Penn TC3B22 Basic Defrost Controller European Installation Guide
- June 10, 2024
- PENN
Table of Contents
- Penn TC3B22 Basic Defrost Controller European
- Instruction
- MEASUREMENTS AND INSTALLATION
- ELECTRICAL CONNECTION
- FIRST-TIME
- UI AND MAIN FUNCTIONS
- ADDITIONAL FUNCTIONS
- SETTINGS
- ALARMS
- ELECTRICAL RATINGS
- TECHNICAL SPECIFICATIONS
- PRODUCT WARRANTY
- SOFTWARE TERMS
- SINGLE POINT OF CONTACT
- CONTACT INFORMATION
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Penn TC3B22 Basic Defrost Controller European
Instruction
Figure 1: UI
Figure 2: Dimensions, mm (in.)
Figure 3: Drilling template, mm (in.)
Figure 4: Electrical connection
- Controller for normal and low temperature units
- Power supply for TC3B22N7x: 230 VAC
- Cabinet probe and auxiliary probe with a negative temperature coefficient (NTC)
- Door switch or multi-purpose input
- Cooling or heating operation
MEASUREMENTS AND INSTALLATION
For the dimensions and drilling template, see Figure 2 and Figure 3. Fit the controller to a panel with the snap-in brackets supplied.
INSTALLATION PRECAUTIONS
- Ensure that the thickness of the panel is between 0.8 mm and 2.0 mm (1/32 and 1/16 in)
- Ensure that the working conditions are within the limits stated in TECHNICAL SPECIFICATIONS.
- Do not install the device close to heat sources, equipment with a strong magnetic field, in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations or shocks.
- In compliance with safety regulations, install the device correctly to ensure adequate protection from contact with electrical parts. Fix all protective parts in such a way so as to need the aid of a tool to remove them.
ELECTRICAL CONNECTION
Important
- Use cables of an adequate wire gauge for the current running through them.
- To reduce any electromagnetic interference, connect the power cables as far away as possible from the signal cables.
For the electrical connection diagram, see Figure 4.
Electrical connection diagram callouts
Callout | Description |
---|---|
A | Note: Maximum 10 A |
B | Compressor |
C | Evaporator fans, configurable |
D | Door switch or multi-purpose |
E | Cabinet |
F | Auxiliary, configurable |
G | Power supply for TC3B22N7x: 230 VAC |
PRECAUTIONS FOR ELECTRICAL CONNECTION
- If you use an electrical or pneumatic screwdriver, adjust the torque to a maximum of 0.5 N•m (4 in. lb).
- If you move the device from a cold to a warm place, the humidity may cause condensation to form inside. Wait an hour before you switch on the power.
- Make sure that the supply voltage, electrical frequency, and power are within the set limits. See TECHNICAL SPECIFICATIONS.
- Disconnect the power supply before you do any type of maintenance.
- Do not use the device as safety device.
- For repairs and further information, contact the Penn sales network.
FIRST-TIME
- Follow the instructions in MEASUREMENTS AND INSTALLATION to install the controller.
- Power up the device as shown in ELECTRICAL CONNECTION and an internal test runs. The test normally takes a few seconds. When it finishes the display switches off.
- Configure the device as shown in Table 6.1 in SETTINGS.
For recommended configuration parameters for first-time use, see the following table. DEF. PARAMETER MIN. – MAX.PAR.| DEF.| PARAMETER| MIN. – MAX.
---|---|---|---
SP| 0.0| Setpoint| r1 to r2
P2| 0| Temperature unit of measurement| 0 = °C 1 = °F
d1| 0| Defrost type| 0 = Electric 1 = Hot gas
2 = Compressor stopped
Check that the remaining settings are appropriate; see CONFIGURATION PARAMETERS.
- Disconnect the device from the mains.
- Make the electrical connection as shown in ELECTRICAL CONNECTION without powering up the device.
- Power up the device.
UI AND MAIN FUNCTIONS
For a figure of the UI, see Figure 1.
UI callouts
Callout | Description |
---|---|
1 | Energy saving |
2 | n/a |
3 | Temperature unit of measurement |
4 | Compressor |
5 | Defrost |
6 | Evaporator fan |
7 | n/a |
8 | Auxiliary |
9 | On or standby |
10 | SET key and keypad lock |
11 | ON/STANDBY key, escape, and cabinet light |
12 | DOWN key and additional functions menu |
13 | UP key and defrost |
Switching the device on or off
If POF = 1, tap the ON/STAND-BY key for 4 s.
If the device is switched on, the display shows the P5 value, cabinet
temperature by default.
If the display shows an alarm code, see ALARMS.
LED | ON | OFF | FLASHING |
---|---|---|---|
Compressor on | Compressor off |
- Compressor protection active
- Setpoint setting active
| Defrost or pre-dripping active| –|
- Defrost delay active
- Dripping active
| Evaporator fan on| Evaporator fan off| Evaporator fan stop active
|
- Alarm active
- Cabinet light on by key
| –| Cabinet light on by digital input
|
- If device on, energy saving active
- If device off, low consumption active
| –| –
****| View temperature| –| –
| Device off| Device on| Device on or off active
If 30 s have elapse and you do not press the keys, the display shows the “Loc” label and the keypad locks automatically.
Unlocking the keypad
Tap any key for 1 s. The display shows the label “UnL”.
Setting the setpoint
Check that the keypad is not locked.
1. | Tap the SET key. | |
---|---|---|
2. | Tap the UP or DOWN key within 15 s to set the value within the limits r1 |
and r2.
3.| | | | Tap the SET key or do not operate for 15 s.
Activating manual defrost (if r5 = 0, default)
Check that the keypad is not locked.
- Tap the UP key for 2 s.
If P4 = 1 (default), the defrost activates if the evaporator temperature is lower than the d2 threshold.
Turning the cabinet light on or off (if u0 = 3)
Tap the ON/STAND-BY key.
ADDITIONAL FUNCTIONS
Navigating the additional functions menu
Before you begin, check that the keypad is not locked.
1. | To access the additional functions menu, tap the DOWN key for 4 s. | |
---|---|---|
2. | To navigate to a label, tap the UP or DOWN key within 15 s. | |
3. | To select a label, tap the SET key. | |
4. | If you cannot edit the parameter, the value displays. |
If you can edit the parameter, tap the UP or DOWN key to navigate to the
value that you want.
5.| | | To set the parameter value, tap the SET key.
6.| | | To exit the procedure, tap the ON/STAND-BY key, or do not operate the
controller for 60 s.
Additional functions menu
Use the additional functions menu to cycle through the labels in the following
table.
LABEL | VALUE | DESCRIPTION |
---|---|---|
CH | View compressor functioning hours in hundreds | |
rCH | Delete compressor functioning hours | |
149 | Command to delete compressor functioning hours | |
Pb1 | Cabinet temperature | |
Pb2 | Auxiliary temperature |
SETTINGS
Setting configuration parameters
1. | Tap the SET key for 4 s. The display shows the label “ PA ”. | ||
---|---|---|---|
2. | Tap the SET key. | ||
3. | Tap the UP or DOWN key within 15 s to set the password. The default |
password is “-19”.
4.| | | | Tap the SET key or do not operate for 15 s. The display shows the
label “ SP ”.
5.| | Tap the UP or DOWN key to select a parameter.
6.| | Tap the SET key.
7.| | Tap the UP or DOWN key within 15 s to set the value.
8.| | | | Tap the SET key or do not operate for 15 s.
9.| | | Tap the SET key for 4 s, or do not operate for 60 s, to exit the
procedure.
Restoring the default factory settings and storing customized settings as default
Important
- Check that the factory settings are appropriate; see CONFIGURATION PARAMETERS.
- When you store customized settings, you overwrite the default.
1. | Tap the SET key for 4 s. The display shows the label “ PA ”. | |||
---|---|---|---|---|
2. | Tap the SET key. | |||
3. | Tap the UP or DOWN key within 15 s to set the value. | |||
VAL. | DESCRIPTION | |||
149 | Restores the default factory settings | |||
161 | Stores customized settings as default | |||
4. | Tap the SET key or do not operate for 15 s. The display shows the |
label “ dEF ” when you set the value “ 149 ” or the label “ MAP ”
when you set the value “ 161 ”.
5.| | Tap the SET key.
6.| | Tap the UP or DOWN key within 15 s to set “ 4 ”.
7.| | Tap the SET key or do not operate for 15 s. The display shows “– -”
flashing for 4 s, then the device exits the procedure.
---|---|---
8.| Interrupt the power supply to the device.
9.| | ****| | Tap the SET key 2 s before step 6. to exit the procedure
beforehand.
ALARMS
COD. | DESCRIPTION | RESET | REMEDIES |
---|---|---|---|
Pr1 | Cabinet probe alarm | Automatic | Check P0 |
Pr2 | Auxiliary probe alarm | Automatic | Check probe integrity |
Check electrical connection
AL| Low temperature alarm| Automatic| Check A1
AH| High temperature alarm| Automatic| Check A4
id| Open door alarm| Automatic| Check i0 and i1
COH| High condenser temperature warning| Automatic| Check C6
CSd| High condenser temperature alarm| Manual|
- Switch the device off and on
- Check C7
iA| Multi-purpose input alarm| Automatic| Check i0 and i1
dFd| Defrost timeout alarm| Manual|
- Tap any key
- Check d2, d3, and d11
ELECTRICAL RATINGS
Output | Units | cULus (UL 60730) | CE (EN 60730) |
---|---|---|---|
Applied voltage at 60 Hz | 120 VAC | 240 VAC | 240 VAC |
K1
compressor relay
| Resistive amperes| 12| 12| 10
Inductive amperes| —| —| 2
Full load amperes| 10| 10| —
Locked rotor amperes| 60| 60| —
K2
defrost or evaporator fan or
configurable relay
| Resistive amperes| 8| 8| 5
Inductive amperes| —| —| 2
Full load amperes| 4.4| 2.9| —
Locked rotor amperes| 26.4| 17.4| —
TECHNICAL SPECIFICATIONS
Purpose of the control device | Function controller |
---|---|
Construction of the control device | Built-in electronic device |
Container | Black, self-extinguishing |
Category of heat and fire resistance | D |
Measurements | 75 mm x 33 mm x 59 mm (2 15/16 in. x 1 5/16 in. x 2 5/16 in.) |
Mounting methods for the control device | Fit the controller to a panel with |
the snap-in brackets supplied
Degree of protection provided by the covering| IP65 in front
Connection method| Fixed screw terminal blocks for wires up to 2.5 mm²
Maximum permitted length for connection cables
Power supply: 10 m (32.8 ft)| Analog inputs: 10 m (32.8 ft)
Digital inputs: 10 m (32.8 ft)| Digital outputs: 10 m (32.8 ft)
Operating temperature| From 0°C to 55°C (from 32°F to 131°F)
Storage temperature| From -25°C to 70°C (from -13°F to 158°F)
Operating humidity| Relative humidity without condensate from 10% to 90%
Pollution status of the control device| 2
Compliance
Europe| Johnson Controls declares product compliance meets requirements of
EMC, LVD, and RoHS Directives.
USA| UL Recognized Component, SDFY2.SA516; FCC Part 15 Subpart B Class A
Canada| UL Recognized Component, SDFY8.SA516; ICES-003 Class A
Power supply| TC3B22N7x| 230 VAC (+10% -15%), 50/60 Hz (+/- 3Hz), max. 2 VA
Grounding methods for the control device| None
Rated impulse-withstand voltage| 4 KV
Over-voltage category| III
Software class and structure| A
Analog inputs| 2 for NTC probes (cabinet probe and auxiliary probe)
NTC probes| Sensor type| ß3435 (10 kohm at 25°C, 77°F)
Measurement field| -40°C to 105°C (-40°F to 221°F)
Resolution| 0.1°C (1°F)
Digital inputs| 1 dry contact (door switch/multi-purpose)
Dry contact| Contact type| 5 VDC, 1.5 mA
Power supply| None
Protection| None
Digital outputs| 2 electro-mechanical relays
Type 1 or Type 2 actions| Type 1
Additional features of Type 1 or Type 2 actions| C
Display| 3-digit custom display with function icons
PRODUCT WARRANTY
This product is covered by a limited warranty, details of which can be found at www.johnsoncontrols.com/buildingswarranty
SOFTWARE TERMS
Use of the software that is in (or constitutes) this product, or access to the cloud, or hosted services applicable to this product, if any, is subject to applicable end-user license, open-source software information, and other terms set forth at www.johnsoncontrols.com/techterms. Your use of this product constitutes an agreement to such terms.
SINGLE POINT OF CONTACT
APAC | Europe | NA/SA |
---|
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT
NO. 32 CHANGJIJANG RD NEW DISTRICT
WUXI JIANGSU PROVINCE 214028
CHINA
| JOHNSON CONTROLS WESTENDHOF 3
45143 ESSEN GERMANY
| JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
CONTACT INFORMATION
Contact your local branch office: www.johnsoncontrols.com/locations
Contact Johnson Controls: www.johnsoncontrols.com/contact-us
Important
The device must be disposed of according to local regulations governing the
collection of electrical and electronic waste.
This document and the solutions contained therein are the intellectual property of Penn and thus protected by the Italian Intellectual Property Rights Code (CPI). Penn imposes an absolute ban on the full or partial reproduction and disclosure of the content other than with the express approval of Penn. The customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the device. Penn accepts no liability for any possible errors in this document and reserves the right to make any changes, at any time without prejudice to the essential functional and safety features of the equipment.
Johnson Controls
507 E. Michigan St.
Milwaukee, WI 53202-5211
USA
www.penncontrols.com
References
- johnsoncontrols.com/buildingswarranty
- johnsoncontrols.com/contact-us
- johnsoncontrols.com/locations
- johnsoncontrols.com/techterms
- PENN
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>