TOSHIBA TE-B Configured Soft Start Packages User Guide
- June 10, 2024
- Toshiba
Table of Contents
TOSHIBA TE-B Configured Soft Start Packages
Manual Addendum for TE-B Configured Soft Start Packages
For use with wiring diagram # 93-4014 Rev A (CB/FS), or 93-4015 Rev A (MLO),
and TE2 instruction manual.
Introduction: The TE-B is a configured enclosed soft start, available as a
Combination (with C/B or Fused disconnect) package, or as an MLO (Main Lug
Only) package, intended for use in Industrial, Commercial, Agricultural, or
Infrastructure applications.
Line Voltage:
By default, units are set-up for 460VAC line power, but can be adjusted to
operate on 230VAC or 208VAC at the reduced HP rating. To adjust the operating
voltage simply move wire #1L2B from the 480V (H4) terminal to the 230V (H3) or
208V (H2) terminal.
Power Connections:
Line Power input is connected directly to the bottom terminals of the Circuit
Breaker, or line terminals on MLO (Main Lug Only) units, and the motor is
connected to the lugs at the bottom of the TE2 soft start.
Remote Start / Stop Control connections:
The TE-B is set up for 2 or 3 wire remote control using dry contacts rated at
120VAC (0.1Amp).
Remote Two Wire Control:
Connect a dry (voltage free) maintained contact closure between terminals 1
and 3 of the customer terminal strip as shown here.
Remote Three Wire Control:
For standard 3-wire control, connect dry (voltage free) contacts for the Stop
/ Start buttons as shown below of the customer terminal strip. Connect the
normally closed “STOP” pushbutton across terminals 1 & 2, and the normally
open “START” pushbutton across terminals 2 & 3 of the customer terminal strip.
Note: the unit can be operated in the “Local” position without any external
control.
Run Status Output Contacts
The TE-B unit offers 2 Form-C (N.O and N.C.) “RUN” contacts located on the
customer terminal strip, terminals 4 (NC), 5 (NO), 6 (Common), and terminals 7
(NC), 8 (NO) 9 (Common). These contacts reflect a successful RUN command in
“SOFT” or “X-LINE” mode, and should be used for any required “Run / Running”
status outputs.
TE2 Auxiliary Contacts (TB2 of Soft Starter)
There are 3 programmable Aux contacts available on TB2 of the TE2 soft start
(2 form-C and 1 form-A). The function of these contacts are labeled on the
wiring diagrams, but can be changed in the TE2
programming. Note however, that the contacts may not function properly when
operating in the X-LINE mode. (see description below).
X-LINE Operation:
TE-B packages are supplied with a SOFT/X-LINE selector switch, located on the
TCB3000 PCB that allows the operator to select Full Voltage operation of the
motor via the bypass contactor for emergency operation when the soft start may
be inoperable.
When operated in the X-LINE mode full
start/stop control is maintained, and the “Run Status Output Contacts” will
function correctly.
During X-LINE operation, the motor will be protected by the external Bi-Metal
overload relay which must be set according to the motor FLA and the Current
transformer ratio of the unit.
Important:
Motor FLA and Service Factor must be entered prior to a start attempt see next
section on how to set Motor FLA and Service Factor parameters.
OVERLOAD RELAY OPERATION
WHEN IN HAND (H) POSITION: USER MUST RESET OL (BY PUSHING GREEN BUTTON) WHEN IN AUTO (A) POSITION: RELAY WILL AUTOMATICALLY RESET AFTER TRIPPING
|
NOTE: YELLOW OVERLOAD DIAL MUST BE SET IN ACCORDANCE WITH THE MOTOR “FULL LOAD AMPS” PER MOTOR NAME PLATE DATA
YELLOW OVERLOAD ADJUSTMENT DIAL
TE-B MODEL NUMBER| CT RATING XXX:5|
4
|
5
|
6
TE-B-21-YY-4| 18-25A| 18| 22| 25
TE-B-27-YY-4| 28-40A| 28| 34| 40
TE-B-40-YY-4| 34-50A| 34| 42| 50
TE-B-45-YY-4| 50:5| 40| 50| 60
TE-B-55-YY-4| 75:5| 60| 75| 90
TE-B-68-YY-4| 75:5| 60| 75| 90
TE-B-96-YY-4| 100:5| 80| 100| 120
TE-B-125-YY-4| 120:5| 96| 120| 144
TE-B-156-YY-4| 200:5| 160| 200| 240
TE-B-220-YY-4| 200:5| 160| 200| 240
TE-B-230-YY-4| 250:5| 200| 250| 300
TE-B-248-YY-4| 300:5| 240| 300| 360
TE-B-400-YY-4| 400:5| 320| 400| 480
TE-B-480-YY-4| 500:5| 400| 500| 600
TE-B-600-YY-4| 500:5| 400| 500| 600
TE-B-690-YY-4| 700:5| 560| 700| 840
TE-B-800-YY-4| 700:5| 560| 700| 840
TE-B-960-YY-4| 1000:5| 800| 1000| 1200
TE-B-1080-YY-4| 1200:5| 960| 1200| N/A
Programming Instructions
This document is intended for use with Models: TE-B Soft Start Packages Motor FLA and Service Factor must be entered prior to start attempt Entering Motor FLA & SF.
Fn # | Function Description | Range | Default |
---|---|---|---|
F001 | Motor Nameplate FLA | 50-100% of Max Amp Rating. | None |
F002 | Motor Nameplate Service Factor | 1.00 – 1.30 SF | 1.0 SF |
For complete parameter list see pages 6-7 of this document
For Complete Installation instructions see TE2 Instruction Manual
Operation and Troubleshooting
Keypad Operation Display Mode (Default) : Fault Mode
Fault Code | Description |
---|---|
nFLA | No Full Load Amps set in F001 |
Inh | Parameter change attempted when in Run Mode or without password |
N3Ph | Line Voltage Loss (no 3 phase prior to start) |
Loc | Lockout Starter is in overload or duty cycle lockout |
Err | Incorrect Password Entered |
ocA; occ: ocd | Over Current during Acceleration; Constant speed; Deceleration |
PLA; PLc; PLd* | Phase Loss during Acceleration; Constant speed; |
Deceleration
otA; otc; otd| Over Temperature during Acceleration; Constant speed;
Deceleration
oLA; oLc; oLd| Over Load during Acceleration; Constant speed; Deceleration
SSA; SSc; SSd| Shorted SCR during Acceleration; Constant speed; Deceleration
st| Shunt Trip during Acceleration; Constant speed; Deceleration
IbA; Ibc; Ibd| Current Imbalance during Acceleration; Constant speed;
Deceleration
UcA; Ucc; Ucd| Under Current during Acceleration; Constant speed; Deceleration
ScA; Scc; Scd| Short Circuit during Acceleration; Constant speed; Deceleration
GFA; GFc; GFd| Ground Fault during Acceleration; Constant speed; Deceleration
bPA; bPc; bPd| Bypass Discrepancy during Acceleration; Constant speed;
Deceleration
LcA; Lcc; Lcd| Normally closed external lockout is open
rtA; rtc; rtd| Rotation Trip during Acceleration; Constant speed; Deceleration
EIA; EIc; EId| Voltage Imbalance during Acceleration; Constant speed;
Deceleration
oEA; oEc; oEd| Overvoltage during Acceleration; Constant speed; Deceleration
UEA; UEc; UEd| Under voltage during Acceleration; Constant speed; Deceleration
PFA; PFc; PFd| Power Factor trip during Acceleration; Constant speed;
Deceleration
PrA; Prc; Prd| Power (kW) trip during Acceleration; Constant speed;
Deceleration
ncPA; ncPc; ncPd| Control Power Loss during Acceleration; Constant speed;
Deceleration
- NOTES :
“PLd” can be caused by a Grounded delta power system. If one input leg measures ZERO volts to ground, reduce
the setting of F051 to “0054” for operation on a “Grounded Delta”.
“SSd” can be caused by operating without a motor connected, ensure the motor is firmly connected.
“LcA, Lcc, or LCD” indicates that the Surge absorber is damaged; see NOTE 1 on wiring diagram.
Full Parameter List
Parameter| Description| Adjustment Range| Factory
Setting
F001| Motor FLA| 50-100% of Max Amp Rating (less Service Factor)| 0
F002| Motor Service Factor| 1.00-1.30| 1.00
F003| Overload Class During Start| NEMA/UL Class 5-30| 10
F004| Overload Class During Run| NEMA/UL Class 5-30| 10
F005| Overload Reset| 0=Manual, 1=Auto, 2=Disabled| 0:Manual
F10
| ****
Ramp Type (If Ramp 2 is not being used, unit will ignore all settings referenced to Ramp 2)
| ****
Ramp #1 Ramp #2
| ****
1
Setting = 1
Setting = 2
Setting = 3
Setting = 4
| Voltage Voltage
Current Current
Voltage Current
Current Voltage
F011| Initial Voltage of Ramp 1| 0-100% Line Voltage| 60%
F012| Initial Current of Ramp 1| 0-600% Motor Current| 200%
F013| Accel Ramp Time of Ramp 1| 1-120 seconds| 10 sec
F014| Max Current Limit of Ramp 1| 200 – 600% Motor Current| 350%
F015| Initial Voltage of Ramp 2 (if Ramp 2 is used)| 0-100% Line Voltage| 60%
F016| Initial Current of Ramp 2 (if Ramp 2 is used)| 0-600% Motor Current|
200%
F017| Accel Ramp Time of Ramp 2 (if Ramp 2 is used)| 1-120 seconds| 10Sec.
F018| Max Current Limit of Ramp 2 (if Ramp 2 is used)| 200 – 600% Motor
Current| 350%
F019| Voltage Jog| 5-100% Line Voltage| 50%
F020| Time of Voltage Jog| 1-20 seconds| 10 sec
F021| Current Jog| 100-500% Motor Current| 150%
F022| Kick Start Voltage| 0=Disabled or 10-100% Line Voltage| 0
F023| Kick Time| 0.1-2 seconds| 0.8 sec
F024| ****
Deceleration Ramp (Pump Control)
| 0=Disabled (Coast to Stop) 1=Enabled (except after OL trip)
2=Enabled (Deceleration even during O/L trip)
| ****
0
F025| Begin Decel Level (BDL)| 0 – 100 % of Output Voltage| 60%
F026| Decel Shut Off Voltage| 0 to (BDL minus 1)% Voltage| 30%
F027| Decel Ramp Time| 1-60 seconds| 10Sec.
F028| Auto Restart Delay Time| 0=Disabled or 1-999sec after Power Loss| 0
F029| Voltage Input| 200 – 690 Volt| 480
F030| Voltage Imbalance Trip %| 0, 1 – 30% [0=Disabled]| 0
F031| Voltage Imbalance Trip Delay| 1 – 20 seconds| 10
F032| Over Voltage Trip %| 0, 1 – 10% [0=Disabled]| 0
F033| Over Voltage Trip Delay| 1 – 20 seconds| 10
F034| Under Voltage Trip on Start %| 0, 1 – 20% [0=Disabled]| 0
F035| UV Trip on Start Delay| 1 – 180 seconds| 10
F036| Under Voltage Trip on Run %| 0, 1 – 20% [0=Disabled]| 0
F037| UV Trip Delay during Run| 1 – 20 seconds| 2
F038| Shorted SCR and Trip Delay| 0, 1-10 seconds [0=Disabled]| 1Sec
F039| Shunt Trip Delay| 0, 1-10 seconds [0=Disabled]| 1Sec
F040| Current Imbalance Trip %| 0=Disabled or 5-30% imbalance| 0
F041| Current Imbalance Trip Delay| 1-20 seconds| 2 sec
F042| Over Current Trip %| 0=Disabled or 100-300% of Motor FLA| 0
F043| Over Current Trip Delay| 1-20 seconds| 1 sec
F044| Under Current %| 0=Disabled or 10-90% of Motor FLA| 0
F045| Under Current Trip Delay| 1-60 seconds| 2 sec
F046| Ground Fault Current Trip Value| 0=Disabled or 5-90% of CT ratio from
Fn74| 0
F047| Ground Fault Current Trip Delay| 1-60 seconds| 2 sec
F048| Coast Down Lockout Time| 0=Disabled or 1-60 minutes| 0
F049| Maximum Starts per Hour| 0=Disabled or 1-10 Starts| 0
F050| Minimum Time Between Starts| 0=Disabled or 1-60 minutes| 0
F051| nCP Trip (No Control Power)| 0, 1 [0=Disabled, 1=Enabled]| 1
Parameter| Description| Adjustment Range| Factory
Setting
---|---|---|---
F052
| ****
Auto Reset Selected Trips
| Auto Reset Disabled| 0
Reset after Over Temperature Trip only Reset after Over Current (Shear Pin)
Trip only
Reset after Under Current Trip only Reset after Phase Loss Trip only
Reset after Current Unbalance Trip only Reset after Ground Fault Trip only Reset after Short Circuit Trip only
Reset after OT Trip or Over/Under Current Trip
Reset after Phase Loss, Current Unbal, or GF Trip Reset after all Except Short Circuit Trip
Reset after all Except GF or Short Circuit Trip Reset after any Trip
| 1
2
3
4 (Default)
5
6
7
8
9
10
11
12
F053| Auto Restart Attempts| 0=Disabled, 1-10 = # of Attempts| 0
F054| Auto Restart Delay Readout| Readout only|
F055| Coast Down Lockout Time Readout| Readout only|
F056| Starts Per Hour Timer Readout| Readout only|
F057| Starts Per Hour Readout| Readout only|
F058| Time Value Between Starts Readout| Readout only|
F059| Thermal Capacity to Start Readout| Readout only|
F060| Aux Relay 1 setting| Run/Stop| 1
F061| Aux Relay 2 setting| At Speed/Stop| 2
F062| Aux Relay 3 setting| Any Trip| 22
F063| Aux. Relay Delay Timer| 0=Disabled or 1-999 seconds| 0
F065
| ****
Communications
| 0=Disabled 1=Enabled(11bit) 2=Enabled(10 bit)| ****
0:Disabled
F066| Baud Rate| 4.8, 9.6, 19.2 KB| 9.6
F067| Modbus Address| 1-247| 1
F068
| ****
Remote Starter Control from Communications
| 0=Disabled 1=Enabled w/Start PB 2=Enabled w/o Start PB
3=Enabled via Remote Jog Input
| ****
0
F070| Parameter Lock/ Level 1 Password| 0=Disabled or 001-999| 0
F071| System Clear / Factory Reset| 0=Disabled, 1=Clear Lockouts 2=Reset to
Factory Default| 0
F073| Frame Rating| 10-2000A| by model
F074| CT Value| 10-2000| by model
F075| Year| 2000-2047| 2000
F076| Month| 1-12| 1
F077| Day| 1-31| 1
F078| Hour| 0-23| 0
F079| Minute| 0-59| 0
F080| Seconds| 0-59| 0
F081| Software rev # (info purposes only)| rev #| Rev #
F085
| ****
Fault History #1 (most recent fault code)
| 0=No Fault History, or Fault # 1-27 (full manual for fault code
descriptions)| 0
F086| Time Stamp Fault #1| 00.00-23.59 (hh.mm)| 00.00
F087| Date Stamp Fault #1| 01.01-12.31 (MM-DD)| 01.01
F088
| ****
Fault History #2 (previous fault code)
| 0=No Fault History, or Fault # 1-27 (full manual for fault code
descriptions)| 0
F089| Time Stamp Fault #2| 00.00-23.59 (hh.mm)| 00.00
F090| Date Stamp Fault #2| 01.01-12.31 (MM-DD)| 01.01
F091
| ****
Fault History #3 (oldest fault code)
| 0=No Fault History, or Fault # 1-27 (full manual for fault code
descriptions)| 0
F092| Time Stamp Fault #3| 00.00-23.59 (hh.mm)| 00.00
F093| Date Stamp Fault #3| 01.01-12.31 (MM-DD)| 01.01
F094| Run Time Hours| 000.9-999.9 hours| 0000
TE-B Door Mounted Operators
Illuminated E-Stop Pushbutton
- Removes control power from all circuits and TE2 soft start.
- Push to activate, twist and pull to release.
- Button Lights when E-stop is pressed.
Start/Stop Pushbutton and Run Light Assembly
- Provides Start/Stop control in “Local” mode.
- Provides “Motor Running” indication in all operating modes.
Local/Off/Remote Selector
- Local” selects door mounted Start/Stop control.
- Remote” selects Start/Stop control from customer supplied signals at terminals 1-3 on TBC.
- Off’ Turns motor off.
Power ON Light
- Indicates presence of 120VAC control power, derived from main (L1 & L2) line voltages.
Fault Light/Reset Pushbutton
- When lit, indicates that the unit has tripped, and requires “Reset”.
- In “Soft” (normal) mode, the “trip” will be displayed on the TE2 keypad (inside), and will reset upon activation of the reset pushbutton.
- In “X-Iine” mode, the light indicates that the X-line overload inside the panel is tripped, and must be reset manually by pressing the (green) reset key on the overload itself. Then the unit can be reset, using the pushbutton on the door.
Note: If the green reset key on the X-line overload is turned to the “A” (auto) position, the O/L relay will reset itself after the required cooldown, after that the unit can be reset by pushing the reset pushbutton without opening the enclosure door.
Wiring Diagram # 93-4014
Wiring Diagram # 93-4015