Mircom MGC-CONFIG-KIT4 Secutron Fire Alarm Control Panels and Voice Evacuation System Instructions
- June 10, 2024
- Mircom
Table of Contents
CONFIG-KIT4 Secutron Fire Alarm Control Panels and Voice Evacuation System
Instructions
Contents of the Kit
Name | Photo | Description |
---|---|---|
UIMA4 interface | • For configuring the following products: |
• FleX-Net™ and FleX-Net™ FX-4000
• FA-300
• FX-350
• FX-2000
• FX-3500
• FX-3318
• QX-5000
•UDACT-300
• MR-2300 and MR-2350
• MMX™
• For use with the FleX-Net™ MP Upgrade Wizard
• Includes one replacement 10 pin cable
UIMA4
9 pin male to female serial
cable| | • For use with the FleX-Net™ MP Upgrade Wizard to connect the UIMA4
interface to FleX-Net™, FleX-Net™ FX-4000, MMX™, RAXN-LCD(G) and RAXN-
4000LCD(G)
MD-508
10 to 8 Pin Adapter| | • For use with the FleX-Net™ MP Upgrade Wizard to
connect the UIMA4 interface to ANC-5000, ANC-4000 and ALCN-792M
RPL-MD-1211
USB A to B Male Cable| | • For use with the following products:
• FX-400 and FX-401
• FX-3500
• FX-3318
•QX-mini
• AUDMAX-MASTER
• ALCN-792MISO and ALCN-4792MISO
• ALCN-960MISO
WC-100011
UIMA4 Driver Installation
Instructions| | • Refer to this manual for instructions on installing the
drivers for the UIMA4 interface
LT-6231
FleX-Net™ MP Upgrade Wizard Manual| | • Refer to this manual for instructions
on using the FleX-Net™ MP Upgrade Wizard
LT-6232
The UIMA4 Interface
The UIMA4 interface has 3 connectors.
- 9 pin male serial connector for connecting the UIMA4 to the 9 pin male to female serial cable and then to the RS-232 serial port on some products
- USB B female connector for connecting the UIMA4 to the USB A to B male cable and then to the computer
- 10 pin female connector for connecting the UIMA4 to the configuration port or debug interface on some productsThe 10 pin cable can be disconnected and replaced if necessary. This kit includes one replacement cable. If you need more replacement cables, use the Mircom part number RPL-WC-25022.
2.1 To disconnect the 10 pin cable
- Insert a small flathead screwdriver in one of the grooves on the side of the case, then turn the screwdriver to open the case.
- Disconnect the 10 pin cable from the board (see picture below).
Install Software
3.1 Install UIMA4 Driver
Refer to the included manual LT-6231 for instructions on installing the driver
for the UIMA4 interface.
Connections for Configuration
Attention: Always connect the UIMA4 interface to the computer first,
before connecting it to the fire alarm product.
4.1 Computer to FleX-Net™, FleX-Net™ FX-4000, MMX™, FA-300, FX-350,
FX-2000, MR-2300, MR-2350, QX-5000, UDACT-300A, DTC-300A, DTC-300A-2
See the table below for the connector designation that the 10 pin UIMA4 connects to.
Panel | Connector |
---|---|
FleX-Net™ | P3 on FIeX-Net™ main board and on ALCN-792M(ISO), P4 on ALC-386S, |
and P10 on ANC-5000
FIeX-Net™ FX-4000| P3 on the FIeX-Net™ FX-4000 main board, ALCN-4792MISO and
ALCN-960MISO, and P10 on ANC-4000
MMXT”| P3 on MMXTM main board and on ALCN-792M(ISO), P4 on ALC-386S, and P10
on ANC-5000
FA-300| P9
FX-350| P5
FX-2000| P3 on FX-3500 main board, P4 on ALC-386S, ALC-198S, and ALC-H16
MR-2300| P9
MR-2350| P5
QX-5000| J9 on 01F-5000B
U DACT-300A, DTC-300A, DTC-300A-2| P2
4.2 Computer to FX-400, FX-401, FX-3500, FX-3500RCU, FX-3318, MR-3500, MR- 3500RCU, MR-3318, QX-mini, AUDMAX-MASTER
Connect the cable to the USB port on the main board.
Connections for the FleX-Net™ MP Upgrade Wizard
Attention: Always connect the UIMA4 interface to the computer first,
before connecting it to the fire alarm product.
Note: Refer to the included manual LT-6232 for instructions on using the
FleX-Net™ MP Upgrade Wizard.
5.1 Main CPU on FX-2000N, FX-4000N and MMX-2000N Series Panels
On FX-4000N boards, turn switch 7 of SW2 ON and switch 8 of SW2 OFF in order
to use the FleX-Net™ MP Upgrade Wizard. After the firmware upgrade is
complete, turn both switch 7 and switch 8 OFF.
5.2 RAXN-LCD(G) and RAXN-4000LCD(G) Remote Annunciator
5.3 ANC-5000 and ANC-4000 Audio Controller
5.4 ALCN-792M Loop Controller
5.5 ALCN-792MISO, ALCN-4792MISO and ALCN-960MISO Loop Controllers
We want your feedback!
Please let us know how we can improve your experience with the UIMA4
interfaces.
Mircom
25 Interchange Way
Vaughan, ON L4K 5W3
Canada
Tel: 1-888-647-2665
http://www.mircom.com
LT-6230 Rev 2 January 2022
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>