi-Function Input Terminal (X1)| +2 FWD Command (X1)
VFD-R2 / VFD-R4 MODELS RM6G1 MODBUS VFD SETTINGS
VFD-R2 / VFD-R4 MODELS RM6G1 MODBUS VFD SETTINGS
Key features include: Start/Stop, 0-10V Speed Reference, Speed Reference Feedback
RM6G1 Parameters & Values| Parameter Description| Comments
| Value| Comments| Default values in parenthesis (xxxxxx)| Mfg / User
A1-05| DF-HD| Heavy Duty Mode| HD:heavy duty mode| Set mode first HD
A1-04| | Input Voltage Setting| 100.0~300.0V(220V series) 240.0~500.0V (380V
series)| Set to Motor Voltage
A3-16| 0| Display| 0: Disable – Alternately Display|
A3-23| 104| Dual Display| 104 – Left side shows output amps / Right side shows
Main Display|
B1-00| 3| Primary Frequency Selection| 3: Modbus Communications|
B1-02| 2| Primary Start Command| 2: Modbus Communications|
B1-04| 2| Primary Direction Command| 2: Modbus Communications|
B1-10| 1| Stop Method| 1: Coast to stop|
b1-11| 1| Reverse Operation Selection| 1: Disabled|
C1-01| 10/15| Acceleration Time (sec)| 10 sec – Acceleration Time from Min
Frequency to Max Frequency| 15 sec for Centrifugal
C1-02| 10/60| Deceleration Time (sec)| 10 sec -Deceleration Time from Max
Frequency to Min Ffrequency| 60 sec for Centrifugal
D2-02| 0.50| Frequency Lower Limit (%)| 0.50= 50%| 0.70=70%
for Centrifugal
E1-01| Maximun Output Voltage Based on Motor Voltage| 0.0-300.0V (220V series)
0.0~550.0V (380V series)| Set to Motor Votage
E1-03| Base Voltage| 0.0-300.0V (220V series)
0.0~550.0V (380V series)| Set to Base Voltage
E2-01
| Model 200V| 010| 016| 022| 031| 042| 060| 075| 090| 112| 150| 185|
220| 275| 346| 410| 500| 700| 840|
Rated Output (A)| 8| 11| 17| 25| 33| 46| 63| 75| 90| 115| 150| 185|
220| 295| 346| 432| 585| 700
Model 400V| 009| 012| 018| 023| 031| 039| 045| 058| 075| 091| 110| 144|
180| 216| 253| 304| 377| 415| 480| 585| 700| 860| 960
Rated Output (A)| 6| 9| 14| 18| 24| 30| 39| 45| 61| 75| 91| 115|
150| 180| 216| 253| 310| 377| 432| 480| 585| 700| 866
H1-00| -22| Multi-Function Input Terminal (X1)| -22 FWD External Fault –
Interlock Relay|
H5-00| 1| Comm. Address| 1: Modbus Address|
H5-01| 38400| Baud Rate| 38400 Baud Rate on Modbus Communication|
H5-04| 2| Comm. Overtime Disposal (COT)| 2: Keep Running on Loss of
Communication (Interlock will stop VFD)|
H5-05| 5| Comm. Overtime(COT)| 0.0 ~ 100.0 sec – Time Out|